Ex Signaling devices<br />

r =<br />

56 m<br />

max. signal<br />

reception<br />

range<br />

Sounder with speech reproduction 110 dB (A)<br />

BExA110 d/e<br />

IP 66<br />

IP 67<br />

Protection<br />

system<br />

+ 70 °C<br />

- 50 °C<br />

Operating<br />

temperature<br />

Electrical data BExA110 d/e<br />

Rated voltage 230 V AC 115 V AC 24 V DC<br />

Rated frequency 50 Hz / 60 Hz 50 Hz / 60 Hz<br />

• text individually programmable without programming device (integrated<br />

microphone)<br />

• max. 16 seconds speech reproduction<br />

• 9 different tones (DIN tone), UKOOA/PFEER conformant<br />

• volume control up to 20 dB (A) via potentiometer<br />

• combination of tone/spoken message<br />

• also available as categories 2D & 3D (Zones 21 & 22) for dust zones<br />

• precise defi nition of alarms and warnings<br />

• low power consumption, hence long alarm using emergency power<br />

• suitable for UPS systems due to 24 V rated voltage<br />

• no PA system required for speech reproduction<br />

• stainless steel mounting bracket for 360° positioning<br />

• protected against pole-reversal<br />

• surface coating has good resistance to most acids, alkalis and oils<br />

Operating range ± 10 % ± 10 % ± 25 %<br />

Power consumption at maximum volume 45 mA 90 mA 480 mA<br />

Mechanical data BExA110 d BExA110 de<br />

Protection system IP 67 IP 66<br />

Explosion protection<br />

II 2G EEx d IIC T4 / II 2G EEx de IIC T4<br />

II 2G EEx d IIB T4 / II 2G EEx de IIB T4<br />

Category (area of use)<br />

2G (Zone 1)<br />

3G (Zone 2)<br />

Certificate of conformity KEMA 99 ATEX 7906<br />

Testing body<br />

KEMA<br />

Sound pressure level distance 1 m 110 dB (A) ± 3 dB (A) – speech reproduction 5 dB (A) lower<br />

Temperature class T<br />

IIC: T4 @ - 50 °C ... + 55 °C Ta<br />

IIB: T4 @ - 50 °C ... + 70 °C Ta<br />

Storage temperature - 50 °C … + 70 °C<br />

Relative humidity 90 %<br />

Duty cycle 100 %<br />

Material<br />

housing die-cast aluminium LM6, similar to RAL 3000 (fl ame red)<br />

horn ABS self-extinguishing, similar to UL 94 VO & 5VA FR ABS, Ex II 2D anti-static ABS, black<br />

Connecting terminals<br />

AC 2 x 1.5 mm 2<br />

DC 1 x 4 mm 2 or 2 x 2.5 mm 2<br />

Cable entry 2 / 1 x closed, 1 x open (M20), optionally PG13.5 or 1/2“ NPT<br />

Weight<br />

AC 3.4 kg 3.7 kg<br />

DC 3.2 kg 3.4 kg<br />