Specification: Fabric<strong>Air</strong> ® <strong>Trevira</strong> <strong>CS</strong> <strong>100</strong> – <strong>NozzFlow</strong><br />
Division 15, Section 15800<br />
2005 Master Spec Format (Section/Category): 23 37 16<br />
PART 1 - GENERAL<br />
1.1 DESCRIPTION OF WORK<br />
a. Non-metal ductwork as indicated on drawings and by requirements of this section.<br />
b. Required type of non-metal ductwork for this project is a: Fabric <strong>Air</strong> Dispersion System.<br />
1.2 QUALITY ASSURANCE AND CODE COMPLIANCE<br />
a. Quality Assurance:<br />
1. Manufacturer must be a UL Registered Firm.<br />
2. Any production facility used by manufacturer must be Registered by Underwriters Laboratories<br />
Inc. to the International Organization for Standardization (ISO) 9000 Series Standards<br />
3. Fabrics used must be produced in environmental friendly factories only. The actual production<br />
site for each individual fabric must be Oeko-Tex certified by Oeko-Tex International –<br />
Association for the Assessment of Environmental Friendly Textiles.<br />
b. Codes and Standards:<br />
1. Product must be classified in accordance with the 25/50 flame spread/smoke development<br />
requirements of UL723 based on NFPA 90A - 1993, "Installation of <strong>Air</strong> Conditioning and<br />
Ventilating Systems". In addition products must be classified in accordance with ICC Evaluation<br />
Service AC167 and UL 2518.<br />
1.3 SUBMITTALS<br />
a. Submit copy of UL Registered Firm certificate and ISO 9001 certificate from production facility.<br />
b. Submit UL file number under which product is Classified by Underwriter’s Laboratories to UL723<br />
(NFPA 90), ICC AC167 and UL 2518.<br />
c. Submit manufacturer's drawings indicating size and placement of dispersion units, and mounting<br />
instructions.<br />
d. Submit manufacturer’s technical product data for fabric dispersion units.<br />
e. Submit manufacturer's performance data for each fabric duct system, including airflow rate, inlet<br />
velocity, static pressure and exit velocity out of duct system.<br />
f. Submit manufacturer’s maintenance data<br />
1.4 WARRANTY<br />
a. Manufacturer must provide a 10 Year Non-Prorated Warranty. Prorated warranties are not accepted.<br />
1.5 DELIVERY, STORAGE AND HANDELING<br />
a. Protect Fabric<strong>Air</strong> ® systems from damage during shipping, storage and handling.<br />
b. Store products inside and protect from weather.<br />
Fabric<strong>Air</strong> ® <strong>Trevira</strong> <strong>CS</strong> <strong>100</strong> - <strong>NozzFlow</strong> Last up-date: 06/2011<br />
Specification guidelines for Fabric<strong>Air</strong> ® products – subject to change without further notice. Page 1 of 5<br />
For more information, contact: Fabric<strong>Air</strong>, Inc.: info@fabricair.com or Phone: (502) 493 2210
Specification: Fabric<strong>Air</strong> ® <strong>Trevira</strong> <strong>CS</strong> <strong>100</strong> – <strong>NozzFlow</strong><br />
Division 15, Section 15800<br />
2005 Master Spec Format (Section/Category): 23 37 16<br />
PART 2 - PRODUCTS<br />
2.1 MANUFACTURER<br />
a. Manufacturer must comply with all previous described requirements. Approved manufacturers:<br />
1. Fabric<strong>Air</strong>, Inc.<br />
312-A Swanson Drive<br />
Lawrenceville, GA 30043<br />
Phone: (502) 493 2210<br />
Fax: (502) 493 4002<br />
E-mail: @fabricair.<br />
2.2 FABRIC AIR DISPERSION SYSTEM<br />
a. Fabricair Dispersion System shall be constructed of Fabric<strong>Air</strong> ® <strong>Trevira</strong> <strong>CS</strong> <strong>100</strong> fabric. The fabric is a<br />
woven fire retardant and permeable fabric complying with the following characteristics:<br />
1. Fabric: <strong>100</strong>% Permanent Flame Retardant Polyester<br />
2. Weight: 7.2 oz./yd² per ASTM D3776<br />
3. Shrinkage: Max. 0,5% per DIN EN 26 630<br />
4. Color: <strong>100</strong>0 white. <strong>100</strong>1 Blue, <strong>100</strong>2 Orange, <strong>100</strong>3 Gray, <strong>100</strong>4 Black, <strong>100</strong>5 Red or custom<br />
