31.07.2014 Views

English version - Rhoss

English version - Rhoss

English version - Rhoss

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

K20301EN ed.2<br />

TCAVZ 2310÷2670<br />

Z-Power range<br />

Macrosystem<br />

297,5 ÷ 665,9 kW<br />

Packaged air cooled water chillers with axial fans.<br />

Range with semihermetic screw compressors and R134a refrigerant gas.


TCAVZ 2310 ÷ 2670 Z-POWER series<br />

A complete and flexible range<br />

Thirtheen models from 310 to 670 kW.<br />

This allows perfect selection of the model<br />

based on the cooling capacity required in the<br />

field, with no waste.<br />

The chillers of the Z-POWER range are also<br />

suitable for any sort of installation, thanks to<br />

their extensive operating limits.<br />

The standard unit works normally with an<br />

outdoor air temperature from 42÷45°C down<br />

to 5°C (down to -15°C with the FI15<br />

accessory).<br />

Furthermore, the unit can work up to 50°C<br />

with stepped cooling capacity.<br />

ESEER and IPLV<br />

On average, chillers perform throughout their<br />

life cycle providing lower cooling capacity than<br />

that for which they were purchased.<br />

Average efficiency is evaluated using the<br />

indexes ESEER (European) and IPLV<br />

(American).<br />

Z-POWER series chillers were designed to<br />

allow outstanding efficiency at partial loads<br />

and to achieve high ESEER and IPLV values,<br />

resulting in decreased energy consumption.<br />

Optimized components R134a<br />

The components used in the Z-POWER<br />

range were specially developed to achieve<br />

high performance and energy efficiency with<br />

R134a gas.<br />

The new screw compressors and the counterflow,<br />

both shell-and-tube and plate, heat<br />

exchangers dedicated to this gas are among<br />

the features of this range. The fan assembly is<br />

sized to provide excellent heat exchange with<br />

reduced noise. Also, the electronic expansion<br />

valve allows quick, precise adjustment in<br />

various load conditions.<br />

Versions<br />

Various <strong>version</strong>s are available to meet<br />

specific installation silence requirements.<br />

Noise reduction in the soundproofed <strong>version</strong>,<br />

with acoustic insulation of the compressor<br />

compartment, can be further enhanced<br />

through speed reduction of the fans in the<br />

silenced <strong>version</strong>.<br />

Proper operation and performance are<br />

ensured by the optimized design of the fan<br />

section.<br />

In the silenced <strong>version</strong>, the electronics enable<br />

the chiller to work with outdoor air<br />

temperatures of up to 50°C with stepped<br />

cooling capacity and a raise in noise over<br />

40÷43°C.<br />

A wide range of accessories<br />

The chillers of the Z-POWER range can be<br />

equipped not only with traditional accessories<br />

but also with total or partial recovery heat<br />

exchangers for the production of hot water at<br />

up to 60°C.<br />

In applications with outdoor air temperatures<br />

down to -15°C, devices are available to<br />

control fan speed.<br />

On request, the chillers can be equipped with<br />

pump assemblies with one or two pumps.<br />

Chillers up to 500 kW, equipped with plate<br />

exchanger, may have pump unit with 1100<br />

litre buffer tank and single or double electric<br />

pump.<br />

2


TCAVZ 2310 ÷ 2670 Z-POWER series<br />

Condensing section<br />

The geometry of the condensing section and<br />

the fluid-dynamics flow generated by the fans<br />

were designed to maximize efficiency of<br />

thermal exchange and to offset load losses,<br />

while holding down the level of noise<br />

propagated to the room.<br />

Also, the standard machine includes a<br />

stepped pressure-switch type of<br />

condensation control to allow operation with<br />

outdoor air temperatures down to +5°C.<br />

Evaporator<br />

Shell and tube or plate evaporator (it depends<br />

on the model) and perfect counter-flow<br />

thermal exchange.<br />

The evaporator is equipped with two<br />

refrigerant circuits (one per compressor). This<br />

also improves efficiency at partial loads.<br />

Compressor<br />

The Z-POWER range uses semi-hermetic<br />

screw compressors specifically designed to<br />

operate with R134a gas.<br />

Each compressor has 3 capacity control<br />

steps, for a total of 6 steps (2x3) thus<br />

providing the chiller with optimal operation<br />

even at partial loads with substantial energy<br />

savings.<br />

An option is also available that allows<br />

modulating control of cooling capacity.<br />

EEV:Electronic expansion valve<br />

The chillers are standard equipped with the<br />

latest electronic expansion valve managed by<br />

microprocessor control.<br />

Besides permitting precise control of the flow<br />

of refrigerant gas, this allows accurate<br />

operation of the cooling unit with improved<br />

response speed over traditional thermostatic<br />

expansion valves.<br />

3


main features<br />

INDEX<br />

Main features page 5<br />

Technical characteristics page 6<br />

Electronic control page 10<br />

Controlli e regolazioni pag. 11<br />

Performances page 12<br />

Pressure drops page 15<br />

Sound levels page 16<br />

Limiti di funzionamento pag. 17<br />

Performances and pressure<br />

drops of heat recuperators page 18<br />

Dimensions page 24<br />

Installation page 30<br />

Weight distribution page 31<br />

Electrical connections page 33<br />

Intended conditions of use<br />

TCAVBZ units are packaged water chillers<br />

with air cooled and axial fans.<br />

TCAVIZ - TCAVS units are packaged water<br />

chillers with air cooled and axial fans, in<br />

silenced format.<br />

TCAVBZ, TCAVIZ and TCAVS chillers are to<br />

be used in air conditioning systems that<br />

require the use of chilled water which is not<br />

for consumption.<br />

The unit is designed for outdoor<br />

installation.<br />

The units conform to the following directives:<br />

● Machine Directive 98/37/CEE (MD);<br />

● Low voltage Directive 2006/95/CEE (LVD);<br />

● Electromagnetic compatibility Directive 89/336/CEE (EMC);<br />

● Pressure equipment Directive 97/23/CEE (PED).<br />

Guide to reading the product code<br />

SERIES coding<br />

T C A V B<br />

Water chiller Cooling only Axial Semi-hermetic Standard<br />

fans screw <strong>version</strong><br />

compressors<br />

I<br />

Soundproofed<br />

<strong>version</strong><br />

S<br />

Silent<br />

<strong>version</strong><br />

Z<br />

R134a refrigerant<br />

charge<br />

“MODEL” coding<br />

2 310 ÷ 670<br />

No. of<br />

compressors<br />

Approximate<br />

cooling<br />

capacity<br />

(kW)<br />

Example: TCAVSZ 2540<br />

● Water chiller, cooling only, air cooled.<br />

● Silent <strong>version</strong>.<br />

● 2 no. semi-hermetic screw compressors.<br />

● Approximate cooling capacity 540 kW.<br />

4


main features<br />

Main features<br />

● Loadbearing structure in polyester powder<br />

coated galvanized steel sheet.<br />

● Semi-hermetic screw compressors,<br />

specifically designed to work with R134a gas.<br />

The compressor start-up is star-triangle type<br />

with starting current limited by equalizer and<br />

load stepping, complete with integral<br />

protection and crankcase heater.<br />

The compressors are also complete with<br />

intercept valve on the refrigerant outlet pipe.<br />

● Capacity control of the chiller as in the<br />

following table:<br />

MODEL Compressors/Steps No. Circuits No.<br />

2310 ÷ 2670 2 / 6 2<br />

● Water side shell and tube heat exchanger<br />

with counter-flow thermal exchange or plate<br />

exchanger with counter-current heat<br />

exchange. The shell and tube heat exchanger<br />

is made of carbon steel with copper pipes, air<br />

bleed valve, water discharge cock. The plate<br />

exchanger is made of stainless steel double<br />

circuit on the refrigerant side and single circuit<br />

on the water side to improve energy efficiency<br />

at partial loads. Both heat exchangers types<br />

have water differential pressure switch and<br />

insulation of closed cell expanded<br />

polyurethane rubber with anti U.V. protection<br />

layer.<br />

● Victaulic type water connections to the<br />

evaporator, female threaded on the<br />

recuperator and desuperheater.<br />

● Air-side exchanger made from<br />

mechanically expanded copper pipes and<br />

corrugated shaped aluminium fins to increase<br />

heat exchange efficiency.<br />

● Axial electric fans, fitted with built-in<br />

protector and safety grilles. The fans are<br />

equipped with pressure-switch control to<br />

ensure operation with outdoor air temperature<br />

down to +5°C.<br />

● Two refrigerant circuits with mild copper<br />

tubes and steel and silver alloy welding. Each<br />

cooling circuit complete with: cartridge filterdrier,<br />

charge connections, manual reset high<br />

pressure switch, automatic reset low pressure<br />

switch, indicator of gas passage and any<br />

presence of humidity, electronic expansion<br />

valve (for hermetic closure on the liquid line<br />

with the unit stopped), valve located on liquid<br />

line, safety valves located in high pressure<br />

sections., intercept and solenoid valve on the<br />

liquid line, safety valve in the high pressure<br />

section, suction line insulation of closed cell<br />

expanded polyurethane rubber with anti U.V.<br />

protection layer.<br />

● Refrigerant high and low pressure gauge<br />

for each refrigeration circuit.<br />

● Refrigerant charge of eco-friendly R134a.<br />

Electric panel<br />

● Electric panel complying with IEC<br />

standards, with ventilation, waterproof box<br />

complete with:<br />

• electrical wiring configured for<br />

400V-3ph-50Hz power supply;<br />

• transformer for auxiliary circuit;<br />

• auxiliary power supply 230V-1ph-50Hz;<br />

• control power supply 24V-1ph-50Hz;<br />

• phase monitoring to protect the compressor;<br />

• power contactors;<br />

• remotable controls:<br />

- remote ON/OFF, double set point (DSP<br />

accessory);<br />

- remotable machine controls: compressor(s)<br />

operation indicator light and general lockout<br />

indicator light;<br />

• main isolator switch on the power supply,<br />

complete with safety door interlock;<br />

• automatic protection switch for auxiliary<br />

circuit.;<br />

• fuses for each compressor (thermal<br />

overloads switches for the protection of each<br />

