Christchurch which has its own residential feeder. There are no retail, commercial or<br />

industrial load on this feeder. It was selected to make it possible to compare the<br />

modelling results with the actual load measured by the utility.<br />

F 1 F 2 F 3 F 4 Lateral Line 1<br />

Residential<br />

Feeders<br />

Lateral Line 2<br />

Distribution<br />

Transformer<br />

Customers/<br />

H 1 H 2 H 3 ... H N<br />

Households<br />

A 1 A 2 A n Appliances<br />

A 1 A 2 A n A 1 A 2 An<br />

Figure 2: Illustration of the modelling approach for a group of customers<br />

Table 1: Maximum 30 minutes average diversified demand per customers (kW) for<br />

given number (n) of appliance [Gönen, 2008].<br />

Appliances n=1 n=5 n=10 n=20 n=40 n=80 n=100<br />

Direct Water Heater 1.1 0.37 0.22 0.18 0.14 0.1 0.1<br />

Heat Pump 4.50 3.00 3.00 2.80 2.80 2.80 2.80<br />

Electric Heater 7.00 4.00 3.50 3.20 3.20 3.20 3.20<br />

Cloth Dryer 4.30 1.80 1.50 1.20 1.00 1.00 1.00<br />

Home Freezer 0.30 0.13 0.10 0.08 0.08 0.08 0.08<br />

Refrigerator 0.18 0.07 0.06 0.05 0.05 0.05 0.05<br />

Range 2.30 0.90 0.70 0.60 0.50 0.50 0.50<br />

Lighting & Misc. 1.10 0.65 0.60 0.55 0.52 0.52 0.52<br />

The total number of each appliance category (n i ) was determined by multiplying the<br />

total number of households (m = 400 in this case) by the appliance saturation rates<br />

(s i ). The appliance saturation rates for New Zealand [Electricity-Commission, 2007]<br />

were used for the location. The saturation rate of heat pumps was taken from a recent<br />

BRANZ study [French, 2008] . The saturation rate of electric heaters was adjusted to<br />

reflect the situation at the Halswell area. Halswell is a relatively new suburb in<br />

Christchurch with high penetration of heat pumps. The saturation rate of electric<br />

heater is expected to be lower than the New Zealand average as space heating is done<br />

mainly with heat pumps. Table 2 Shows the average maximum diversified demand<br />

estimated for 400 households in Halswell, neighbourhood in Christchurch.<br />

Estimation of the hourly variation factor, fi(t)<br />

The hourly variation factors, fi(t) reveal the behaviour characteristics of appliance<br />

usage and depends on the living habits of the individuals in a particular location.<br />

These living habits in turn are affected by the socio-economic factors such as the<br />

number of occupants in the individual households, their age and income. The hourly<br />