<strong>ATyS</strong> M<br />

Three-phase and single-phase<br />

modular automatic transfer switch<br />

from 40 to 160 A


SOCOMEC:<br />

intelligent changeover systems<br />

As a worldwide leading company in changeover power<br />

solutions, SOCOMEC is introducing an innovative new<br />

changeover concept based on switch technology dedicated<br />

to replacement power supplies and single-phase or threephase<br />

safety from 40 to 160 A.<br />

<strong>ATyS</strong> M:<br />

fully integrated control and<br />

automatic changeover functions<br />

SOCOMEC has developed a new concept combining the<br />

benefits of switching technology and fast operation with<br />

unique control flexibility.<br />

<strong>ATyS</strong> M:<br />

a specific response<br />

to IEC or EN 60947-6-1<br />

changeover switching standards<br />

The new range of <strong>ATyS</strong> M changeover switching has been<br />

designed, tested and proven according to the criteria defined<br />

in the international product standards IEC 60947-3 and<br />

60947-6-1. Its compliance with this standard guarantees<br />

a quality product which meets switching and changeover<br />

applications requirements.<br />

APPLI 184 A<br />

A<br />

A<br />

230 VAC<br />

40 A 1323 4004<br />

63 A 1323 4006<br />

80 A 1323 4008<br />

100 A 1323 4010<br />

125 A 1323 4012<br />

160 A 1323 4016<br />

<strong>ATyS</strong> M 6e<br />

230 / 400 VAC<br />

40 A 1354 4004<br />

63 A 1354 4006<br />

80 A 1354 4008<br />

100 A 1354 4010<br />

125 A 1354 4012<br />

160 A 1354 4016<br />

127 / 230 VAC<br />

40 A 1353 4004<br />

63 A 1353 4006<br />

80 A 1353 4008<br />

100 A 1353 4010<br />

125 A 1353 4012<br />

160 A 1353 4016<br />

Without communication<br />

230 / 400 VAC<br />

40 A 1364 4004<br />

63 A 1364 4006<br />

80 A 1364 4008<br />

100 A 1364 4010<br />

125 A 1364 4012<br />

160 A 1364 4016<br />

127 / 230 VAC<br />

40 A 1363 4004<br />

63 A 1363 4006<br />

80 A 1363 4008<br />

100 A 1363 4010<br />

125 A 1363 4012<br />

160 A 1363 4016<br />

ATYSM 022 A<br />

With communication<br />

230 / 400 VAC<br />

40 A 1384 4004<br />

63 A 1384 4006<br />

80 A 1384 4008<br />

100 A 1384 4010<br />

125 A 1384 4012<br />

160 A 1384 4016<br />

127 / 230 VAC<br />

40 A 1383 4004<br />

63 A 1383 4006<br />

80 A 1383 4008<br />

100 A 1383 4010<br />

125 A 1383 4012<br />

160 A 1383 4016


ully integrated Normal / Backup function<br />

he best in breaking and control technology, dedicated to source switching<br />

WITCHING<br />

OPERATION<br />

MONITORING<br />

INSTALLATION<br />

wo mechanically interlocked<br />

ower switches.<br />

A configurable automatic control<br />

associated with a backup<br />

manual operation.<br />

A built-in configuration and<br />

control interface, simple or<br />

advanced.<br />

A modular product adapted to<br />

any type of enclosure integration.<br />

<strong>ATyS</strong> M 3s <strong>ATyS</strong> M 6s <strong>ATyS</strong> M 6e<br />