compressors is an option);<br />

• fuses for auxiliary circuit.<br />

● Programmable microprocessor electronic<br />

board with user terminal fitted to the unit,<br />

remotable up to 1,000 metres.<br />

The electronic board performs the following<br />

functions:<br />

• regulation and management of chiller inlet<br />

water temperature set points (with the optional<br />

accessory CCL - stepless capacity control -<br />

chiller are managed through the evaporator<br />

outlet water temperature);<br />

• management of safety timer delays; of the<br />

run-hours meter for each compressor; of<br />

automatic in<strong>version</strong> of the compressor<br />

operation sequence; of the circulation or user<br />

system pump (both evaporator side and<br />

condenser side); of the electronic antifreezing<br />

protection, of the load steps, of functions that<br />

integrate the workings of individual devices<br />

fitted to the unit;<br />

• management of the electronic expansion<br />

valve (EEV) with possibility to read and<br />

display suction temperature, evaporation<br />

pressure, overheating and valve opening<br />

status.<br />

• LCD display of programmed set points, of<br />

inlet/outlet water temperatures, of the<br />

condensing pressures, of alarms;<br />

● multilanguage management (Italian,<br />

<strong>English</strong>, French, German, Spanish) of display<br />

information.<br />

● alarm history management. The following is<br />

memorized for each alarm (if KSC accessory<br />

is provided):<br />

• date and time of activation;<br />

• alarm code and description;<br />

• the water inlet/outlet temperature values<br />

when the alarm intervened;<br />

• condensation pressure values at the time of<br />

the alarm;<br />

• alarm delay time from the switch-on of the<br />

connected device;<br />

• compressor status when the alarm<br />

intervened.<br />

• self-diagnosis with continuous monitoring of<br />

the machine’s operational status.<br />

● Advanced functions:<br />

• configured for serial connection via RS 485<br />

port for communication with building<br />

automation, centralised systems and<br />

supervision networks;<br />

• management of time bands and operation<br />

parameters with the possibility of daily/weekly<br />

programming;<br />

• check up and verification of programmed<br />

maintenance status;<br />

• computer-aided testing of the units.<br />

Versions<br />

● B - Standard <strong>version</strong> (TCAVBZ).<br />

● I - Soundproofed <strong>version</strong>, with soundproof<br />

jackets on compressors (TCAVIZ).<br />

● S - Silent <strong>version</strong> with soundproof jackets of<br />

compressors and low fan speed (TCAVSZ).<br />

Factory-fitted accessories<br />

● PUMP - One or two electric pumps, with<br />

one in standby and automatic operation based<br />

on operating times (for the equal division of the<br />

operating hours) or in the event of alarms. The<br />

electric pumps are available in the low or high<br />

pressure <strong>version</strong>s.<br />

● TANK&PUMP - as for the PUMP accessory<br />

described above, furthermore provided with:<br />

1100 litre built-in buffer tank (for 2310÷2470<br />

models), expansion tank, air bleed valves,<br />

safety valve and water pressure gauge. The<br />

buffer tank is provided on the water outlet.<br />

● RAS - Buffer tank antifreeze heater, in<br />

order to prevent freeze in the buffer tank when<br />

the machine is in OFF condition (only if the<br />

machine is connected to power supply).<br />

● RA - Evaporator antifreezing electrical<br />

heater with switch.<br />

● DS - recovery with desuperheater.<br />

● RC100 - 100% recovery with condensation<br />

heat recuperator. The accessory is complete<br />

with condensation control FI10 and a<br />

differential pressure switch on the recovery<br />

heat exchanger.<br />

TRD - Thermostat with display to show the<br />

water temperature at the recuperator/<br />

desuperheater inlet with the possibility of<br />

programming the activation set-point of a<br />

possible remote regulation device.<br />

● RDR - Desuperheater or heat recovery<br />

trace heater, used to prevent the risk of ice<br />

forming (only with DS or RC100) when the<br />

machine is in OFF condition (only if the<br />

machine is connected to power supply).<br />

● IM - thermal overloads switches for the<br />

protection of the compressors and fans.<br />

● RR - Units with intercept valve on the<br />

compressor inlet (valve comes as standard on<br />

outlet).<br />

● CCL - Unit with linear control of compressor<br />

capacity (25-100%).<br />

● SLO - oil level sensor (this accessory is<br />

suggested when it is difficult to visual check<br />

the pilot lamp of the compressor or when a<br />

more detailed monitoring is requested).<br />

● FI10 - Proportional electronic device for the<br />

continuous adjustment of the fan rotation<br />

speed down to an outside air temperature of<br />

–10°C.<br />

● FI15 - Proportional electronic device for the<br />

continuous adjustment of the fan rotation<br />

speed down to an outside air temperature of<br />

–15°C.<br />

● CR - Power factor correction capacitors<br />

(cosφ > 0,94).<br />

● SPS - refrigerant pressure signal on high<br />

and low side, on card.<br />

● SS -RS 485 serial interface for<br />

communicating with building management<br />

systems, centralised control systems and<br />

supervision networks (proprietary protocol,<br />

Modbus RTU).<br />

● FTT10 -LON serial interface - Serial<br />

interface for connection to BMS with protocol<br />

LON standard FTT10.<br />

● CMT - control of power supply voltage<br />

MIN/MAX values.<br />

● RAP - Unit with copper/pre-painted<br />

copper/aluminium coils.<br />

● BRR - Unit with copper/copper coils.<br />

● RRS - Unit with copper/tin-plated copper<br />

coils.<br />

● RPE - Lower protective grilles.<br />

On request, the following factory fitted<br />

accessories are available:<br />

● DSP - double set point<br />

● CS - set point setting (4-20 mA).<br />

Accessories supplied separately<br />

● KRP - Protection grille.<br />

● KSAM - Spring antivibration mountings.<br />

● KTR - Remote keyboard for control at a<br />

distance with the same functions as the one<br />

built into the unit.<br />

● KSC - Clock board to display date/hour, for<br />

the management of the machine with hourly,<br />

daily and weekly start-stop periods, with the<br />

possibility of varying the set points.<br />

5


TCAVBZ - TCAVIZ 2310 ÷ 2470:<br />

technical characteristics<br />

MODEL TCAVBZ - TCAVIZ 2310 2320 2340 2360 2400 2430 2470<br />

STANDARD-SOUNDPROOFED VERSION<br />

Technical data<br />

Nominal cooling capacity (*) kW 307,2 326,0 345,2 367,4 394,8 427,9 467,4<br />

E.E.R. (*) 2,83 2,84 2,82 2,80 2,86 2,83 2,80<br />

E.S.E.E.R. 3,95 3,96 3,96 3,98 3,99 3,91 3,83<br />

I.P.L.V. 4,11 4,11 4,12 4,13 4,15 4,07 3,98<br />

Sound pressure level TCAVBZ (*) (**) dB(A) 79 79 79 79 80 80 80<br />

Sound power level TCAVBZ (*) dB(A) 97 97 97 97 98 98 98<br />

Sound power level TCAVIZ (*) dB(A) 96 96 96 96 97 97 97<br />

Screw compressor/steps n. 2/6 2/6 2/6 2/6 2/6 2/6 2/6<br />

Circuits n. 2 2 2 2 2 2 2<br />

Fans n. x kW 6x2.1 6x2.1 6x2.1 6x2.1 8x2.1 8x2.1 8x2.1<br />

Fan nominal air flow m 3 /h 134000 132000 130000 130000 180000 176800 173600<br />

Evaporator Type Plate Plate Plate Plate Plate Plate Plate<br />

Evaporator nominal water flow (*) m 3 /h 52,8 56,1 59,4 63,2 67,9 73,6 80,4<br />

Evaporator nominal pressure drops (*) kPa 16 18 20 18 21 23 27<br />

Evaporator water contents L 65 65 65 76 76 82 82<br />

STE nominal pressure drops (*) (***) kPa 37 42 46 52 37 44 52<br />

STE water contents (***) L 111 111 111 111 113 113 113<br />

Electrical data<br />

Total power consumption (*) kW 108,4 114,8 122,3 131,4 138,2 151,1 166,7<br />

Electrical power supply V-ph-Hz 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50<br />

Auxiliary power supply V-ph-Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50<br />

Control power supply V-ph-Hz 24/1/50 24/1/50 24/1/50 24/1/50 24/1/50 24/1/50 24/1/50<br />

Nominal current A 197 207 218 232 244 262 284<br />

Maximum current A 284 299 314 341 376 386 396<br />

Starting current A 313 347 362 423 458 522 532<br />

Dimensions<br />

Length L mm 3830 3830 3830 3830 4830 4830 4830<br />

Height H mm 2430 2430 2430 2430 2430 2430 2430<br />

Depth P mm 2260 2260 2260 2260 2260 2260 2260<br />

(*) In the following conditions: condenser inlet<br />

air temperature 35°C; chilled water<br />

temperature 7°C; temperature differential at<br />

the evaporator 5°K; fouling factor of<br />

0.35x10 -4 m 2 K/W<br />

(**) Sound pressure level in dB(A) refers to a<br />

measurement in open space at a distance of<br />

1 m from the unit (average value measured<br />

on 4 sides) and with directionality factor Q=2.<br />

(***) Shell and tube evaporator accessory<br />

(STE) available for models 2310-2470.<br />

For R134a refrigerant charge and for polyester<br />

oil capacity (POE), see machine serial no. plate<br />

6


TCAVBZ - TCAVIZ 2500 ÷ 2670:<br />

technical characteristics<br />

MODEL TCAVBZ - TCAVIZ 2500 2540 2580 2600 2650 2670<br />

STANDARD-SOUNDPROOFED VERSION<br />

Technical data<br />

Nominal cooling capacity (*) kW 505,7 538,1 575,5 607,4 646,8 665,9<br />

E.E.R. (*) 2,87 2,87 2,87 2,81 2,87 2,83<br />

E.S.E.E.R. 3,91 3,99 3,97 3,95 3,96 3,96<br />

I.P.L.V. 4,07 4,15 4,13 4,11 4,11 4,12<br />

Sound pressure level TCAVBZ (*) (**) dB(A) 81 81 81 81 82 82<br />

Sound power level TCAVBZ (*) dB(A) 98 98 98 98 99 99<br />

Sound power level TCAVIZ (*) dB(A) 97 97 97 97 98 98<br />

Screw compressor/steps n. 2/6 2/6 2/6 2/6 2/6 2/6<br />

Circuits n. 2 2 2 2 2 2<br />

Fans n. x kW 10x2.1 10x2.1 10x2.1 10x2.1 12x2.1 12x2.1<br />

Fan nominal air flow m 3 /h 224400 224400 220600 216800 269200 269200<br />

Evaporator Type Shell and tube Shell and tube Shell and tube Shell and tube Shell and tube Shell and tube<br />

Evaporator nominal water flow (*) m 3 /h 87,0 92,6 99,0 104,5 111,2 114,5<br />

Evaporator nominal pressure drops (*) kPa 42 45 39 44 47 50<br />

Evaporator water contents L 256 256 250 250 250 250<br />

Electrical data<br />

Total power consumption (*) kW 176,1 187,3 200,7 215,9 225,4 235,7<br />

Electrical power supply V-ph-Hz 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50<br />

Auxiliary power supply V-ph-Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50<br />

Control power supply V-ph-Hz 24/1/50 24/1/50 24/1/50 24/1/50 24/1/50 24/1/50<br />

