Evaluation of Appliance Duty with respect to Makeup Air Configuration<br />

Sensitivity of appliance duty was evaluated with one of two appliance line configurations: the<br />

heavy-duty (three broiler) line, or the combination-duty (fryer, broiler, oven) line. These<br />

comparisons were made with three makeup air strategies available, displacement, 4-way ceiling<br />

diffuser, and 4-sided perforated plenum supply. The results are shown graphically in Figure 29.<br />

10000<br />

> 9000 > 9000<br />

8600<br />

Exhaust Airflow Rate [cfm]<br />

8000<br />

6000<br />

4000<br />

4900<br />

5600<br />

7400<br />

7600<br />

7800<br />

2000<br />

0<br />

Combo(F,B,O)<br />

Displacement<br />

Front & Back<br />

102<br />

Combo(F,B,O)<br />

PPS<br />

4 Side<br />

80 cfm/ft<br />

of PPS<br />

119<br />

Heavy(3Broilers)<br />

Displacement<br />

Front & Back<br />

101<br />

Heavy(3Broilers)<br />

PPS<br />

4 Side<br />

80 cfm/ft<br />

of PPS<br />

123<br />

Heavy(3Broilers)<br />

4-Way Diffuser<br />

Front & Side<br />

2000 cfm<br />

(1000 cfm each)<br />

114<br />

Heavy(3Broilers)<br />

PPS<br />

4 Side<br />

160 cfm/ft<br />

of PPS<br />

122<br />

Combo(F,B,O)<br />

PPS<br />

4 Side<br />

160 cfm/ft<br />

of PPS<br />

118<br />

Combo(F,B,O)<br />

4-Way Diffuser<br />

Front & Side<br />

2000 cfm<br />

(1000 cfm each)<br />

110<br />

Figure 29. Evaluation of Appliance Line Duty and Makeup Air Configuration<br />

With displacement ventilation, the combination-duty appliance line required 4,900 cfm (490<br />

cfm/ft) and the heavy-duty appliance line required 7,400 cfm (740 cfm/ft). With displacement<br />

ventilation, the heavy-duty line required a 2,500 cfm (250 cfm/ft) increase from the combinationduty<br />

appliance line’s exhaust rate.<br />

With the front and right side 4-way ceiling diffusers each supplying 1,000 cfm for a total of<br />

2,000 cfm of locally supplied makeup air, the combination-duty appliance line required over<br />

9,000 cfm (900 cfm/ft) and the heavy-duty appliance line required 7,800 cfm (780 cfm/ft). With<br />

this local makeup air configuration, the heavy-duty line required at least 1,200 cfm (120 cfm/ft)<br />

less than the combination-duty appliance line’s exhaust rate. The 4-way diffusers created<br />

turbulence around the hood, which had a great impact on the combination-duty line’s required<br />

3-5<br />

RP-<strong>1480</strong>