160 A<br />

ATYSM 200 A<br />

ATYSM 023 A<br />

ATYSM 201 A<br />

ATYSM 024 A<br />

ATYSM 022 A<br />

40 A<br />

Motorised changeover switch<br />

Dual power supply<br />

built-in control relay<br />

Communication*<br />

tripping**<br />

Specific version. ** Return to zero without external energy source.<br />

ocomec switching also includes<br />

An ATS bypass range<br />

Mains<br />

Backup<br />

> An extended <strong>ATyS</strong> range of ratings up<br />

to 3200 A*<br />

> SIRCOVER manual changeover range<br />

G<br />

From 40 to 160 A<br />

From 125 to 3200 A<br />

ø<br />

….....................<br />

ø<br />

SIRCO M 8 P SIRCOVER 8 P*<br />

ø<br />

ø<br />

ø<br />

ø<br />

...............................<br />

GAMME 148 A<br />

<strong>ATyS</strong> M<br />

<strong>ATyS</strong> 6e<br />

ø<br />

ø<br />

ATYS 102 B<br />

.............................<br />

* Also available as an enclosed product.<br />

SIRCO M<br />

changeover switch<br />

(I-0-II)<br />

SIRCOVER<br />

ø<br />

ø<br />

> A BYPASS range<br />

.........................................<br />

UPS<br />

SIRCO M<br />

changeover switch<br />

(I-0-II)<br />

SIRCOVER*<br />

* SIRCOVER Bypass<br />

12 + 4 pole<br />

SVR 059 A<br />

COMUT 034 A


Innovation dedicated to source switching<br />

An optimised breaking system<br />

> Choice of switching technology<br />

• An on load switch disconnector providing<br />

safety isolation combined with high<br />

making and breaking characteristics.<br />

• Safety isolation.<br />

• Stable positions.<br />

ATYSM 029 B<br />

A dedicated control interface<br />

> <strong>ATyS</strong> M 3s: motorised changeover with external control<br />

ATYSM 202 A<br />

> A new switching module combining<br />

• High dynamic withstand.<br />

• Fast operation.<br />

• High number of operations.<br />

ATYSM 038 A<br />

ATYSM 031 B<br />

> <strong>ATyS</strong> M 6s: automatic, simple and ergonomic motorised<br />

changeover<br />

Configurable automatic transfer switch cycles, with stable positions.<br />

> Two power switches<br />

Mechanically and electrically<br />

interlocked.<br />

> <strong>ATyS</strong> M 6e: advanced, programmable automatic motorised<br />

changeover<br />

Fully programmable automatic transfer switch cycles ensuring<br />

position stability or return to 0 position feature upon loss of network.<br />

SI<br />

SII<br />

ATYSM 002 B<br />

Ultra fast electrical control<br />

Automatic control logic<br />

> Electromagnetic control<br />

Allows extremely fast switching<br />

< 180 ms.<br />

Automatic mode (AUT)<br />

> An available energy storage<br />

device<br />

Enables the switch to return to 0<br />

position without any power source<br />

available (<strong>ATyS</strong> M 6e).<br />

Backup manual operation<br />

ATYSM 037 A<br />

Source 1 failure<br />

End “t” source 1 failure<br />

Generator start<br />

Source 2 availability<br />

End “t” source 2 availability<br />

Switch to position 0<br />

End “t” stop to position 0<br />

Switch to position II<br />

Switch to position I<br />

End “t” stop to position 0<br />

Switch to position 0<br />

no<br />

Semi automatic mode<br />

End “t” source 1 availability<br />

Source 1 availability<br />

Generator stop<br />

End “t” cool down timer before generator<br />

yes<br />

Manual<br />

operation<br />

Example (generator application):<br />

Source 1 : priority power source<br />

Source 2 : backup power source<br />

“t” : timer<br />

Flexible integration<br />

> Enclosed products<br />

ATYSM 015 B<br />

ATYSM 014 B<br />

ATYSM 203 A<br />

ATYSM 030 B<br />

ATYS 028 E GB<br />

ATYSM 016 B<br />

> Selection of<br />

Automatic / Manual<br />

operating mode<br />

via the protective<br />

sealable cover.<br />

> Backup manual<br />

operation using a<br />

standard allen key.<br />

> Padlocking function<br />

configurable in<br />

position 0 or in all<br />

three positions (I,<br />

0, II).<br />

IP54.<br />

ATYSM 196 A<br />

IP3x.<br />

Single-phase<br />

Three-phase<br />

ATys M 3s ATys M 6s ATys M 3s ATys M 6s ATys M 6e<br />

40 A 1823 2004 1854 2004 1823 4004 1854 4004 1884 4004<br />

63 A 1823 2006 1854 2006 1823 4006 1854 4006 1884 4006<br />

80 A 1823 2008 1854 2008 1823 4008 1854 4008 1884 4008<br />

100 A 1823 2010 1854 2010 1823 4010 1854 4010 1884 4010<br />

125 A 1823 2012 1854 2012 1823 4012 1854 4012 1884 4012<br />

160 A 1823 2016 1854 2016 1823 4016 1854 4016 1884 4016<br />

COFF 366 A


Switching for industrial, service sector and residential applications<br />

Six ratings 40 / 63 / 80 / 100 / 125 / 160 A<br />

2 or 4 pole versions<br />

<strong>ATyS</strong> M 3s <strong>ATyS</strong> M 6s <strong>ATyS</strong> M 6e<br />

