Section 2 – <strong>Reliability</strong> Performance Measures<br />
<strong>Reliability</strong> Performance Indices<br />
The benchmarks and standards established by the <strong>Commission</strong> are based on four reliability performance<br />
indices which have been adopted by the Institute of Electrical and Electronic Engineers Inc. (IEEE).<br />
These indices include: (1) Customer Average Interruption Duration Index (CAIDI); (2) System Average<br />
Interruption Frequency Index (SAIFI); (3) System Average Interruption Duration Index (SAIDI); and<br />
(4) Momentary Average Interruption Frequency Index (MAIFI).<br />
• CAIDI is the average duration of sustained interruptions 17 for those customers who experience<br />
interruptions during the analysis period. CAIDI represents the average time required to restore<br />
service to the average customer per sustained interruption. It is determined by dividing the sum<br />
of all sustained customer interruption durations, in minutes, by the total number of interrupted<br />
customers;<br />
• SAIFI measures the average frequency of sustained interruptions per customer occurring during<br />
the analysis period. It is calculated by dividing the total number of sustained customer<br />
interruptions by the total number of customers served;<br />
• SAIDI is the average duration of sustained customer interruptions per customer occurring during<br />
the analysis period. It is the average time customers were without power. It is determined by<br />
dividing the sum of all sustained customer interruption durations, in minutes, by the total number<br />
of customers served. SAIDI is also the product of CAIDI and SAIFI; and<br />
• MAIFI measures the average frequency of momentary interruptions 18 per customer occurring<br />
during the analysis period. It is calculated by dividing the total number of momentary customer<br />
interruptions by the total number of customers served.<br />
The actual values of these four reliability indices are submitted by the EDCs on both a quarterly (rolling<br />
12-month average) and annual basis. Also included is the data used in calculating the indices, namely<br />
the average number of customers served, the number of sustained customer interruption minutes and the<br />
number of customers affected by service interruptions.<br />
It is noted that some EDCs do not currently have the necessary equipment to collect meaningful data<br />
relating to momentary service interruptions (MAIFI). However, the <strong>Commission</strong> desires to assess,<br />
where possible, the affect of frequent momentary interruptions on EDCs’ customers. Thus, the<br />
provision of this data is required, if available.<br />
In addition to the outage data mentioned above, the <strong>Commission</strong>’s regulations require EDCs to report a<br />
breakdown and analysis of outage causes, such as equipment failure, animal contact and contact with<br />
17 The loss of electric service by one or more customers for the period defined as a sustained customer interruption by the<br />
IEEE as it may change from time to time – currently five minutes or greater. The term does not include “major events” or the<br />
authorized termination of service to an individual customer.<br />
18 The loss of electric service by one or more customers for the period defined as a momentary customer interruption by the<br />
IEEE as it may change from time to time – currently less than five minutes. The term does not include “major events” or the<br />
authorized termination of service to an individual customer.<br />