5. Temperature Range: -40°F to +140°F<br />
6. Permeabilities: per design: 2,11,18,36 or 66 (+/- 5%) per ASTM D737, Frazier – calandering of<br />
fabric NOT accepted<br />
7. Fire Retardancy: Must meet the requirements in NFPA 90-A, ICC AC167 and UL 2518<br />
b. SYSTEMS FABRICATION REQUIREMENTS<br />
1. <strong>Air</strong> dispersion accomplished by using conical aerodynamic nozzles. Diameter of nozzles to be<br />
¾” – height to be minimum ½”. Due to exact requirements of throw and maximum level of noise<br />
alternative flow models are not acceptable.<br />
2. Color of nozzles must match color of fabric. Unless otherwise specifically mentioned on<br />
drawings or otherwise in this specification suppliers standard table is used for selection of color.<br />
3. Location and number of nozzles to be specified and approved by manufacturer<br />
4. The system is made of permeable fabric. Permeability of fabric must be reached based on<br />
weave construction only and weave must have gone through thermo fixation in order to secure<br />
same permeability after wash. Fabric with permeability obtained based on calandering is not<br />
accepted.<br />
5. Fibers used must be permanently fire retardant – fire-reducing treatments are not accepted.<br />
6. Provide system in sections optimized for maintenance, connected by zippers. Zippers must<br />
provide closure completely around the circumference to prevent leakage. Required number of<br />
zippers as specified by manufacturer.<br />
7. Each section to have a unique tag including information about: manufacturers order number,<br />
position, diameter of section, length of section, maintenance instruction, code compliance and<br />
contact details for spare parts.<br />
8. Fabric system shall include connectors to attach to suspension system listed below.<br />
Fabric<strong>Air</strong> ® <strong>Trevira</strong> <strong>CS</strong> <strong>100</strong> - <strong>NozzFlow</strong> Last up-date: 06/2011<br />
Specification guidelines for Fabric<strong>Air</strong> ® products – subject to change without further notice. Page 2 of 5<br />
For more information, contact: Fabric<strong>Air</strong>, Inc.: info@fabricair.com or Phone: (502) 493 2210
Specification: Fabric<strong>Air</strong> ® <strong>Trevira</strong> <strong>CS</strong> <strong>100</strong> – <strong>NozzFlow</strong><br />
Division 15, Section 15800<br />
2005 Master Spec Format (Section/Category): 23 37 16<br />
c. DESIGN PARAMETERS<br />
1. Use fabric air diffusers only for positive pressure air distribution.<br />
2. Do not use fabric air diffusers in concealed locations.<br />
3. Fabric diffusers shall be designed from minimum 0.25” water gage to 3” as the maximum – 0.5”<br />
being the standard.<br />
4. Design temperatures between –40°F and 140°F<br />
5. Manufacturer shall approve all technical design parameters.<br />
d. HANGERS AND SUPPORT (must specify only one of the below system types)<br />
1. Type 1: One row cable system located 1.5” above 12 o’clock of Fabric<strong>Air</strong> ® system. Fabric<strong>Air</strong> ®<br />
system to be attached to hardware using one single row of plastic hooks located 12 o’clock<br />
spaced 20 inches. Hardware to include cable, cable clamps, turnbuckles, and tie down straps as<br />
required.<br />
Hardware options – (please select one)<br />
a. Plastic Coated Stainless Steel Cable – all other components Stainless Steel<br />
b. Stainless Steel Cable – all other components Stainless Steel<br />
c. Plastic Coated Galvanized Cable – all other components Galvanized Steel<br />
2. Type 2: Two rows cable system located 1.5” above 3 & 9 o’clock of Fabric<strong>Air</strong> ® system.<br />
Fabric<strong>Air</strong> ® system to be attached to hardware using two rows of plastic hooks located 3 & 9<br />
o’clock spaced 20 inches. Hardware to include cable, cable clamps, turnbuckles, and tie down<br />
straps as required.<br />