Nominal current A 303 323 342 364 381 398<br />

Maximum current A 424 444 470 496 504 504<br />

Starting current A 583 603 603 629 637 637<br />

Dimensions<br />

Length L mm 5830 5830 5830 5830 6680 6680<br />

Height H mm 2430 2430 2430 2430 2430 2430<br />

Depth P mm 2260 2260 2260 2260 2260 2260<br />

(*) In the following conditions: condenser inlet<br />

air temperature 35°C; chilled water<br />

temperature 7°C; temperature differential at<br />

the evaporator 5°K; fouling factor of<br />

0.35x10 -4 m 2 K/W<br />

(**) Sound pressure level in dB(A) refers to a<br />

measurement in open space at a distance of<br />

1 m from the unit (average value measured<br />

on 4 sides) and with directionality factor Q=2.<br />

(***) Shell and tube evaporator accessory<br />

(STE) available for models 2310-2470.<br />

For R134a refrigerant charge and for polyester<br />

oil capacity (POE), see machine serial no. plate<br />

7


TCAVSZ 2310 ÷ 2470:<br />

technical characteristics<br />

MODEL TCAVSZ 2310 2320 2340 2360 2400 2430 2470<br />

SILENT VERSION<br />

Technical data<br />

Nominal cooling capacity (*) kW 297,5 315,0 334,5 353,0 382,9 413,4 450,0<br />

E.E.R. (*) 2,74 2,73 2,71 2,62 2,78 2,72 2,66<br />

E.S.E.E.R. 3,75 3,78 3,81 3,83 3,86 3,73 3,60<br />

I.P.L.V. 3,90 3,93 3,96 3,99 4,01 3,88 3,74<br />

Sound pressure level (*) (**) dB(A) 73 73 73 73 74 74 74<br />

Sound power level (*) dB(A) 91 91 91 91 92 92 92<br />

Screw compressor/steps n. 2/6 2/6 2/6 2/6 2/6 2/6 2/6<br />

Circuits n. 2 2 2 2 2 2 2<br />

Fans n. x kW 6x1,3 6x1,3 6x1,3 6x1,3 8x1,3 8x1,3 8x1,3<br />

Fan nominal air flow m 3 /h 104400 102800 101200 101200 140400 137800 135200<br />

Evaporator Type Plate Plate Plate Plate Plate Plate Plate<br />

Evaporator nominal water flow (*) m 3 /h 51,2 54,2 57,5 60,7 65,9 71,1 77,4<br />

Evaporator nominal pressure drops (*) kPa 15 16 18 17 20 22 25<br />

Evaporator water contents L 65 65 65 76 76 82 82<br />

STE nominal pressure drops (*) (***) kPa 34 38 42 47 34 41 48<br />

STE water contents (***) L 111 111 111 111 113 113 113<br />

Electrical data<br />

Total power consumption (*) kW 108,5 115,5 123,6 134,9 137,8 152,1 169,0<br />

Electrical power supply V-ph-Hz 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50<br />

Auxiliary power supply V-ph-Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50<br />

Control power supply V-ph-Hz 24/1/50 24/1/50 24/1/50 24/1/50 24/1/50 24/1/50 24/1/50<br />

Nominal current A 197 207 219 237 242 262 286<br />

Maximum current A 284 299 314 341 376 386 396<br />

Starting current A 304 338 353 414 446 510 520<br />

Dimensions<br />

Length L mm 3830 3830 3830 3830 4830 4830 4830<br />

Height H mm 2430 2430 2430 2430 2430 2430 2430<br />

Depth P mm 2260 2260 2260 2260 2260 2260 2260<br />

(*) In the following conditions: condenser inlet<br />

air temperature 35°C; chilled water<br />

temperature 7°C; temperature differential at<br />

the evaporator 5°K; fouling factor of<br />

0.35x10 -4 m 2 K/W<br />

(**) Sound pressure level in dB(A) refers to a<br />

measurement in open space at a distance of<br />

1 m from the unit (average value measured<br />

on 4 sides) and with directionality factor Q=2.<br />

(***) Shell and tube evaporator accessory<br />

(STE) available for models 2310-2470.<br />

For R134a refrigerant charge and for polyester<br />

oil capacity (POE), see machine serial no. plate<br />

8


TCAVSZ 2500 ÷ 2670:<br />

technical characteristics<br />

MODEL TCAVSZ 2500 2540 2580 2600 2650 2670<br />

SILENT VERSION<br />

Technical data<br />

Nominal cooling capacity (*) kW 490,3 520,9 555,4 584,5 627,9 647,1<br />

E.E.R. (*) 2,79 2,77 2,74 2,67 2,77 2,71<br />

E.S.E.E.R. 3,72 3,84 3,83 3,82 3,81 3,80<br />

I.P.L.V. 3,87 3,99 3,98 3,97 3,96 3,95<br />

Sound pressure level (*) (**) dB(A) 75 75 75 75 76 76<br />

Sound power level (*) dB(A) 92 92 92 92 93 93<br />

Screw compressor/steps n. 2/6 2/6 2/6 2/6 2/6 2/6<br />

Circuits n. 2 2 2 2 2 2<br />

Fans n. x kW 10x1,3 10x1,3 10x1,3 10x1,3 12x1,3 12x1,3<br />

Fan nominal air flow m 3 /h 175600 175600 172600 168800 210400 210400<br />

Evaporator Type Shell and tube Shell and tube Shell and tube Shell and tube Shell and tube Shell and tube<br />

Evaporator nominal water flow (*) m 3 /h 84,3 89,6 95,5 100,5 108,0 111,3<br />

Evaporator nominal pressure drops (*) kPa 39 42 36 40 44 46<br />

Evaporator water contents L 256 256 250 250 250 250<br />

Electrical data<br />

Total power consumption (*) kW 175,8 187,8 202,6 219,2 226,7 238,6<br />

Electrical power supply V-ph-Hz 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50<br />

Auxiliary power supply V-ph-Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50<br />

Control power supply V-ph-Hz 24/1/50 24/1/50 24/1/50 24/1/50 24/1/50 24/1/50<br />

