Makeup Air Specifications<br />

Displacement Diffusers<br />

To maintain a neutral pressure of zero between the inside and outside of the laboratory,<br />

replacement air was supplied through fourteen floor-mounted displacement diffusers to either<br />

supplement the difference between the local makeup air and exhaust rate or entirely supply the<br />

laboratory when local makeup air was not in operation. These diffusers were located as far away<br />

as possible from the hood, with seven in the front system and seven in the rear system. The<br />

diffusers were balanced left-to-right across each system and each system was then balanced to<br />

ensure similar airflow from each side of the laboratory. The intention was to emulate transfer air<br />

from adjoining spaces and provide a low-velocity air supply, which has been proven to minimize<br />

the influence of replacement air on hood performance. The front system is shown in Figure 16.<br />

Figure 16. Floor Mounted Displacement Diffusers as Used to Supply Makeup Air<br />

2-15<br />

RP-<strong>1480</strong>