Hardware options – (please select one)<br />
a. Plastic Coated Stainless Steel Cable – all other components Stainless Steel<br />
b. Stainless Steel Cable – all other components Stainless Steel<br />
c. Plastic Coated Galvanized Cable – all other components Galvanized Steel<br />
3. Type 3: One row T-rail system fixed directly to ceiling. Hardware to include tie down strap, T-rail<br />
and end lock T-rail as required. Fabric<strong>Air</strong> ® system to be attached to hardware using one single<br />
row of plastic sliders located 12 o’clock spaced 20 inches.<br />
Hardware options – (please select one)<br />
a. Aluminum Rails – all other components Stainless Steel<br />
b. Aluminum Rails – all other components Galvanized Steel<br />
4. Type 4: Two rows T-rail system fixed directly to ceiling. Hardware to include tie down strap, T-<br />
rail and end lock T-rail as required. Fabric<strong>Air</strong> ® system to be attached to hardware using two rows<br />
of plastic sliders located 3 & 9 o’clock spaced 20 inches.<br />
Hardware options – (please select one)<br />
a. Aluminum Rails – all other components Stainless Steel<br />
b. Aluminum Rails – all other components Galvanized Steel<br />
Fabric<strong>Air</strong> ® <strong>Trevira</strong> <strong>CS</strong> <strong>100</strong> - <strong>NozzFlow</strong> Last up-date: 06/2011<br />
Specification guidelines for Fabric<strong>Air</strong> ® products – subject to change without further notice. Page 3 of 5<br />
For more information, contact: Fabric<strong>Air</strong>, Inc.: info@fabricair.com or Phone: (502) 493 2210
Specification: Fabric<strong>Air</strong> ® <strong>Trevira</strong> <strong>CS</strong> <strong>100</strong> – <strong>NozzFlow</strong><br />
Division 15, Section 15800<br />
2005 Master Spec Format (Section/Category): 23 37 16<br />
5. Type 5: One row H-rail/spacer system located 1.5” above 12 o’clock of Fabric<strong>Air</strong> ® system.<br />
Hardware to include H-rail joint, end cap H-rail, spacer, fastener ceiling/H-rail, tie down strap<br />
and H-rail as required. Fabric<strong>Air</strong> ® system to be attached to hardware using one single row of<br />
plastic sliders located 12 o’clock spaced 20 inches.<br />
Hardware options – (please select one)<br />
a. Aluminum Rails – all other components Stainless Steel<br />
b. Aluminum Rails – all other components Galvanized Steel<br />
6. Type 6: Two rows H-rail/spacer system located 1.5” above 3 and 9 o’clock of Fabric<strong>Air</strong> ® system.<br />
Hardware to include H-rail joint, end cap H-rail, spacer, fastener ceiling/H-rail, tie down strap<br />
and H-rail as required. Fabric<strong>Air</strong> ® system to be attached to hardware using two rows of plastic<br />
sliders located 3 and 9 o’clock spaced 20 inches.<br />
Hardware options – (please select one)<br />
a. Aluminum Rails – all other components Stainless Steel<br />
b. Aluminum Rails – all other components Galvanized Steel<br />
7. Type 7: One row H-rail/spacer system located 1.5” above 12 o’clock of Fabric<strong>Air</strong> ® system.<br />
Hardware to include H-rail joint, end cap H-rail, spacer, fastener ceiling/H-rail, tie down strap<br />
and H-rail as required. Fabric<strong>Air</strong> ® system to be attached to hardware using one single row of<br />
bulb edge located 12 o’clock supported entire length.<br />
Hardware options – (please select one)<br />
a. Aluminum Rails – all other components Stainless Steel<br />
b. Aluminum Rails – all other components Galvanized Steel<br />
8. Type 8: One row H-rail/cable system located 1.5” above 12 o’clock of Fabric<strong>Air</strong> ® system.<br />
Hardware to include H-rail joint, eye bolt, end cap H-rail, cable, tie down strap and H-rail as<br />
required. Fabric<strong>Air</strong> ® system to be attached to hardware using one single row of plastic sliders<br />
located 12 o’clock spaced 20 inches.<br />
Hardware options – (please select one)<br />
a. Aluminum Rails – all other components Stainless Steel<br />