Nominal current A 301 318 340 367 380 400<br />

Maximum current A 424 444 470 496 504 504<br />

Starting current A 568 588 588 614 619 619<br />

Dimensions<br />

Length L mm 5830 5830 5830 5830 6680 6680<br />

Height H mm 2430 2430 2430 2430 2430 2430<br />

Depth P mm 2260 2260 2260 2260 2260 2260<br />

(*) In the following conditions: condenser inlet<br />

air temperature 35°C; chilled water<br />

temperature 7°C; temperature differential at<br />

the evaporator 5°K; fouling factor of<br />

0.35x10 -4 m 2 K/W<br />

(**) Sound pressure level in dB(A) refers to a<br />

measurement in open space at a distance of<br />

1 m from the unit (average value measured<br />

on 4 sides) and with directionality factor Q=2.<br />

For R134a refrigerant charge and for polyester<br />

oil capacity (POE), see machine serial no. plate<br />

9


microprocessor electronic controller and accessories<br />

Description of the keypad and display<br />

1<br />

5 2<br />

6<br />

7<br />

!<br />

ALARM<br />

Prg<br />

ON<br />

OFF<br />

KTR - Remote keypad<br />

MODE<br />

3<br />

4<br />

1 = Values and parameters DISPLAY:<br />

displays the numbers and the values of<br />

all the parameters (e.g. water outlet<br />

temperature, etc.), the codes of any<br />

alarms and the status of all the<br />

resources using message strings.<br />

2/4 = ▲ (up), ▼ (down) buttons:<br />

used to scroll the list of parameters, the<br />

operating status and any alarms; also<br />

used to change the set point.<br />

3 = MODE - ENTER button:<br />

used to to confirm the values entered.<br />

5 = ALARM button:<br />

used to display the alarm codes and<br />

reset any alarms.<br />

6 = PRG button:<br />

used to set the main operating<br />

parameters of the unit.<br />

7 = ON/OFF button:<br />

used to switch the unit on and off.<br />

!<br />

ALARM<br />

Prg<br />

ON<br />

OFF<br />

MODE<br />

Accessory - Remote keypad<br />

The remote keypad accessory (KTR) is used<br />

to control the unit and display all the digital<br />

and analogue process variables relating to the<br />

unit from a remote position.<br />

This accessory faithfully reproduces the<br />

functions of the keypad and the display of the<br />

microprocessor electronic controller.<br />

This allows all the functions of the unit to be<br />

controlled directly from inside the room.<br />

TRD - Thermostat with display<br />

°C<br />

SEL 2<br />

PRG<br />

mute 3<br />

4<br />

5<br />

1 = DISPLAY:<br />

displays the recuperator/desuperheater inlet water<br />

temperature value.<br />

2/4/5 = keys SEL, ▲ (up), ▼ (down):<br />

enable programming of the set-point and activation<br />

differential of a possible remote regulating device.<br />

3 = Key PRG/mute:<br />

allows entering the programming menu parameters.<br />

(only for RHOSS authorised personnel).<br />

The installation in the unit of the thermostat<br />

with display accessory (TRD) enables display<br />

of the recuperator/desuperheater inlet water<br />

temperature and programming of the<br />

activation set-point of a possible remote<br />

regulation device (e.g. ON/OFF 3-way valve),<br />

allowing a rational and efficient use of the<br />

recovered thermal energy.<br />

1<br />

10


!<br />

ALARM<br />

Prg<br />

ON<br />

OFF<br />

MODE<br />

ACCESSORIES: controls and adjustments<br />

SS / FTT10 serial interface<br />

Serial communication<br />

The electronic controller which is fitted to all<br />

the units can communicate with an external<br />

system through a serial communication line.<br />

Supervision system<br />

In general, a supervision system allows<br />

access to all the functions of the unit, such as:<br />

● setting all the values accessible from the<br />

keyboard;<br />

● reading all the process variables of the<br />

digital or analogue inputs and outputs;<br />

● reading the various alarm codes and<br />

possibly resetting them;<br />

● reading all the programming parameters<br />

and changing some of them.<br />

Note:<br />

For further information contact RHOSS sales<br />

support service.<br />

performance<br />

Selecting the unit and using the<br />

performance tables<br />

● Tables “A” and “B” provide the cooling<br />

capacity (QF) and the power input (P),<br />

according to the water temperature at the<br />

evaporator outlet, with a constant temperature<br />

differential ∆t = 5°C, and the ambient air<br />

temperature.<br />

● Tables “D” and “E” provide, for each<br />

model, the energy indexes, E.E.R., ESEER<br />

and IPLV, values.<br />

● As regards the operating limits (see page<br />

16), the values in tables “A” and “B” can be<br />

interpolated to calculate the performance, but<br />

not extrapolated.<br />

● Tables “F” and “G” provide, for each model,<br />

the sound pressure values in dB by octave<br />

band, the total sound power level in dB(A) and<br />

the sound pressure values in dB(A) at<br />

different distances.<br />

● Table “H” shows the correction coefficients<br />

to be applied to the nominal values if using a<br />

water glycol solution.<br />

11


TCAVBZ - TCAVIZ 2310 ÷ 2670: performances<br />

Table “A” - Cooling capacity TCAVBZ - TCAVIZ<br />

2670 2650 2600 2580 2540 2500 2470 2430 2400 2360 2340 2320 2310<br />

Tue (°C)<br />

Ta (°C)<br />

25 30 35 40 42 45<br />

MODEL QF P QF P QF P QF P QF P QF P<br />

kW kW kW kW kW kW kW kW kW kW kW kW<br />

5 311,6 91,9 299,5 98,3 286,7 105,6 272,8 113,3 267,0 116,6 258,0 121,8<br />

7 333,7 94,7 320,8 101,3 307,2 108,4 292,9 116,2 286,7 119,5 277,2 124,7<br />

9 356,4 97,6 343,3 104,3 329,4 111,5 313,5 119,2 307 122,6 297,4 127,9<br />

11 379,7 100,7 366,3 107,4 351,5 114,6 335,8 122,5 328,3 125,9 318,1 131,1<br />

13 404,7 103,9 390,4 110,6 374,6 117,9 358,0 125,8 350,6 129,2 339,8 134,5<br />

5 329,3 97,2 316,9 104,0 303,3 111,8 289,6 120,2 283,5 123,7 273,6 129,3<br />

7 353,1 100,1 339,9 107,0 326,0 114,8 310,8 123,3 304,3 126,9 293,8 132,4<br />

9 377,2 103,2 363,6 110,2 348,8 118,1 332,6 126,5 325,7 130,1 315,1 135,7<br />

11 403,0 106,4 388,5 113,5 372,8 121,4 355,6 130,0 348,1 133,5 337,5 139,1<br />

13 428,8 109,8 413,4 116,9 397,3 124,9 379,7 133,5 372,4 137,2 360,5 142,7<br />

5 349,5 103,2 336,2 110,6 322,3 118,9 306,8 128,1 300,7 131,9 291,0 137,9<br />

7 373,7 106,3 360,0 113,8 345,2 122,3 329,7 131,4 322,7 135,3 312,3 141,3<br />

9 399,6 109,5 385,1 117,1 369,3 125,6 353,3 134,9 345,8 138,8 334,8 144,9<br />

11 426,8 112,9 411,4 120,7 395,2 129,2 377,6 138,5 370,2 142,4 357,9 148,5<br />

13 454,2 116,5 439,0 124,5 421,8 133,0 403,1 142,2 395,2 146,2 382,8 152,4<br />

5 372,5 110,8 358,6 118,8 342,9 127,9 327,0 137,5 320,1 141,6 309,6 148,1<br />

7 398,6 114,3 384,0 122,4 367,4 131,4 350,0 141,1 342,7 145,3 331,7 151,7<br />

9 425,5 117,8 409,4 126,1 393,2 135,2 374,8 144,9 367,1 149,1 354,9 155,5<br />

11 452,4 121,6 436,8 130,0 419,0 139,0 400,3 148,9 391,5 153,0 379,3 159,5<br />

13 481,2 125,5 464,1 134,0 446,0 143,1 426,3 153,0 417,8 157,3 404,9 163,8<br />

5 398,3 117,9 383,9 125,8 368,2 134,8 351,8 144,7 344,3 149,0 333,4 155,7<br />

7 425,4 121,1 410,8 129,2 394,8 138,2 376,8 148,3 369,6 152,7 357,4 159,4<br />

9 455,1 124,4 439,0 132,6 421,5 141,8 403,9 152,0 395,6 156,4 382,7 163,2<br />

11 485,0 127,9 469,3 136,2 450,3 145,5 430,3 155,9 422,9 160,3 409,4 167,1<br />

13 516,3 131,6 499,8 140,0 480,4 149,4 459,4 159,9 450,9 164,3 436,7 171,2<br />

5 430,7 128,4 416,2 137,3 399,3 147,3 381,2 158,3 373,4 163,0 361,6 170,5<br />

7 461,1 132,0 445,2 141,0 427,9 151,1 408,7 162,4 400,4 167,1 387,9 174,7<br />

9 492,5 135,6 475,6 144,8 457,4 155,1 437,6 166,5 428,9 171,3 415,1 178,9<br />

11 525,4 139,6 507,6 148,8 488,3 159,2 466,8 170,8 457,6 175,7 443,7 183,4<br />

13 559,3 143,8 541,1 153,3 520,8 163,7 498,1 175,2 488,4 180,1 473,7 187,9<br />

5 470,3 141,1 454,3 151,0 436,1 162,2 416,5 174,8 408,8 180,1 395,5 188,5<br />

7 503,6 145,2 486,7 155,3 467,4 166,7 446,7 179,3 438,0 184,6 424,5 193,1<br />

9 538,7 149,4 519,6 159,7 500,4 171,2 478,5 184,0 468,7 189,5 454,4 198<br />

11 574,3 153,7 555,5 164,1 533,8 176,0 510,7 189,0 501,6 194,4 485,9 202,9<br />

13 610,4 158,3 591,7 168,9 568,9 180,8 544,5 193,9 534,9 199,5 518,3 208,1<br />

5 514,5 150,5 495,5 160,5 473,3 171,8 451,2 184,4 441,7 189,8 425,9 198,3<br />

7 548,1 154,4 528,5 164,7 505,7 176,1 481,8 188,9 471,5 194,4 455,8 202,8<br />

9 584,1 158,5 562,8 168,9 539,3 180,6 514,7 193,4 503,6 199,0 486,8 207,5<br />

11 621,5 162,8 598,4 173,2 574,2 185,1 546,6 198,2 535,7 203,8 519,0 212,4<br />

13 659,0 167,3 636,4 177,9 610,3 189,8 581,9 203,1 570,1 208,7 551,2 217,5<br />

5 548,6 159,7 528,1 170,4 504,4 182,6 480,7 196,1 470,0 202,0 453,9 210,9<br />

7 584,8 163,8 562,5 174,9 538,1 187,3 512,6 200,9 501,5 206,8 484,9 215,9<br />

9 622,3 168,4 599,4 179,3 574,2 192,0 546,8 206,0 535,4 211,8 517,2 221,0<br />

11 661,2 173,0 637,6 184,3 610,5 196,8 582,3 211,0 569,4 217,0 550,6 226,3<br />

13 701,5 177,8 677,2 189,3 649,3 202,2 619,1 216,1 607,0 222,2 586,5 231,6<br />

5 587,7 171,3 564,7 182,7 539,2 195,7 511,1 210,4 499,6 216,7 481,7 226,5<br />

7 626,8 175,9 601,8 187,5 575,5 200,7 546,6 215,5 534,8 221,9 515,1 231,9<br />

9 667,2 180,8 641,5 192,5 613,2 205,9 582,8 220,9 570,0 227,3 550,4 237,4<br />

11 709,2 186,1 682,8 198,0 652,2 211,4 620,9 226,5 607,8 233,0 587,0 243,1<br />

13 752,6 191,5 724,0 203,5 692,6 217,1 659,8 232,3 645,5 238,7 624,1 249,1<br />

5 623,0 184,1 598,4 196,4 569,9 210,5 540,2 226,6 528,6 233,4 509,3 244,3<br />

7 664,6 189,1 636,7 201,5 607,4 215,9 576,8 232,1 564,2 239,1 544,3 250,2<br />

9 707,9 194,4 679,1 206,9 647,6 221,4 616,1 237,8 602,5 245,0 580,6 256,1<br />

11 752,7 200,1 723,0 212,7 689,2 227,2 655,5 243,9 640,8 251,1 619,7 262,4<br />

13 799,0 206,0 767,1 218,8 733,8 233,5 697,7 250,1 681,8 257,4 658,7 268,8<br />

5 655,0 191,1 632,0 204,6 606,6 220,3 578,2 238,0 566,7 245,7 505,9 242,5<br />

7 698,6 195,9 673,5 209,6 646,8 225,4 616,9 243,4 605,3 251,1 541,3 248,1<br />

9 742,2 201,0 716,5 214,8 687,6 230,8 657,1 248,9 644,4 256,8 578,0 253,8<br />

11 787,4 206,5 761,2 220,5 731,6 236,5 698,8 254,8 638,2 248,7 616,0 259,9<br />

13 834,2 212,2 807,4 226,3 775,6 242,6 742,0 261,0 678,2 254,9 655,4 266,0<br />

5 668,8 197,8 649,3 213,0 625,5 230,7 600,1 250,5 589,0 259,1 498,9 243,2<br />

7 710,9 202,5 689,5 217,9 665,9 235,7 639,2 255,9 627,9 264,6 533,8 248,8<br />

9 754,6 207,6 732,7 223,0 707,8 241,1 679,8 261,5 589,9 243,6 569,9 254,5<br />

11 799,8 212,8 777,5 228,7 750,5 246,9 721,8 267,3 629,3 249,4 607,4 260,6<br />

13 846,6 218,4 822,2 234,4 794,6 252,8 764,5 273,5 668,8 255,6 646,3 266,7<br />

12<br />

Tue<br />

Ta<br />

= Evaporator outlet water temperature<br />

(inlet/outlet ∆t = 5°C)<br />

= Outdoor air temperature (dry bulb)<br />

QF<br />

P<br />

= Cooling capacity with fouling factor of<br />

0.35x10 -4 m 2 K/W<br />

