01.09.2013 Views

P olyethylene Pin Type Insulators – T ie-Top ... - PROMELSA

P olyethylene Pin Type Insulators – T ie-Top ... - PROMELSA

P olyethylene Pin Type Insulators – T ie-Top ... - PROMELSA

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

OVERHEAD PRODUCTS<br />

P<strong>olyethylene</strong> <strong>Pin</strong> <strong>Type</strong> <strong>Insulators</strong> <strong>–</strong> T<strong>ie</strong>-<strong>Top</strong><br />

Description:<br />

Hendrix T<strong>ie</strong>-<strong>Top</strong> insulators are molded of propr<strong>ie</strong>tary, gray, track resistant, high density p<strong>olyethylene</strong>. They are ideal for<br />

use with covered conductors because the low d<strong>ie</strong>lectric constant matches that of Hendrix and other p<strong>olyethylene</strong> conductor<br />

insulating compounds. In addition, Hendrix T<strong>ie</strong>-<strong>Top</strong> insulators may be used with bare conductors. They are<br />

designed with standard ANSI neck sizes and will fit on standard 1” or 1 3/8” pins. <strong>Insulators</strong> are available with ratings<br />

of 15kV, 25kV or 35kV.<br />

Benefits:<br />

HPI-15 HPI-25 HPI-35<br />

• Electrically compatible with covered conductors - no stripping is required<br />

• Resistant to impact damage, breakage and vandalism<br />

• Excellent weather washing characteristics<br />

• Interchangeable with porcelain insulators<br />

• Excellent weatherability proven by 25 years of f<strong>ie</strong>ld exper<strong>ie</strong>nce<br />

• Designed for use with hand wrapped t<strong>ie</strong>s or preshaped t<strong>ie</strong>s<br />

• Light weight for easy handling<br />

• Excellent for contaminated environments<br />

Application:<br />

Hendrix T<strong>ie</strong>-<strong>Top</strong> insulators are recommended for use on spacer cable construction at angles and for open wire construction<br />

with either covered conductors or bare conductors. Using p<strong>olyethylene</strong> insulators avoids the problem<br />

of increased corona and the resulting erosion of covered conductors that can occur with porcelain insulators. Hendrix<br />

p<strong>olyethylene</strong> insulators are especially well suited to areas with a history of vandalism. Ballistics tests have shown that<br />

even with damage from rifle or shotgun fire, the insulators were still able to operate. Hendrix p<strong>olyethylene</strong> insulators<br />

are also excellent for contaminated environments due to their long leakage distance and washing characteristics.<br />

When using Hendrix T<strong>ie</strong>-<strong>Top</strong> insulators with covered conductors, a covered t<strong>ie</strong> wire is required to prevent erosion<br />

of the conductor covering. Hendrix thermoplastic rubber covered t<strong>ie</strong> wire is available for this purpose. When using<br />

Hendrix T<strong>ie</strong>-<strong>Top</strong> insulators with bare conductors, a bare t<strong>ie</strong> wire should be used.<br />

HPI insulator with covered conductor<br />

and covered t<strong>ie</strong> wire<br />

continued<br />

HPI insulator with bare conductor<br />

and bare t<strong>ie</strong> wire<br />

A3 P<strong>olyethylene</strong> <strong>Pin</strong> <strong>Type</strong> <strong>Insulators</strong> <strong>–</strong> T<strong>ie</strong>-<strong>Top</strong> A3


OVERHEAD PRODUCTS<br />

P<strong>olyethylene</strong> <strong>Pin</strong> <strong>Type</strong> <strong>Insulators</strong> <strong>–</strong> Data<br />

B-1 Torque Bolt, HT-1 Hook Tool<br />

Electrical, Mechanical & Physical Data:<br />

Characteristic<br />

When ordering Vise-<strong>Top</strong> insulators, specify the suffix “P” for covered conductors and bare copper conductors<br />

or “M” for bare aluminum conductors.<br />

* Different pin hole diameters and thread configurations to meet international standards are available upon request.<br />