b. Aluminum Rails – all other components Galvanized Steel<br />
9. Type 11: Two rows T-rail/lock system fixed directly to ceiling. Hardware to include tie down<br />
strap, T-rail and locking profile as required. Fabric<strong>Air</strong> ® system to be attached to hardware using<br />
two rows of bulb edge located 3 & 9 o’clock.<br />
Hardware options – (please select one)<br />
a. Aluminum Rails – all other components Stainless Steel<br />
b. Aluminum Rails – all other components Galvanized Steel<br />
10. Type 12: Two rows T-rail system fixed directly to ceiling. Hardware to include tie down strap, T-<br />
rail and end lock as required. Fabric<strong>Air</strong> ® system to be attached to hardware using two rows of<br />
sliders located 3 & 9 o’clock.<br />
Fabric<strong>Air</strong> ® <strong>Trevira</strong> <strong>CS</strong> <strong>100</strong> - <strong>NozzFlow</strong> Last up-date: 06/2011<br />
Specification guidelines for Fabric<strong>Air</strong> ® products – subject to change without further notice. Page 4 of 5<br />
For more information, contact: Fabric<strong>Air</strong>, Inc.: info@fabricair.com or Phone: (502) 493 2210
Specification: Fabric<strong>Air</strong> ® <strong>Trevira</strong> <strong>CS</strong> <strong>100</strong> – <strong>NozzFlow</strong><br />
Division 15, Section 15800<br />
2005 Master Spec Format (Section/Category): 23 37 16<br />
Hardware options – (please select one)<br />
a. Aluminum Rails – all other components Stainless Steel<br />
b. Aluminum Rails – all other components Galvanized Steel<br />
11. Type 13: 2x1 (24” – 48”), two rows H-rail/curved rods system located 1.5” above 3 and 9 o’clock<br />
of Fabric<strong>Air</strong> ® system. Hardware to include H-rail joint, end cap H-rail, curved rods, fastener<br />
ceiling/H-rail, tie down strap, cable, cable locks and H-rail as required. Fabric<strong>Air</strong> ® system to be<br />
attached to hardware using two rows of plastic sliders located 3 and 9 o’clock spaced 20 inches.<br />
Hardware options – (please select one)<br />
a. Plastic Coated Stainless Steel Cable – all other components Stainless Steel or Aluminum<br />
b. Stainless Steel Cable – all other components Stainless Steel or Aluminum<br />
c. Plastic Coated Galvanized Cable – all other components Galvanized Steel or Aluminum<br />
2.3 AIR HANDLER REQUIREMENTS<br />
a. Provide adequate pre-filtering prior to the fabric duct system, all according to manufacturers<br />
specifications.<br />
b. Provide fans supplying constant static pressure.<br />
PART 3 - INSTALLATION<br />
3.1 INSTALLATION OF FABRICAIR ® SYSTEM<br />
a. Examine area and conditions under which the Fabric<strong>Air</strong> ® system are to be installed. Do not continue<br />
any installation until unsatisfactory conditions have been corrected.<br />
b. Install chosen suspension system in accordance with the requirements of the manufacturer. Installation<br />
instructions to be provided by the manufacturer with product.<br />
c. Coordinate layout with suspended ceiling, lighting layouts, and similar finished work.<br />
3.2 CLEANING<br />
a. Clean air handling unit and other ductwork prior to the Fabric<strong>Air</strong> ® system as it is installed. Make sure<br />
that all dust from installation are removed from the air handling unit and other ductwork before<br />
connecting the Fabric<strong>Air</strong> ® system.<br />
b. If the Fabric<strong>Air</strong> ® system becomes soiled during the installation, it should be removed and cleaned<br />
following the manufacturers cleaning instructions.<br />
END OF SECTION<br />
Fabric<strong>Air</strong> ® <strong>Trevira</strong> <strong>CS</strong> <strong>100</strong> - <strong>NozzFlow</strong> Last up-date: 06/2011<br />
Specification guidelines for Fabric<strong>Air</strong> ® products – subject to change without further notice. Page 5 of 5<br />
For more information, contact: Fabric<strong>Air</strong>, Inc.: info@fabricair.com or Phone: (502) 493 2210