= Total electrical power consumption


TCAVSZ 2310 ÷ 2670: performances<br />

Table “B” - Cooling capacity TCAVSZ<br />

2670 2650 2600 2580 2540 2500 2470 2430 2400 2360 2340 2320 2310<br />

Tue (°C)<br />

Ta (°C)<br />

25 30 35 40 42 45<br />

MODEL QF P QF P QF P QF P QF P QF P<br />

kW kW kW kW kW kW kW kW kW kW kW kW<br />

5 302,7 91,1 290,7 97,9 277,6 105,3 263,8 113,3 258,1 116,6 249,3 121,9<br />

7 323,7 94,2 310,9 101,1 297,5 108,5 283,3 116,6 276,7 119,9 267,2 125,3<br />

9 345,2 97,4 332,2 104,3 317,8 111,8 302,7 119,9 296,3 123,3 286,2 128,7<br />

11 367,7 100,7 354,4 107,7 339,2 115,2 323,1 123,4 316,8 126,9 306,1 132,3<br />

13 391,3 104,2 377,1 111,2 361,6 118,8 344,5 127,1 337,1 130,6 326,4 136,0<br />

5 320,2 96,8 307,4 104,1 294,0 112,1 279,5 120,7 273,4 124,4 264,2 130,1<br />

7 342,4 100,0 329,3 107,5 315,0 115,5 300,0 124,2 293,5 127,9 283,1 133,6<br />

9 365,6 103,5 351,7 110,9 337,1 119,1 320,5 127,8 314,2 131,5 303,7 137,3<br />

11 389,5 107 375,2 114,6 359,6 122,8 342,6 131,7 335,3 135,4 324,1 141,1<br />

13 414,4 110,7 399,3 118,4 383,3 126,6 365,2 135,6 358,1 139,3 346,2 145,1<br />

5 339,7 103,3 326,6 111,1 312,3 119,9 297,4 129,3 290,8 133,3 281,2 139,5<br />

7 363,7 106,8 349,7 114,8 334,5 123,6 318,6 133,0 312,1 137,0 301,3 143,2<br />

9 388,5 110,4 373,5 118,7 357,8 127,4 340,9 136,9 334,0 141,0 323,1 147,2<br />

11 414,4 114,3 398,5 122,6 382,4 131,3 364,3 140,9 357,0 145,0 345,4 151,3<br />

13 440,3 118,3 424,6 126,6 407,5 135,5 388,9 145,2 380,5 149,3 368,2 155,6<br />

5 359,6 112,9 345,4 121,6 329,9 130,9 313,6 141,1 306,8 145,3 296,5 152,1<br />

7 383,8 116,8 368,8 125,6 353,0 134,9 335,8 145,1 328,6 149,4 317,1 156,1<br />

9 409,1 120,8 393,3 129,7 376,6 139,2 358,5 149,5 350,9 153,9 339,4 160,5<br />

11 435,1 125,0 419,0 133,9 401,4 143,5 382,3 153,9 374,3 158,3 361,5 165,1<br />

13 462,2 129,4 445,2 138,3 427,4 148,0 406,6 158,5 398,2 162,9 385,4 169,7<br />

5 387,9 116,4 373,1 124,7 357,6 134,2 340,8 144,6 333,4 149,0 322,5 155,9<br />

7 414,3 120,0 399,3 128,4 382,9 137,8 365,1 148,4 357,4 152,9 345,3 159,9<br />

9 442,0 123,7 426,8 132,3 409,5 142,0 390,2 152,5 382,0 157,0 369,9 164,0<br />

11 471,2 127,5 455,1 136,3 436,9 146,1 416,4 156,8 408,5 161,4 395,1 168,3<br />

13 501,7 131,6 484,0 140,6 464,8 150,4 444,0 161,2 434,9 165,8 421,5 172,9<br />

5 417,7 128,0 402,4 137,3 385,2 147,8 367,2 159,5 359,5 164,4 347,3 172,2<br />

7 446,7 132,0 430,4 141,5 413,4 152,1 393,8 163,7 385,7 168,8 372,7 176,6<br />

9 476,6 136,2 459,9 145,9 441,9 156,7 421,2 168,4 412,6 173,4 398,9 181,3<br />

11 508,5 140,6 490,9 150,4 470,6 161,4 450,0 173,4 440,9 178,9 426,5 186,3<br />

13 540,7 145,2 522,1 155,3 501,4 166,3 478,9 178,4 469,3 183,5 454,8 191,4<br />

5 455,0 141,8 437,7 152,3 420,3 164,3 400,9 177,5 392,8 183,0 379,7 191,7<br />

7 486,3 146,3 469,6 157,0 450,0 169,0 429,0 182,3 420,4 188,0 406,5 196,8<br />

9 519,1 151,0 501,4 161,9 481,3 174,1 459,1 187,6 450,0 193,1 435,3 201,9<br />

11 553,5 155,9 534,2 167,1 513,5 179,5 490,1 192,9 480,4 198,7 464,9 207,5<br />

13 589,6 161,1 568,6 172,5 546,1 185,1 521,9 198,8 511,8 204,5 495,4 213,2<br />

5 500,2 148,8 480,4 159,3 458,6 171,2 435,8 184,3 426,0 189,9 411,0 198,6<br />

7 533,1 153,0 512,8 163,9 490,3 175,8 465,7 189,1 455,1 194,7 439,1 203,5<br />

9 567,2 157,7 546,3 168,6 522,1 180,7 496,8 194,1 485,8 199,8 469,3 208,6<br />

11 602,7 162,4 579,9 173,5 555,0 185,9 528,4 199,3 516,5 205,0 499,6 213,9<br />

13 638,2 167,4 614,8 178,6 589,1 191,2 561,2 204,8 549,5 210,4 530,9 219,4<br />

5 531,4 158,6 510,2 169,9 487,0 182,5 462,7 196,7 452,1 202,7 436,3 212,1<br />

7 566,7 163,3 544,9 174,9 520,9 187,8 493,7 201,7 482,8 207,9 466,0 217,3<br />

9 602,2 168,2 578,6 180,0 553,9 193,1 527,0 207,3 514,7 213,4 497,3 222,8<br />

11 639,0 173,3 615,8 185,3 589,2 198,6 560,4 212,9 547,7 219,1 529,3 228,6<br />

13 677,1 178,7 652,0 190,9 624,7 204,4 595,0 219,0 581,9 225,1 563,0 234,5<br />

5 570,3 171,2 546,3 183,4 521,2 197,1 493,5 212,2 482,2 218,7 464,0 229,0<br />

7 607,8 176,5 582,6 188,7 555,4 202,6 526,9 217,9 514,7 224,5 495,9 234,8<br />

9 646,8 181,8 620,1 194,3 592,2 208,4 561,6 224,1 549,0 230,7 529,7 240,9<br />

11 686,4 187,6 659,0 200,4 628,9 214,5 597,5 230,3 584,5 237,0 563,3 247,5<br />

13 727,5 193,6 697,9 206,5 666,9 220,8 634,6 236,8 620,6 243,5 599,5 254,1<br />

5 601,4 185,1 576,0 198,2 548,1 213,1 518,9 229,9 506,2 237,1 487,2 248,5<br />

7 640,7 190,7 613,2 204,0 584,5 219,2 553,2 236,1 540,2 243,4 520,6 254,9<br />

9 681,4 196,6 653,2 210,1 622,3 225,5 590,1 242,7 576,7 249,9 555,2 261,6<br />

11 723,6 202,8 693,2 216,5 661,4 232,1 627,6 249,5 613,1 257,0 591,8 268,5<br />

13 767,3 209,5 736,0 223,2 701,9 239,0 666,5 256,6 651,6 264,2 629,7 276,0<br />

5 638,5 190,0 615,7 204,4 589,8 221,0 561,6 239,5 507,8 232,1 488,9 243,2<br />

7 680,0 195,5 655,1 210,0 627,9 226,7 599,1 245,5 542,3 238,0 522,9 249,2<br />

9 723,0 201,1 696,0 215,9 667,4 232,9 637,1 251,8 578,8 244,1 558,1 255,5<br />

11 766,0 207,1 738,4 222,1 709,2 239,3 630,3 243,2 616,5 250,5 594,6 262,0<br />

13 810,5 213,3 782,3 228,6 750,8 245,9 669,8 250,0 655,7 257,2 633,2 268,8<br />

5 653,8 198,0 633,1 214,2 609,5 232,9 582,8 253,4 500,6 233,0 482,0 244,1<br />

7 693,9 203,2 672,0 219,8 647,1 238,6 619,9 259,8 534,7 238,8 515,5 250,1<br />

9 735,5 208,8 713,1 225,7 687,7 244,9 583,7 237,8 570,6 245,0 550,2 256,5<br />

11 780,1 214,8 754,9 231,9 728,2 251,3 621,3 244,1 607,8 251,4 586,2 263,0<br />

13 824,8 221,1 799,0 238,4 771,7 257,9 660,3 250,9 646,4 258,1 624,2 269,8<br />

Tue<br />

Ta<br />

= Evaporator outlet water temperature<br />

(inlet/outlet ∆t = 5°C)<br />

= Outdoor air temperature (dry bulb)<br />

QF<br />

P<br />

= Cooling capacity with fouling factor of<br />

0.35x10 -4 m 2 K/W<br />

= Total electrical power consumption<br />

13


performance<br />

Energy efficiency with partial loads<br />

- ESEER and IPLV indexes<br />

● The E.E.R. index represent an estimate of<br />

the energy efficiency of the cooling unit at<br />

nominal design conditions.<br />

Actually, the operating time of a chiller at<br />

nominal conditions is generally less than the<br />

operating time in partial load conditions.<br />

● The indexes IPLV (Integrated Part Load<br />

Value) and ESEER (European Seasonal<br />

EER) are indexes which estimate the average<br />

seasonal energy efficiency of the chiller in four<br />

conditions of load and of outdoor air<br />

temperature. Generally, two chillers that have<br />

the same EER value may have different IPLV<br />

or ESEER values.<br />

As a matter of fact, for an air cooled chiller<br />

unit, the average energy efficiency depends<br />

on design decisions and on the temperature<br />

of the incoming air at the condensing coil.<br />

● The IPLV e ESEER energy indexes,<br />

introduced respectively by the (American<br />

Refrigeration Institute - ARI standard 550/590)<br />

and by the European Community (project<br />

EECCAC - Energy Efficiency and Certification<br />

of Central Air Conditioners), have the same<br />

formulation, but they differ in outdoor air<br />

temperatures (see table “C”) and for the<br />

energy weights which are assigned to the four<br />

load conditions considered in the calculations:<br />

100%, 75%, 50% e 25% and for Tw produced<br />

(6,7°C IPLV / 7°C ESEER).<br />

IPLV = 1*EER 100% + 42*EER 75% + 45*EER 50% + 12*EER 25%<br />

100<br />

● Tables “D”, “D”, show, for each model, the<br />

values of E.E.R., ESEER and IPLV.<br />

The high energy efficiency values at partial<br />

loads were obtained thanks to the<br />

optimisation of the heat exchangers and the<br />

adoption of groups of fans managed<br />

independently based on load conditions.<br />

Table “D”: E.E.R. - ESEER - IPLV<br />

for TCAVBZ-TCAVIZ<br />

MODEL E.E.R ESEER IPLV<br />

2310 2,83 3,95 4,11<br />

2320 2,84 3,96 4,11<br />

2340 2,82 3,96 4,12<br />

2360 2,80 3,98 4,13<br />

2400 2,86 3,99 4,15<br />

2430 2,83 3,91 4,07<br />

2470 2,80 3,83 3,98<br />

2500 2,87 3,91 4,07<br />

2540 2,87 3,99 4,15<br />

2580 2,87 3,97 4,13<br />

2600 2,81 3,95 4,11<br />

2650 2,87 3,96 4,11<br />

2670 2,83 3,96 4,12<br />

ESEER = 3*EER 100% + 33*EER 75% + 41*EER 50% + 23*EER 25%<br />

100<br />

where EER100% EER75% EER50% EER25%<br />

represent the efficiency of the cooling unit at<br />

the four load and temperature conditions<br />

shown in table “C”.<br />

Table “C”: load and temperature<br />

conditions<br />

Outdoor air temperature:<br />

Load IPLV ESEER<br />

100% 35°C 35°C<br />

75% 26,7°C 30°C<br />

50% 18,3°C 25°C<br />

25% 12,8°C 20°C<br />

Table “E”: E.E.R. - ESEER - IPLV<br />

for TCAVSZ<br />

MODEL E.E.R ESEER IPLV<br />

2310 2,74 3,75 3,90<br />

2320 2,73 3,78 3,93<br />

2340 2,71 3,81 3,96<br />

2360 2,62 3,83 3,99<br />

2400 2,78 3,86 4,01<br />

2430 2,72 3,73 3,88<br />

2470 2,66 3,60 3,74<br />

2500 2,79 3,72 3,87<br />

2540 2,77 3,84 3,99<br />

2580 2,74 3,83 3,98<br />

2600 2,67 3,82 3,97<br />

2650 2,77 3,81 3,96<br />

2670 2,71 3,80 3,95<br />

All models feature 6 cooling load steps. The table below shows, for each model, the values of<br />

the cooling capacity % and the total power input % corresponding to each load step delivered.<br />

STEPS 6 5 4 3 2 1<br />

P (*)QF (*) P (*)QF (*) P (*)QF (*) P (*)QF (*) P (*)QF (*) P (*) QF (*)<br />

MODEL kW kW kW kW kW kW kW kW kW kW kW kW<br />

2310÷2600 100 100 93 94 77 78 50 50 42 44 27 28<br />

2650÷2670 100 100 83 86 71 72 46 47 35 37 27 28<br />

QF = Cooling capacity %<br />

P = Total power input %<br />

(*) At the following conditions: condenser air<br />

intake temperature 35°C; chilled water<br />

temperature 7°C; temperature differential at<br />

the evaporator 5°C.<br />

14


pressure drop and external static pressure<br />

Evaporator pressure drop<br />

Pressure drop calculation<br />

● The water flow-rate at the exchanger is<br />

calculated using the following formula:<br />

G = (QF x 0,86) : ∆T<br />

• Where:<br />

G (m 3 /h) = water flow-rate at the exchanger;<br />

QF (kW) = refrigerating capacity;<br />

∆T (°C) = temperature differential;<br />

● The pressure drop can be taken from the<br />

<strong>Rhoss</strong> selection software or alternatively<br />

estimated using the following approximate<br />

formulae:<br />

∆pw = ∆pwnom x (G : Gnom) 2<br />

• Where:<br />

∆pw (kPa) = pressure drop at the evaporator;<br />

∆pwnom (kPA) = nominal pressure drop at the<br />

evaporator (table of “technical specifications”);<br />

G (m 3 /h) = water flow-rate at the exchanger in<br />

question;<br />

Gnom (m 3 /h) = nominal water flow-rate at the<br />

evaporator (table of “technical specifications”).<br />

External static pressure calculation<br />

● The external static pressure values can be taken from the following graphs, with reference to the expected water flows.<br />

