Process<br />

automation<br />

HBSO · HBSC · HBSR<br />

LEVEL SENSORS FOR<br />

TOUGH ENVIRONMENTS<br />

Service minded split type...<br />

Operate in most<br />

types of Liquids<br />

Your Sensor Specialist<br />

www.hbproducts.dk<br />

It`s worth to use<br />

HB Products A/S<br />

as a partner when you<br />

requireindividual<br />

solutions


The HBS Level Switch/Sensor<br />

is designed <strong>for</strong> Long-Term function<br />

and detect most types of Liquids.<br />

Detect: Waste Water, Clean Water,<br />

all types of Refrigerant and all types of Oil.<br />

Designed <strong>for</strong> high and low pressure/<br />

temperature aplication.<br />

Split design <strong>for</strong> easy replacement of the<br />

electronic part.<br />

Process<br />

Automation<br />

Applications:<br />

• Automatic Oil control<br />

• Liquid <strong>level</strong> control<br />

• Alarm low and<br />

high Level<br />

• Compressor Proction<br />

• Water and brine<br />

systems<br />

Advantages:<br />

• High Pressure<br />

aplications<br />

• Replace Sight Glass<br />

• LED indication<br />

• No moving parts<br />

• Split type<br />

• Easy replacing<br />

It´s worth to use<br />

HB Products A/S as<br />

a partner when you<br />

require individual<br />

solutions.<br />

HBSC<br />

HBSO<br />

HBSR<br />

HBSX<br />

CO2<br />

OIL<br />

Water, NH3, HFC<br />

Custom type<br />

Note: Each type of HBS <strong>sensors</strong> have a data sheet <strong>for</strong><br />

further details/in<strong>for</strong>mations.<br />

Specifications:<br />

Power Supply:<br />

11 to 30V DC<br />

Current consumption: Max 5mA<br />

Output:<br />

Output current:<br />

Indicating:<br />

Media temp.:<br />

Ambiant temp.:<br />

Material sensorpart:<br />

ON/OFF, PNP or<br />

NPN, NO/NC<br />

Max 50mA<br />

Green or Red-LED,<br />

wet ON<br />

-56...to +100deg.C<br />

-25...to +60deg.C<br />

Stainless Steel<br />

AISI304/PTFE<br />

Mechan. Connection: 1/2” - 3/4” NPT,<br />

BSPT or BSPP<br />

EMC test:<br />

EN Industrial<br />

Vibration: IEC 68-2-6,<br />

4g 2 to 500Hz<br />

Pressure:<br />

Accessories:<br />

Max. 170bar.<br />

Ordering code:<br />

HBS_ - ___/ ___/ ____/ __/ _/_<br />

S = Spare electronic<br />

LED:<br />

R = RED<br />

G = GREEN<br />

Output function:<br />

NO = Normal open<br />

NC = Normal close<br />

(Fail Safe = NC)<br />

Thread type:<br />

NPT, BSPT<br />

BSPP<br />

Thread size:<br />

1/2" Only HBSO, Oil switch<br />

3/4" All types<br />

Output type:<br />

PNP<br />

NPN<br />

Media (liquid):<br />

C = CO2<br />

O1 = Oil switch type 1<br />

O2 = Oil switch type 2<br />

R = Water, NH3, HFC, (Conductive liquids)<br />

X = Custom type<br />

• HBPA Power adaptor plug, <strong>for</strong> easy connection to high voltage (switching solinoid valves directly)<br />

• ICE PROOF heater, recommended <strong>for</strong> low temperature operation (below -30° C)<br />

Your Sensor Specialist<br />

www.hbproducts.dk<br />

HBP Level Switch 03 091009