Evaluation of Side Panels<br />

The effect of installing side panels on hood capture and containment performance was evaluated<br />

using the heavy-duty (three broiler) and combination-duty (fryer, broiler, oven) appliance lines.<br />

Various makeup air strategies were also used to quantify the effect of makeup air with the hood<br />

partition installed, including displacement, 4-way ceiling diffuser, and perforated perimeter<br />

supply systems.<br />

While every effort was made to evaluate each supply air strategy in a fair manner, a feature of<br />

the laboratory layout may have caused understated performance for side panel installation. Since<br />

displacement air was supplied in line with the front and rear of the hood and air was not supplied<br />

from either the left or right of the hood, the displacement ventilation system saw the edge of the<br />

side panels rather than the surface. Due to this layout, the results may understate the performance<br />

improvement found in the field for side panels with air supplied from other directions.<br />

3-7<br />