the enclosure, shall be provided as a safety measure. There shall be provision of<br />
proper illumination inside the enclosure to facilitate maintenance of the DG set.<br />
The insulating materials, such as rock wool/mineral wool etc. used for the<br />
purpose shall have high sound absorption quality, high temperature withstand and<br />
high fire retardant capability. It shall confirm to IS:8183 . Sound attenuators/down<br />
stream silencers may be provided at all opening for air inlet/outlet to facilitate flow of<br />
air with low noise.<br />
AMF PANEL :<br />
The panels shall be fabricated out of sheet steel and have hinged doors<br />
removable bottom gland plate, incoming & outgoing bus bar arrangement and<br />
required protections and metering arrangements. It shall be dust proof, vermin proof,<br />
totally enclosed suitable for indoor use with IP 41 class of protection. The cable facility<br />
shall be provided from bottom.<br />
The AMF panel shall consist of 2nos 630A, 36KA motorized MCCB complete<br />
with suitable spreader links & ROM. One MCCB shall be fed from the substation panle<br />
& the other from the alternator of DG set. The MCCB’s shall bee suitable for O/C,<br />
E/F, S/C protections with thermal adjustable type. Electrical interlocking shall be<br />
provided in-between the above to MCCB’s for AMF operation. Suitable arrangement &<br />
adequate clearance may be maintained for easy termination of 3nos 3 ½ c x 150sqmm<br />
armoured aluminium XLPE (E) cables with both the MCCB’s & outgoings. The control<br />
panels shall be complete with the arrangement for automatic ON/OFF of DG Sets.<br />
Following measuring instruments shall be fitted to the control panel.<br />
1. One number 3-Phase 4-Wire CT operated electronic KWH meter with required<br />
CT and sealing & locking arrangement in a separate tamper proof enclosure. It<br />
shall have a viewing window for taking the meter reading.<br />
2. One number 0-500 volt AC digital voltmeter with selector switch and control<br />
fuses.<br />
3. One number 0-250 Amp AC digital ammeter with required current transformers<br />
and selector switch.<br />
4. Auto / manual selection switch.<br />
5. Push buttons for Engine start, Engine stop, reset.<br />
6. Window fault annunciation for load on mains, load on set, set running, DC<br />
control on, start failure, overload, DC control ON, low oil pressure, high water<br />
temperature.<br />