02.03.2014 Views

UK 22125702 Large TSL - Ingersoll Rand

UK 22125702 Large TSL - Ingersoll Rand

UK 22125702 Large TSL - Ingersoll Rand

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Technical Specifications<br />

Model<br />

Nominal Air Flow<br />

m 3 /min<br />

cfm<br />

Air<br />

Connections<br />

DN/PN<br />

Water<br />

Connections<br />

inch<br />

Dimensions (mm)<br />

A B C<br />

Weight<br />

kg<br />

AIRCOOLED VERSION<br />

<strong>TSL</strong> 130A 130 4591 150/10 - 4000 960 1740 780<br />

<strong>TSL</strong> 170A 170 6004 200/10 - 4085 1150 2150 1290<br />

<strong>TSL</strong> 225A 225 7946 200/10 - 4130 1150 2150 1380<br />

WATERCOOLED VERSION<br />

<strong>TSL</strong> 130W 130 4591 150/10 1” 4000 755 1670 750<br />

<strong>TSL</strong> 170W 170 6004 200/10 1 1 Ú2 “ 4085 927 1710 1200<br />

<strong>TSL</strong> 225W 225 7946 200/10 1 1 Ú2 “ 4130 1120 1750 1350<br />

<strong>TSL</strong> 280W 280 9888 250/10 1 1 Ú2 “ 5125 1190 1840 1450<br />

<strong>TSL</strong> 350W 350 12361 300/10 1 1 Ú2 “ 5135 1240 1915 1620<br />

Performances refer to air suction of FAD 20°C, 1 bar, and the following operating conditions: air suction 25°C/60%RH, 7 barg<br />

working pressure, 3°C pressure dew point, 25°C condenser cooling media temperature, 40°C condensing temperature, 35°C<br />

compressed air inlet temperature. All indicated data refers to DIN ISO 7183. All models supplied with refrigerant R407C and for<br />

operation up to 10 barg. 50 Hz models supplied with 400/3/50 power supply. 60 Hz models also available. IP Rating IP54.<br />

Multiplication Factors for Working Pressure up to maximum:<br />

Pressure bar g 3 4 5 6 7 8 9 10<br />

Correction Factor 0.64 0.76 0.86 0.94 1.00 1.06 1.10 1.13<br />

Multiplication Factors for Inlet Temperatures up to maximum:<br />

°C 30 35 40 45 50 55 60 65<br />

Correction Factor 1.20 1.00 0.82 0.68 0.56 0.46 0.44 0.42<br />

Multiplication Factors for Dewpoint<br />

°C 3 5 7<br />

Correction Factor 1.00 1.14 1.19<br />

Multiplication Factors Ambient Temperatures up to maximum:<br />

°C 20 25 30 35 40 46<br />

Correction Factor 1.02 1.00 0.98 0.93 0.87 0.80<br />

Example:<br />

Ambient Temperature 30ºC (correction factor 0.98)<br />

Inlet Temperature 40ºC (correction factor 0.82)<br />

System Pressure 6 bar g (correction factor 0.94)<br />

Pressure Dewpoint 3ºC (correction factor 1.0)<br />

Flow Rate<br />

98m 3 /min<br />

98m 3 /min<br />

0.98 x 0.82 x 0.94 x 1.0<br />

Therfore select <strong>TSL</strong> 130<br />

= 128.9m 3 /min<br />

B<br />

C<br />

6<br />

A

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!