**Rev<strong>ie</strong>w design performance data before using on bare wire systems.<br />

B-1 Torque Bolt:<br />

The B-1 torque bolt may be purchased<br />

separately for replacement purposes. It<br />

is made of black nylon and is designed<br />

to be tightened using the break-away ring.<br />

This ensures proper gripping force on<br />

the conductor. The B-1 torque bolt fits<br />

all Vise-<strong>Top</strong> insulators. A new torque<br />

bolt should be used when a conductor<br />

is removed and re-installed in an insulator.<br />

Catalog No.: B-1<br />

Weight: 5.0 lbs/50 p<strong>ie</strong>ces<br />

Length: 6 1 ⁄2"<br />

Material: Black Nylon<br />

HPI-15F HPI-15 HPI-25 HPI-25-02 HPI-35** HPI-35-02**<br />

HPI-15VT HPI-25VT HPI-25VT-02 HPI-35VT** HPI-35VT-02**<br />

Typical Application, kV 15 15 25 25 35 35<br />

ANSI Class 55-4 55-3 55-5 55-5 55-6 55-6<br />

Leakage Distance, inches 11 3 ⁄4 12 13 3 ⁄4 13 3 ⁄4 21 21<br />

Dry Arcing Distance, inches 6 6 1 ⁄4 7 1 ⁄2 7 1 ⁄2 9 1 ⁄2 9 1 ⁄2<br />

<strong>Pin</strong> Hole Diameter, inches* 1 1 1 1 3 ⁄8 1 1 3 ⁄8<br />

Minimum <strong>Pin</strong> Length, inches 6 6 6 6 6 6<br />

60Hz. Dry Flashover, kV 69 77 94 94 110 110<br />

60Hz. Wet Flashover, kV 44 46 52 52 63 63<br />

Positive Impulse Flashover, kV 128 130 150 150 184 184<br />

Negative Impulse Flashover, kV 175 176 182 182 250 250<br />

Low Frequency Puncture, kV 215 195 220 190 220 190<br />

RIV @1mhz.<br />

10kV to grd, mV 0 0 0 0 0 0<br />

15kV to grd, mV - - 0 0 0 0<br />

22kV to grd, mV - - - - 850 850<br />

Cantilever Strength, lbs. 3,000 3,000 3,000 3,000 3,000 3,000<br />

Dimensions, inches<br />

Plain <strong>Top</strong> / Vise-<strong>Top</strong> A 5 1 ⁄4 5 1 ⁄4 / 8 1 ⁄4 5 1 ⁄2 / 8 5 ⁄8 5 1 ⁄2 / 8 5 ⁄8 7 1 ⁄8 / 10 3 ⁄8 7 1 ⁄8 / 10 3 ⁄8<br />

B 5 1 ⁄2 5 1 ⁄2 / 5 1 ⁄2 7 1 ⁄2 / 7 1 ⁄2 7 1 ⁄2 / 7 1 ⁄2 7 1 ⁄2 / 7 1 ⁄2 7 1 ⁄2 / 7 1 ⁄2<br />

C 3 7 ⁄8 3 7 ⁄8 / 3 7 ⁄8 4 / 4 4 / 4 5 1 ⁄2 / 5 1 ⁄2 5 1 ⁄2 / 5 1 ⁄2<br />

D 2 7 ⁄8 2 1 ⁄4 / 2 1 ⁄4 2 7 ⁄8 / 3 2 7 ⁄8 / 3 2 7 ⁄8 / 3 2 7 ⁄8 / 3<br />

E 1 3 ⁄4 / N/A 1/ N/A 1 / N/A 1 / N/A 1 / N/A<br />

F<br />

3 ⁄4<br />

3 ⁄4 / N/A 7 ⁄8 / N/A 7 ⁄8 / N/A 7 ⁄8 / N/A 7 ⁄8 / N/A<br />

Max. Conductor, Vise-<strong>Top</strong>, inches N/A 1.75 1.75 1.75 1.75 1.75<br />

Weight, lbs. 1.5 1.3 2.0 2.0 2.6 2.6<br />

Neck Style F C F F F F<br />

Maximum continuous 120 120 120 120 120 120<br />

conductor operating temp., °C<br />

HT-1 Hook Tool:<br />

The HT-1 Hook Tool is for quick<br />

tightening of the Torque Bolts on<br />

Vise-<strong>Top</strong> <strong>Insulators</strong> on de-energized<br />

circuits. It snaps into most hydraulic<br />

impact wrenches and other tools<br />

used in aerial bucket trucks. The tool<br />

should be operated at slow speed.<br />

Catalog No.: HT-1<br />

Size: 7/16 “ Hex<br />

Length: 6 3 ⁄8"<br />

Material: Aluminum<br />

C<br />

C<br />

D<br />

D<br />

E<br />

B<br />

B<br />

F<br />

T<strong>ie</strong>-<strong>Top</strong> Insulator<br />

Vise-<strong>Top</strong> Insulator<br />

A<br />

A<br />

A3<br />

P<strong>olyethylene</strong> <strong>Pin</strong> <strong>Type</strong> <strong>Insulators</strong> <strong>–</strong> Data<br />