External static pressure TCAVZ 2310÷2670<br />

with PUMP (P1 - P2) accessory<br />

250<br />

230<br />

∆pr = external static pressure<br />

G = water flow<br />

Important note:<br />

for all the units, refer to the operating limits<br />

shown on page 17 and the temperature<br />

differential (∆T) allowed.<br />

PUMP accessory with single or double pump.<br />

Maximum admissible pressure 600 kPa.<br />

ECH<br />

210<br />

PD<br />

190<br />

P/DP<br />

170<br />

150<br />

2400-2470 P2<br />

130<br />

2310-2340 P2<br />

110<br />

RI<br />

RI<br />

2400-2470 P1 - 2360 P2<br />

90<br />

GI<br />

GI<br />

70<br />

50<br />

2310-2340 P1<br />

2360 P1<br />

2500-2670 P1<br />

2500-2670 P2<br />

30<br />

30 40 50 60 70 80 90 100 110 120 130 140 150 160<br />

C<br />

FA<br />

External static pressure TCAVZ 2310÷2470<br />

with TANK&PUMP (T&P1 - T&P2) accessory<br />

250<br />

230<br />

∆pr = external static pressure<br />

G = water flow<br />

TANK&PUMP accessory with single or double<br />

pump. Maximum admissible pressure 600 kPa.<br />

ECH<br />

210<br />

190<br />

2310-2340 T&P2<br />

PD<br />

P/DP<br />

VSM<br />

M<br />

VS<br />

170<br />

150<br />

130<br />

SA<br />

1100 l<br />

VE<br />

110<br />

2360 T&P1<br />

2310-2340 T&P1<br />

RI<br />

RI<br />

S<br />

90<br />

2400-2470 T&P1 - 2360 T&P2<br />

70<br />

GI<br />

GI<br />

2400-2470 T&P2<br />

50<br />

FA<br />

30<br />

30 40 50 60 70 80 90 100<br />

C<br />

External static pressure TCAVZ 2310÷2470<br />

with STE and PUMP (P1 - P2) accessories<br />

250<br />

230<br />

210<br />

190<br />

170<br />

150<br />

130<br />

2310-2340 STE P1<br />

∆pr = external static pressure<br />

G = water flow<br />

Key<br />

P = Main circulating pump PN6 - 600 kPa<br />

(P1 = low pressure, P2 = high pressure)<br />

DP = Two main circulating pumps, one of which in standby<br />

PN6 - 600 kPa<br />

ECH = Plate evaporator<br />

M = System pressure gauge<br />

PD = Differential pressure switch<br />

SA = Storage tank (1100 litre)<br />

VE = Expansion vessel (24 litre)<br />

VR = Non-return valve<br />

VS = Safety valve (setting 600 kPa)<br />

VSM = Manual air vent valve<br />

110<br />

90<br />

70<br />

50<br />

2360 STE P1<br />

2310-2340 STE P2<br />

2400-2470 STE P1 - 2360 STE P2<br />

2400-2470 STE P2<br />

30<br />

40 50 60 70 80 90 100<br />

Components to be fitted by the installer<br />

C = Fill cock<br />

FA = Water filter<br />

GI = Vibration damper attachment<br />

RI = Shutoff cock<br />

S = System drain cock<br />

= Connection by the installer<br />

15


caratteristiche acustiche<br />

Table “F”: sound pressure and power TCAVBZ standard <strong>version</strong><br />

MODEL Sound pressure levels in dB by octave band, total sound power level in dB (A) and sound pressure level in dB (A) at different distances<br />

125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz Lw Lp (1) (*) Lp (10)<br />

2310 80 76 73 76 72 67 57 97 79 63<br />

2320 80 76 73 76 72 67 57 97 79 63<br />

2340 80 76 73 76 72 67 57 97 79 63<br />

2360 80 76 73 76 72 67 57 97 79 63<br />

2400 80 76 73 77 74 68 59 98 80 64<br />

2430 80 76 73 77 74 68 59 98 80 64<br />

2470 80 76 73 77 74 68 59 98 80 64<br />

2500 80 76 74 78 75 70 60 98 81 65<br />

2540 80 76 74 78 75 70 60 98 81 65<br />

2580 80 76 74 78 75 70 60 98 81 65<br />

2600 80 76 74 78 75 70 60 98 81 65<br />

2650 80 76 76 79 75 73 61 99 82 66<br />

2670 80 76 76 79 75 73 61 99 82 66<br />

Table “G”: sound pressure and power TCAVSZ silent <strong>version</strong><br />

MODEL Sound pressure levels in dB by octave band, total sound power level in dB (A) and sound pressure level in dB (A) at different distances<br />

125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz Lw Lp (1) Lp (10)<br />

2310 65 64 68 70 67 61 51 91 73 57<br />

2320 65 64 68 70 67 61 51 91 73 57<br />

2340 65 64 68 70 67 61 51 91 73 57<br />

2360 65 64 68 70 67 61 51 91 73 57<br />

2400 65 65 69 71 68 62 52 92 74 58<br />

2430 65 65 69 71 68 62 52 92 74 58<br />

2470 65 65 69 71 68 62 52 92 74 58<br />

2500 65 66 70 72 69 64 52 92 75 59<br />

2540 65 66 70 72 69 64 52 92 75 59<br />

2580 65 66 70 72 69 64 52 92 75 59<br />

2600 65 66 70 72 69 64 52 92 75 59<br />

2650 65 66 71 72 69 67 54 93 76 60<br />

2670 65 66 71 72 69 67 54 93 76 60<br />

Lp = Sound pressure level in dB(A).<br />

Lw =Total sound power level in dB (A) based<br />

on measurements made in accordance<br />

with the UNI EN-ISO 3744 and Eurovent<br />

8/1 standards.<br />

(*) For TCAVIZ (soundproofed <strong>version</strong>) take<br />

off 2 dB(A).<br />

Important note:<br />

● The sound pressure level refers to<br />

measurements made in an open field at<br />

different distances from the unit (average<br />

value measured on 4 sides) with a direction<br />

factor Q = 2. The distance in metres is shown<br />

in brackets.<br />

● The sound pressure values cannot be<br />

extrapolated for distances less than 10m.<br />

● With an ambient air temperature below<br />

around 25°C, or with the FI10 / FI15 for<br />

outdoor air temperature less than 5°C, the unit<br />

in chiller mode decreases its sound level to a<br />

value lower than the nominal value indicated<br />

in the table.<br />

16


operating limits and use of antifreeze solutions<br />

Operating as a chiller<br />

50<br />

t max<br />

40<br />

35<br />

10<br />

5<br />

0<br />

-5<br />

-10<br />

-15<br />

FI10<br />

FI15<br />

5 6 7 8 9 10 11 12 13 14 15<br />

MODEL TCAVBZ -<br />

TCAVIZ -<br />

TCAVSZ<br />

TCAVSZ<br />

2310÷2600 t max = 45°C (1) (2) t max = 43°C (1) (3)<br />

2650÷2670 t max = 42°C (1) (2) t max = 40°C (1) (3)<br />

T (°C) = temperature of water produced<br />

t (°C) = outdoor air temperature (d.b.)<br />

● Temperature differential at evaporator:<br />

∆t=3÷8°C. Consider the minimum and<br />

maximum water flow indicated in the table<br />

R134a standard operation.<br />

Operation with condensation control<br />

(FI10 - FI15).<br />

Operation, with stepped cooling<br />

capacity. If the unit is supplied with<br />

the accessory CCL, the external air<br />

temperature maximum limit is 45°C.<br />

We can also provide units on demand to<br />

supply chilled water at less than 5°C.<br />

(1) Evaporator water temperature (IN/OUT) 12/7<br />

(2) Maximum external air temperature for standard operation mode at full load<br />

(3) Maximum external air temperature for silent operation mode<br />

Evaporator water flow<br />

MODEL Min. Max.<br />

2310 (*) m 3 /h 40 110<br />

2320 (*) m 3 /h 40 110<br />

2340 (*) m 3 /h 40 110<br />

2360 (*) m 3 /h 40 110<br />

2400 (*) m 3 /h 40 135<br />

2430 (*) m 3 /h 40 135<br />

2470 (*) m 3 /h 40 135<br />

2500 m 3 /h 60 135<br />

2540 m 3 /h 60 135<br />

2580 m 3 /h 75 165<br />

2600 m 3 /h 75 165<br />

2650 m 3 /h 75 165<br />

2670 m 3 /h 75 160<br />

(*) Values referred to acessory shell and tube<br />

evaporator (STE).<br />

Use of antifreeze solutions<br />

The use of ethylene glycol is necessary if the<br />

user wishes to avoid draining the water from<br />

the hydraulic circuit during the winter<br />

shutdown, or if the unit is required to supply<br />

chilled water at temperatures lower than 4°C.<br />

The addition of glycol changes the physical<br />

properties of the water and consequently the<br />

unit’s performance.<br />

The proper glycol percentage to be put into<br />

the system can be determined by selecting<br />

the most exacting of the operating conditions<br />

detailed below.<br />

Anti-freeze protection during<br />

seasonal shutdown<br />

● Table shows the multipliers to obtain the<br />

changes in the unit’s performance according<br />

to the necessary percentages of ethylene<br />

glycol.<br />

● The multipliers refer to the following<br />

conditions: condenser inlet air temperature<br />

35°C; chilled water temperature 7°C; water ∆t<br />

at the evaporator 5°C.<br />

● For different operating conditions the same<br />

multipliers can be used since the amount of<br />

change is negligible.<br />

● A trace electrical heater (accessory RA)<br />

reduces the freezing risk during winter<br />

shutdowns.<br />

Table “H”: TCAVBZ-TCAVIZ-TCAVSZ 2310 ÷ 2670<br />

Minimum ambient air temp. °C 2 0 –3 –6 –10 –15 –20<br />

% glycol in weight 10 15 20 25 30 35 40<br />

Freezing temperature °C –5 –7 –10 –13 –16 –20 –25<br />

fc G 1,025 1,039 1,054 1,072 1,093 1,116 1,140<br />

fc ∆pw 1,085 1,128 1,191 1,255 1,319 1,383 1,468<br />

fc QF 0,975 0,967 0,963 0,956 0,948 0,944 0,937<br />

fc P 0,993 0,991 0,990 0,988 0,986 0,983 0,981<br />

fc G = correction factor for glycol water<br />

flow to the evaporator<br />

fc ∆pw = correction factor for pressure drops<br />

through the evaporator<br />

fc QF<br />

fc P<br />

= correction factor for cooling capacity<br />

= correction factor for total power<br />

consumption<br />

17


TCAVBZ-TCAVIZ 2310 ÷ 2430<br />

ACCESSORIES DS and RC100: performances and pressure drops<br />

MODEL TCAVBZ - TCAVIZ 2310 2320<br />

STANDARD-SOUNDPROOFED VERSION<br />

Technical data<br />

RC100 - 100% recuperator<br />

Inlet/outlet water temperature °C 35/40 (**) 40/45 (*) 45/50 (**) 35/40 (**) 40/45 (*) 45/50 (**)<br />

