the enclosure, shall be provided as a safety measure. There shall be provision of<br />

proper illumination inside the enclosure to facilitate maintenance of the DG set.<br />

The insulating materials, such as rock wool/mineral wool etc. used for the<br />

purpose shall have high sound absorption quality, high temperature withstand and<br />

high fire retardant capability. It shall confirm to IS:8183 . Sound attenuators/down<br />

stream silencers may be provided at all opening for air inlet/outlet to facilitate flow of<br />

air with low noise.<br />

AMF PANEL :<br />

The panels shall be fabricated out of sheet steel and have hinged doors<br />

removable bottom gland plate, incoming & outgoing bus bar arrangement and<br />

required protections and metering arrangements. It shall be dust proof, vermin proof,<br />

totally enclosed suitable for indoor use with IP 41 class of protection. The cable facility<br />

shall be provided from bottom.<br />

The AMF panel shall consist of 2nos 630A, 36KA motorized MCCB complete<br />

with suitable spreader links & ROM. One MCCB shall be fed from the substation panle<br />

& the other from the alternator of DG set. The MCCB’s shall bee suitable for O/C,<br />

E/F, S/C protections with thermal adjustable type. Electrical interlocking shall be<br />

provided in-between the above to MCCB’s for AMF operation. Suitable arrangement &<br />

adequate clearance may be maintained for easy termination of 3nos 3 ½ c x 150sqmm<br />

armoured aluminium XLPE (E) cables with both the MCCB’s & outgoings. The control<br />

panels shall be complete with the arrangement for automatic ON/OFF of DG Sets.<br />

Following measuring instruments shall be fitted to the control panel.<br />

1. One number 3-Phase 4-Wire CT operated electronic KWH meter with required<br />

CT and sealing & locking arrangement in a separate tamper proof enclosure. It<br />

shall have a viewing window for taking the meter reading.<br />

2. One number 0-500 volt AC digital voltmeter with selector switch and control<br />

fuses.<br />

3. One number 0-250 Amp AC digital ammeter with required current transformers<br />

and selector switch.<br />

4. Auto / manual selection switch.<br />

5. Push buttons for Engine start, Engine stop, reset.<br />

6. Window fault annunciation for load on mains, load on set, set running, DC<br />

control on, start failure, overload, DC control ON, low oil pressure, high water<br />

temperature.<br />

No. of Correction :<br />

No. of overwriting :<br />

Signature of the Contractor