Electrical operation I - 0 - II Automatic product Automatic product<br />

Applications<br />

Normal / Backup without automatic controller<br />

•<br />

Normal / Backup with built-in automatic controller • •<br />

Stable positions • • •<br />

Load changeover<br />

•<br />

FUNCTIONS<br />

Power supply<br />

External<br />

•<br />

Integrated • •<br />

Operation<br />

Backup manual operation of the 3 positions,<br />

configurable<br />

• • •<br />

Electrical (dry contact) control of positions I, 0<br />

and II<br />

• •*<br />

Automatic control of positions I, 0 and II • •<br />

Return to 0 position feature upon loss of source<br />

•<br />

Monitoring<br />

3 voltages on networks I and II • •<br />

Frequency on networks I and II • •<br />

Phase rotation on networks I and II<br />

•<br />

Asymmetry of networks I and II<br />

•<br />

Automatic controller configuration<br />

By potentiometer and micro-switch<br />

•<br />

By screen + keyboard<br />

•<br />

V n<br />

, F n<br />

, V threshold, F threshold • •<br />

Driving with or without priority • •<br />

Adjustable operating timers • •<br />

Control type (impulse or switch / contactor)<br />

•<br />

Display<br />

Position, fully visualised breaking • • •<br />

LED: source status, automatic mode, fault LED • •<br />

LED: switch positions, supply, tests, control<br />

•<br />

V, F, timers, number of operations, last event •<br />

REMOTE CONTROL<br />

Outputs<br />

Generator start / stop order • •<br />

Product availability<br />

(not fault and not manual mode)<br />

• •*<br />

Programmable output (source, availability, fault)<br />

•*<br />

Inputs<br />

Test on load • •*<br />

Retransfer • •*<br />

Automatic mode inhibit • •*<br />

Other programmable inputs<br />

(test off-load, position control, etc.)<br />

•*<br />

Remote control<br />

Human / Machine Interface (<strong>ATyS</strong> D10 and D20)<br />

•<br />

RS485 communication (JBUS / MODBUS)<br />

•**<br />

* 3 inputs / 3 outputs (programmable).<br />

** Product reference is different: communication by RS485 connection (JBUS/ MODBUS) allows up to 31 <strong>ATyS</strong> M to be connected to a PC or a PLC over 1500 m.<br />