Nominal heating capacity(•) kW 408 401 393 434 426 418<br />

Recuperator nominal water flow m 3 /h 71,0 69,9 69,9 75,4 74,2 74,3<br />

Recuperator nominal pressure drops kPa 57 56 56 64 62 62<br />

Recuperator water contents L 38 38 38 38 38 38<br />

DS - Desuperheater<br />

Inlet/outlet water temperature °C 40/50 (***) 50/60 (***) - 40/50 (***) 50/60 (***) -<br />

Nominal heating capacity(•) kW 63 37 - 69 41 -<br />

Recuperator nominal water flow m 3 /h 5,6 3,2 - 6,1 3,6 -<br />

Recuperator nominal pressure drops kPa 8 3 - 10 4 -<br />

Recuperator water contents L 9 9 - 9 9 -<br />

MODEL TCAVBZ - TCAVIZ 2340 2360<br />

STANDARD-SOUNDPROOFED VERSION<br />

Technical data<br />

RC100 - 100% recuperator<br />

Inlet/outlet water temperature °C 35/40 (**) 40/45 (*) 45/50 (**) 35/40 (**) 40/45 (*) 45/50 (**)<br />

Nominal heating capacity(•) kW 460 453 444 493 484 475<br />

Recuperator nominal water flow m 3 /h 80,0 78,9 78,9 85,7 84,3 84,3<br />

Recuperator nominal pressure drops kPa 71 69 69 65 63 63<br />

Recuperator water contents L 38 38 38 45 45 45<br />

DS - Desuperheater<br />

Inlet/outlet water temperature °C 40/50 (***) 50/60 (***) - 40/50 (***) 50/60 (***) -<br />

Nominal heating capacity(•) kW 75 45 - 85 52 -<br />

Recuperator nominal water flow m 3 /h 6,6 3,9 - 7,5 4,6 -<br />

Recuperator nominal pressure drops kPa 11 4 - 14 6 -<br />

Recuperator water contents L 9 9 - 10,5 10,5 -<br />

MODEL TCAVBZ - TCAVIZ 2400 2430<br />

STANDARD-SOUNDPROOFED VERSION<br />

Technical data<br />

RC100 - 100% recuperator<br />

Inlet/outlet water temperature °C 35/40 (**) 40/45 (*) 45/50 (**) 35/40 (**) 40/45 (*) 45/50 (**)<br />

Nominal heating capacity(•) kW 522 514 504 567 559 548<br />

Recuperator nominal water flow m 3 /h 90,8 89,5 89,6 98,6 97,4 97,4<br />

Recuperator nominal pressure drops kPa 72 70 70 59 58 58<br />

Recuperator water contents L 45 45 45 61 61 61<br />

DS - Desuperheater<br />

Inlet/outlet water temperature °C 40/50 (***) 50/60 (***) - 40/50 (***) 50/60 (***) -<br />

Nominal heating capacity(•) kW 72 40 - 82 47 -<br />

Recuperator nominal water flow m 3 /h 6,3 3,5 - 7,2 4,1 -<br />

Recuperator nominal pressure drops kPa 4 1 - 5 2 -<br />

Recuperator water contents L 12 12 - 12 12 -<br />

(•) Heating capacity with recuperator and<br />

desuperheater fouling factor of 0,35x10 -4 m 2<br />

K/W.<br />

(*) Conditions refer to the unit complete with<br />

condensation control (FI10) with standard<br />

setting and chilled water temperature 7°C,<br />

with evaporator temperature differential 5 K.<br />

(**) Conditions refer to the unit complete with<br />

condensation control (FI10) with the<br />

appropriate setting (expressly requested at<br />

the time of ordering) and chilled water<br />

temperature 7°C, with evaporator temperature<br />

differential 5 K.<br />

(***) Conditions refer to the unit with chilled<br />

water temperature 7°C, with evaporator<br />

temperature differential 5 K.<br />

Operating limits:<br />

● RC100:<br />

• temperature of hot water produced 35÷50°C<br />

with permitted water temperature differential<br />

4÷6 K.<br />

• the minimum permitted inlet water<br />

temperature is 30°C.<br />

• If the unit is equipped with the accessory<br />

and RC100 the FI10 accessory must be used.<br />

● DS:<br />

• temperature of hot water produced 45÷<br />

60°C with permitted water temperature<br />

differential 5÷10 K.<br />

• the minimum permitted inlet water<br />

temperature is 40°C.<br />

ATTENTION!<br />

Units fitted with a heat recovery placed in<br />

series with the compressor must be used in<br />

compliance with current local laws.<br />

Hot water for domestic use can be produced<br />

only with the use of an additional heat<br />

exchanger which is suited to the purpose.<br />

Refer to current laws and standards in the<br />

place of installation.<br />

18


TCAVBZ-TCAVIZ 2470 ÷ 2650<br />

ACCESSORIES DS and RC100: performances and pressure drops<br />

MODEL TCAVBZ - TCAVIZ 2470 2500<br />

STANDARD-SOUNDPROOFED VERSION<br />

Technical data<br />

RC100 - 100% recuperator<br />

Inlet/outlet water temperature °C 35/40 (**) 40/45 (*) 45/50 (**) 35/40 (**) 40/45 (*) 45/50 (**)<br />

Nominal heating capacity(•) kW 623 614 603 671 658 643<br />

Recuperator nominal water flow m 3 /h 108,4 107,0 107,2 116,7 114,6 114,2<br />

Recuperator nominal pressure drops kPa 70 69 69 43 41 41<br />

Recuperator water contents L 61 61 61 66 66 66<br />

DS - Desuperheater<br />

Inlet/outlet water temperature °C 40/50 (***) 50/60 (***) - 40/50 (***) 50/60 (***) -<br />

Nominal heating capacity(•) kW 93 54 - 91 50 -<br />

Recuperator nominal water flow m 3 /h 8,2 4,7 - 8,0 4,4 -<br />

Recuperator nominal pressure drops kPa 7 3 - 4 1 -<br />

Recuperator water contents L 12 12 - 16 16 -<br />

MODEL TCAVBZ - TCAVIZ 2540 2580<br />

STANDARD-SOUNDPROOFED VERSION<br />

Technical data<br />

RC100 - 100% recuperator<br />

Inlet/outlet water temperature °C 35/40 (**) 40/45 (*) 45/50 (**) 35/40 (**) 40/45 (*) 45/50 (**)<br />

Nominal heating capacity(•) kW 716 701 686 767 751 733<br />

Recuperator nominal water flow m 3 /h 124,5 122,1 121,9 133,3 130,8 130,3<br />

Recuperator nominal pressure drops kPa 48 46 46 51 49 49<br />

Recuperator water contents L 66 66 66 71 71 71<br />

DS - Desuperheater<br />

Inlet/outlet water temperature °C 40/50 (***) 50/60 (***) - 40/50 (***) 50/60 (***) -<br />

Nominal heating capacity(•) kW 100 56 - 109 62 -<br />

Recuperator nominal water flow m 3 /h 8,8 4,9 - 9,6 5,4 -<br />

Recuperator nominal pressure drops kPa 4 2 - 5 2 -<br />

Recuperator water contents L 16 16 - 16 16 -<br />

MODEL TCAVBZ - TCAVIZ 2600 2650<br />

STANDARD-SOUNDPROOFED VERSION<br />

Technical data<br />

RC100 - Recuperatore 100%<br />

Inlet/outlet water temperature °C 35/40 (**) 40/45 (*) 45/50 (**) 35/40 (**) 40/45 (*) 45/50 (**)<br />

Nominal heating capacity(•) kW 817 798 779 857 843 829<br />

Recuperator nominal water flow m 3 /h 142,0 139,0 138,3 149,0 146,8 147,3<br />

Recuperator nominal pressure drops kPa 48 46 46 52 51 51<br />

Recuperator water contents L 76 76 76 76 76 76<br />

DS - Desuperheater<br />

Inlet/outlet water temperature °C 40/50 (***) 50/60 (***) - 40/50 (***) 50/60 (***) -<br />