B-1 Torque Bolt, HT-1 Hook Tool<br />

A3


A3<br />

P<strong>olyethylene</strong> <strong>Pin</strong> <strong>Type</strong> <strong>Insulators</strong> <strong>–</strong> Vise-<strong>Top</strong><br />

A3<br />

P<strong>olyethylene</strong> <strong>Pin</strong> <strong>Type</strong> <strong>Insulators</strong> <strong>–</strong> Vise-<strong>Top</strong><br />

Description:<br />

Hendrix Vise-<strong>Top</strong> insulators are a labor saving alternative to T<strong>ie</strong>-<strong>Top</strong> insulators. When used with the VTST-1 Stringing<br />

Tool, conductors can be installed without separate stringing blocks. The built-in clamp secures the conductor in the top<br />

or side position, eliminating the need for t<strong>ie</strong> wire. Vise-<strong>Top</strong> insulators are molded of propr<strong>ie</strong>tary gray, track resistant,<br />

high density p<strong>olyethylene</strong>. They are ideal for use with covered conductors because the low d<strong>ie</strong>lectric constant of the<br />

p<strong>olyethylene</strong> matches that of Hendrix and other p<strong>olyethylene</strong> insulating compounds. In addition, Hendrix offers<br />

Vise-<strong>Top</strong> insulators with aluminum clamping inserts for use with bare conductors. They are designed to fit on standard<br />

1” or 1 3/8” pins. <strong>Insulators</strong> are available with ratings of 15kV, 25kV or 35kV.<br />

Benefits:<br />

HPI-15VTP HPI-25VTP<br />

• Quick and easy installation using two torque bolts<br />

• Torque bolt ring breaks off at a predetermined torque<br />

to provide proper clamping force<br />

• Insulator acts as a stringing block when used with the<br />

VTST-1 stringing tool, significantly reducing installation costs<br />

• Electrically compatible with covered conductors,<br />

no stripping is required<br />

• Resistant to impact damage, breakage and vandalism<br />

• Excellent weather washing characteristics<br />

• Interchangeable with porcelain insulators<br />

• Excellent weatherability proven by 25 years of f<strong>ie</strong>ld exper<strong>ie</strong>nce<br />

• Light weight for easy handling<br />

• Excellent for contaminated environments<br />

OVERHEAD PRODUCTS<br />

Application:<br />

Hendrix p<strong>olyethylene</strong> insulators are recommended for use on spacer cable construction at angles and for open<br />

wire construction with either covered conductors or bare conductors. Using p<strong>olyethylene</strong> insulators avoids the problems of<br />

increased corona and the resulting erosion of covered conductors that can occur with porcelain insulators. Hendrix<br />

p<strong>olyethylene</strong> insulators are especially well suited to areas with a history of vandalism. Ballistics tests have shown<br />

that even with damage from rifle or shotgun fire, the insulators were still able to operate. Hendrix p<strong>olyethylene</strong> insulators<br />

are also excellent for contaminated environments due to their long leakage distance and washing characteristics.<br />

There are two types of Vise-<strong>Top</strong> insulators. One type has nylon clamping inserts for covered conductors and<br />

bare copper conductors. The other type has aluminum clamping inserts for bare aluminum conductors. To specify<br />

Vise-<strong>Top</strong> insulators with nylon clamping inserts, add the suffix “P” (ex. HPI-15 VTP). For metal clamping inserts, add<br />

the suffix ”M“ (ex. HPI-15VTM).<br />

Vise-<strong>Top</strong> with covered conductor<br />

and nylon insert<br />

continued<br />

Vise-<strong>Top</strong> used with a VTST-1 stringing tool<br />

Vise-<strong>Top</strong> with bare wire<br />

and aluminum insert<br />

HPI-35VTP