A product for all power changeover applications from 40 to 160 A<br />

> Network / Genset<br />

• Controlled via the generator<br />

• ATS solution<br />

> Network / Network<br />

• Building services<br />

<strong>ATyS</strong> M 3s<br />

GS<br />

<strong>ATyS</strong> M 6s<br />

<strong>ATyS</strong> M 6e<br />

GS<br />

<strong>ATyS</strong> M<br />

<strong>ATyS</strong> M 6e<br />

Non-critical<br />

loads<br />

Critical<br />

loads<br />

UPS<br />

ATYSM 003 C GB<br />

Non-critical<br />

loads<br />

Critical<br />

loads<br />

UPS<br />

ATYSM 004 C GB<br />

<strong>ATyS</strong> M<br />

ATYSM 005 D<br />

Non-critical<br />

loads<br />

Critical<br />

loads<br />

UPS<br />

ATYSM 006 D GB


A complete range of accessories<br />

<strong>Socomec</strong> worldwide<br />

In EUROPE<br />

> Bridging bars<br />

A dedicated, BELGIUM compact accessory<br />

B - 1190 Brussel<br />

providing changeover output common<br />

info.scp.be@socomec.com<br />

point keeping cable connec-<br />

Tel. +32 (0)2 340 02 30<br />

tion capacity complete (protection<br />

FRANCE<br />

index F - 94132 IP2X). Fontenay-sous-Bois Cedex<br />

Tel. +33 (0)1 45 14 63 30<br />

info.scp.fr@socomec.com<br />

GERMANY<br />

D - 76275 Ettlingen<br />

Tel. +49 (0)7243 65 29 2 0<br />

info.scp.de@socomec.com<br />

ITALY<br />

I - 20098 San Giuliano Milanese (MI)<br />

Tel. +39 02 9849821<br />

info.scp.it@socomec.com<br />

POLAND<br />

> Single 01-625 pole Warszawa voltage sensing<br />

Tel. +48 91 442 64 11<br />

tap<br />

info.scp.pl@socomec.com<br />

Provides two terminals per pole for<br />

SLOVENIA<br />

voltage SI - 1000 sensing Ljubljana or power supply<br />

requirements.<br />

Tel. +386 1 5807 860<br />

info.scp.si@socomec.com<br />

It can be fitted on any pole keeping<br />

SPAIN cable connection capacity<br />

complete. E - 08310 Argentona (Barcelona)<br />

Tel. +34 93 741 60 67<br />

info.scp.es@socomec.com<br />

ThE NEThERLANDS<br />

NL - 3991 CD Houten<br />

Tel. +31 (0)30 760 0901<br />

> Auxiliary info.scp.nl@socomec.com contact<br />

Each ThE product UNITED KINGDOM can take up to 2<br />

Hitchin Hertfordshire SG4 0TY<br />

auxiliary Tel. +44 contact (0)1462 440033 blocks. One unit<br />

comprises info.scp.uk@socomec.com 1 NO / NC contact for<br />

each<br />

TURKEY<br />

position (I, 0 and II).<br />

Specifications: 34775 Istanbul 250 VAC / 5A maximum.<br />

Tel. +90 (0) 216 540 71 20<br />

info.scp.tr@socomec.com<br />

hEAD OFFICE<br />

SOCOMEC GROUP<br />

S.A. SOCOMEC capital 10 951 300 €<br />

R.C.S. Strasbourg B 548 500 149<br />

B.P. 60010 - 1, rue de Westhouse<br />

F-67235 Benfeld Cedex - FRANCE<br />

VALID FOR FRANCE<br />

www.socomec.com<br />

In ASIA<br />

Single-phase<br />

NORTh EAST ASIA<br />

P.R.C 200052 Shanghai - China<br />

Tel. +86 (0)21 5298 9555<br />

info.scp.cn@socomec.com<br />

40 to 125 A: 1309 2006<br />

SOUTh EAST ASIA & PACIFIC<br />

160 A: 1309 2016<br />

Singapore 408723<br />

Tel. +65 6506 7600<br />

info.scp.sg@socomec.com<br />

Three-phase<br />

SOUTh ASIA<br />

122001 Gurgaon, Haryana - India<br />

Tel. +91 124 4562 700<br />

info.scp.in@socomec.com<br />

40 to 125 A: 1309 4006<br />

160 A: 1309 4016<br />

1399 4006<br />

1309 0001<br />

InTERnATIOnAL SALES<br />

DEPARTMEnT<br />

SOCOMEC<br />

1, rue de Westhouse - B.P. 60010<br />

F - 67235 Benfeld Cedex - FRANCE<br />

Tel. +33 (0)3 88 57 41 41<br />

Fax +33 (0)3 88 74 08 00<br />

info.scp.isd@socomec.com<br />

ATYSM 198 A<br />

ATYSM 025 A<br />

ATYSM 026 A<br />

ATYSM 028 A<br />

In MIDDLE EAST<br />

In nORTh AMERICA<br />

> Terminal shrouds (pair)<br />

UNITED Protection ARAB against EMIRATES direct contact USA, CANADA & MEXICO<br />

Dubai, U.A.E.<br />

Cambridge, MA 02142 USA<br />

with terminals or connecting parts.<br />

Tel. +971 (0) 4 29 98 441<br />

Tel. +1 617 245 0447<br />

info.scp.ae@socomec.com<br />

A specific front hole enables info.scp.us@socomec.com<br />

access to terminals’ tightening<br />

screws for thermographic<br />

measurement or voltage sensing.<br />

2294 4016<br />

> Sealable cover (for <strong>ATyS</strong> M 6s)<br />

Prevents access to the product’s<br />

configuration.<br />

> <strong>ATyS</strong> D10 or D20 remote<br />

interfaces (for <strong>ATyS</strong> M 6e)<br />

To display source availability and<br />

changeover state on the front of<br />

a panel.<br />

RJ45 cable connection.<br />

YOUR DISTRIBUTOR<br />

Single-phase<br />

Three-phase<br />

1359 2000<br />

1359 0000<br />

ATYS 564 D<br />

1599 2010 1599 2020<br />

non contractual document. © 2013, <strong>Socomec</strong> SA. All rights reserved.<br />

ATYSM 043 A<br />

ATYSM 199 A<br />

ATYSM 027 A<br />

ATYS 565 D<br />

DOC 67093 - 03 / 13 - Photo: Martin Bernhart - Réalisation: SOCOMEC - Gyss Imprimeur Obernai - To help protect the environment, this document has been printed on PEFC paper (Programme To for help the protect Endorsement the environment, of Forest Certification)<br />

this document has been printed on PEFC paper (Programme for the Endorsement of Forest Certification)

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!