Nominal heating capacity(•) kW 116 66 - 130 76 -<br />

Recuperator nominal water flow m 3 /h 10,3 5,8 - 11,5 6,6 -<br />

Recuperator nominal pressure drops kPa 6 2 - 7 3 -<br />

Recuperator water contents L 16 16 - 16 16 -<br />

(•) Heating capacity with recuperator and<br />

desuperheater fouling factor of 0,35x10 -4 m 2<br />

K/W.<br />

(*) Conditions refer to the unit complete with<br />

condensation control (FI10) with standard<br />

setting and chilled water temperature 7°C,<br />

with evaporator temperature differential 5 K.<br />

(**) Conditions refer to the unit complete with<br />

condensation control (FI10) with the<br />

appropriate setting (expressly requested at<br />

the time of ordering) and chilled water<br />

temperature 7°C, with evaporator temperature<br />

differential 5 K.<br />

(***) Conditions refer to the unit with chilled<br />

water temperature 7°C, with evaporator<br />

temperature differential 5 K.<br />

Operating limits:<br />

● RC100:<br />

• temperature of hot water produced 35÷50°C<br />

with permitted water temperature differential<br />

4÷6 K.<br />

• the minimum permitted inlet water<br />

temperature is 30°C.<br />

• If the unit is equipped with the accessory<br />

and RC100 the FI10 accessory must be used.<br />

● DS:<br />

• temperature of hot water produced 45÷<br />

60°C with permitted water temperature<br />

differential 5÷10 K.<br />

• the minimum permitted inlet water<br />

temperature is 40°C.<br />

ATTENTION!<br />

Units fitted with a heat recovery placed in<br />

series with the compressor must be used in<br />

compliance with current local laws.<br />

Hot water for domestic use can be produced<br />

only with the use of an additional heat<br />

exchanger which is suited to the purpose.<br />

Refer to current laws and standards in the<br />

place of installation.<br />

19


TCAVBZ-TCAVIZ 2670<br />

ACCESSORIES DS and RC100: performances and pressure drops<br />

MODEL TCAVBZ - TCAVIZ 2670<br />

STANDARD-SOUNDPROOFED VERSION<br />

Technical data<br />

RC100 - 100% recuperator<br />

Inlet/outlet water temperature °C 35/40 (**) 40/45 (*) 45/50 (**)<br />

Nominal heating capacity(•) kW 882 872 863<br />

Recuperator nominal water flow m 3 /h 153,4 151,9 153,3<br />

Recuperator nominal pressure drops kPa 55 54 55<br />

Recuperator water contents L 76 76 76<br />

DS - Desuperheater<br />

Inlet/outlet water temperature °C 40/50 (***) 50/60 (***) -<br />

Nominal heating capacity(•) kW 141 84 -<br />

Recuperator nominal water flow m 3 /h 12,4 7,4 -<br />

Recuperator nominal pressure drops kPa 8 3 -<br />

Recuperator water contents L 16 16 -<br />

(•) Heating capacity with recuperator and<br />

desuperheater fouling factor of 0,35x10 -4 m 2<br />

K/W.<br />

(*) Conditions refer to the unit complete with<br />

condensation control (FI10) with standard<br />

setting and chilled water temperature 7°C,<br />

with evaporator temperature differential 5 K.<br />

(**) Conditions refer to the unit complete with<br />

condensation control (FI10) with the<br />

appropriate setting (expressly requested at<br />

the time of ordering) and chilled water<br />

temperature 7°C, with evaporator temperature<br />

differential 5 K.<br />

(***) Conditions refer to the unit with chilled<br />

water temperature 7°C, with evaporator<br />

temperature differential 5 K.<br />

Operating limits:<br />

● RC100:<br />

• temperature of hot water produced 35÷50°C<br />

with permitted water temperature differential<br />

4÷6 K.<br />

• the minimum permitted inlet water<br />

temperature is 30°C.<br />

• If the unit is equipped with the accessory<br />

and RC100 the FI10 accessory must be used.<br />

● DS:<br />

• temperature of hot water produced 45÷<br />

60°C with permitted water temperature<br />

differential 5÷10 K.<br />

• the minimum permitted inlet water<br />

temperature is 40°C.<br />

ATTENTION!<br />

Units fitted with a heat recovery placed in<br />

series with the compressor must be used in<br />

compliance with current local laws.<br />

Hot water for domestic use can be produced<br />

only with the use of an additional heat<br />

exchanger which is suited to the purpose.<br />

Refer to current laws and standards in the<br />

place of installation.<br />

20


TCAVSZ 2310 ÷ 2430<br />

ACCESSORIES DS and RC100: performances and pressure drops<br />

MODEL TCAVSZ 2310 2320<br />

SILENT VERSION<br />

Technical data<br />

RC100 - 100% recuperator<br />

Inlet/outlet water temperature °C 35/40 (**) 40/45 (*) 45/50 (**) 35/40 (**) 40/45 (*) 45/50 (**)<br />

Nominal heating capacity(•) kW 408 401 393 434 426 418<br />

Recuperator nominal water flow m 3 /h 71,0 69,9 69,9 75,4 74,2 74,3<br />

Recuperator nominal pressure drops kPa 57 56 56 64 62 62<br />

Recuperator water contents L 38 38 38 38 38 38<br />

DS - Desuperheater<br />

Inlet/outlet water temperature °C 40/50 (***) 50/60 (***) - 40/50 (***) 50/60 (***) -<br />

Nominal heating capacity(•) kW 64 38 - 69 42 -<br />

Recuperator nominal water flow m 3 /h 5,6 3,3 - 6,1 3,7 -<br />

Recuperator nominal pressure drops kPa 8 3 - 10 4 -<br />

Recuperator water contents L 9 9 - 9 9 -<br />

MODEL TCAVSZ 2340 2360<br />

SILENT VERSION<br />

Technical data<br />

RC100 - 100% recuperator<br />

Inlet/outlet water temperature °C 35/40 (**) 40/45 (*) 45/50 (**) 35/40 (**) 40/45 (*) 45/50 (**)<br />

Nominal heating capacity(•) kW 460 453 444 493 484 475<br />

Recuperator nominal water flow m 3 /h 80,0 78,9 78,9 85,7 84,3 84,3<br />

Recuperator nominal pressure drops kPa 71 69 69 65 63 63<br />

Recuperator water contents L 38 38 38 45 45 45<br />

DS - Desuperheater<br />

Inlet/outlet water temperature °C 40/50 (***) 50/60 (***) - 40/50 (***) 50/60 (***) -<br />

Nominal heating capacity(•) kW 77 48 - 88 56 -<br />

Recuperator nominal water flow m 3 /h 6,8 4,2 - 7,7 4,9 -<br />

Recuperator nominal pressure drops kPa 12 5 - 15 6 -<br />

Recuperator water contents L 9 9 - 10,5 10,5 -<br />

MODEL TCAVSZ 2400 2430<br />

SILENT VERSION<br />

Technical data<br />

RC100 - 100% recuperator<br />

Inlet/outlet water temperature °C 35/40 (**) 40/45 (*) 45/50 (**) 35/40 (**) 40/45 (*) 45/50 (**)<br />

Nominal heating capacity(•) kW 522 514 504 567 559 548<br />

Recuperator nominal water flow m 3 /h 90,8 89,5 89,6 98,6 97,4 97,4<br />

Recuperator nominal pressure drops kPa 72 70 70 59 58 58<br />

Recuperator water contents L 45 45 45 61 61 61<br />

DS - Desuperheater<br />

Inlet/outlet water temperature °C 40/50 (***) 50/60 (***) - 40/50 (***) 50/60 (***) -<br />

Nominal heating capacity(•) kW 73 42 - 83 49 -<br />

Recuperator nominal water flow m 3 /h 6,4 3,6 - 7,3 4,3 -<br />

Recuperator nominal pressure drops kPa 4 2 - 6 2 -<br />

Recuperator water contents L 12 12 - 12 12 -<br />

(•) Heating capacity with recuperator and<br />

desuperheater fouling factor of 0,35x10 -4 m 2<br />

K/W.<br />

(*) Conditions refer to the unit complete with<br />

condensation control (FI10) with standard<br />

setting and chilled water temperature 7°C,<br />

with evaporator temperature differential 5 K.<br />

(**) Conditions refer to the unit complete with<br />

condensation control (FI10) with the<br />

appropriate setting (expressly requested at<br />

the time of ordering) and chilled water<br />

temperature 7°C, with evaporator temperature<br />

differential 5 K.<br />

(***) Conditions refer to the unit with chilled<br />

water temperature 7°C, with evaporator<br />

temperature differential 5 K.<br />

Operating limits:<br />

● RC100:<br />

• temperature of hot water produced 35÷50°C<br />

with permitted water temperature differential<br />

4÷6 K.<br />

• the minimum permitted inlet water<br />

temperature is 30°C.<br />

• If the unit is equipped with the accessory<br />

and RC100 the FI10 accessory must be used.<br />

● DS:<br />

• temperature of hot water produced 45÷<br />

60°C with permitted water temperature<br />

differential 5÷10 K.<br />

• the minimum permitted inlet water<br />

temperature is 40°C.<br />

ATTENTION!<br />

Units fitted with a heat recovery placed in<br />

series with the compressor must be used in<br />

compliance with current local laws.<br />

Hot water for domestic use can be produced<br />

only with the use of an additional heat<br />

exchanger which is suited to the purpose.<br />

Refer to current laws and standards in the<br />

place of installation.<br />

21


TCAVSZ 2310 ÷ 2430<br />

ACCESSORIES DS and RC100: performances and pressure drops<br />

MODEL TCAVSZ 2470 2500<br />

SILENT VERSION<br />

Technical data<br />

RC100 - 100% recuperator<br />

Inlet/outlet water temperature °C 35/40 (**) 40/45 (*) 45/50 (**) 35/40 (**) 40/45 (*) 45/50 (**)<br />

Nominal heating capacity(•) kW 623 614 603 671 658 643<br />

Recuperator nominal water flow m 3 /h 108,4 107,0 107,2 116,7 114,6 114,2<br />

Recuperator nominal pressure drops kPa 70 69 69 43 41 41<br />

Recuperator water contents L 61 61 61 66 66 66<br />

DS - Desuperheater<br />

Inlet/outlet water temperature °C 40/50 (***) 50/60 (***) - 40/50 (***) 50/60 (***) -<br />

Nominal heating capacity(•) kW 95 57 - 92 52 -<br />

Recuperator nominal water flow m 3 /h 8,4 5,0 - 8,1 4,6 -<br />

Recuperator nominal pressure drops kPa 7 3 - 4 1 -<br />

Recuperator water contents L 12 12 - 16 16 -<br />

MODEL TCAVSZ 2540 2580<br />

SILENT VERSION<br />

Technical data<br />

RC100 - 100% recuperator<br />

Inlet/outlet water temperature °C 35/40 (**) 40/45 (*) 45/50 (**) 35/40 (**) 40/45 (*) 45/50 (**)<br />

Nominal heating capacity(•) kW 716 701 686 767 751 733<br />

Recuperator nominal water flow m 3 /h 124,5 122,1 121,9 133,3 130,8 130,3<br />

Recuperator nominal pressure drops kPa 48 46 46 51 49 49<br />

Recuperator water contents L 66 66 66 71 71 71<br />

DS - Desuperheater<br />

Inlet/outlet water temperature °C 40/50 (***) 50/60 (***) - 40/50 (***) 50/60 (***) -<br />

Nominal heating capacity(•) kW 101 58 - 109 64 -<br />

Recuperator nominal water flow m 3 /h 8,9 5,1 - 9,6 5,6 -<br />

Recuperator nominal pressure drops kPa 5 2 - 5 2 -<br />

Recuperator water contents L 16 16 - 16 16 -<br />

MODEL TCAVSZ 2600 2650<br />

SILENT VERSION<br />

Technical data<br />

RC100 - 100% recuperator<br />

Inlet/outlet water temperature °C 35/40 (**) 40/45 (*) 45/50 (**) 35/40 (**) 40/45 (*) 45/50 (**)<br />

Nominal heating capacity(•) kW 817 798 779 857 843 829<br />

Recuperator nominal water flow m 3 /h 142,0 139,0 138,3 149,0 146,8 147,3<br />

Recuperator nominal pressure drops kPa 48 46 46 52 51 51<br />

Recuperator water contents L 76 76 76 76 76 76<br />

DS - Desuperheater<br />

Inlet/outlet water temperature °C 40/50 (***) 50/60 (***) - 40/50 (***) 50/60 (***) -<br />

Nominal heating capacity(•) kW 118 69 - 131 78 -<br />

Recuperator nominal water flow m 3 /h 10,4 6,1 - 11,5 6,8 -<br />

Recuperator nominal pressure drops kPa 6 2 - 7 3 -<br />

Recuperator water contents L 16 16 - 16 16 -<br />

(•) Heating capacity with recuperator and<br />

desuperheater fouling factor of 0,35x10 -4 m 2<br />

K/W.<br />

(*) Conditions refer to the unit complete with<br />

condensation control (FI10) with standard<br />

setting and chilled water temperature 7°C,<br />

with evaporator temperature differential 5 K.<br />

(**) Conditions refer to the unit complete with<br />

condensation control (FI10) with the<br />

appropriate setting (expressly requested at<br />

the time of ordering) and chilled water<br />

temperature 7°C, with evaporator temperature<br />

differential 5 K.<br />

(***) Conditions refer to the unit with chilled<br />

water temperature 7°C, with evaporator<br />

temperature differential 5 K.<br />

Operating limits:<br />

● RC100:<br />

• temperature of hot water produced 35÷50°C<br />

with permitted water temperature differential<br />

4÷6 K.<br />

• the minimum permitted inlet water<br />

temperature is 30°C.<br />

• If the unit is equipped with the accessory<br />

and RC100 the FI10 accessory must be used.<br />

● DS:<br />

• temperature of hot water produced 45÷<br />

60°C with permitted water temperature<br />

differential 5÷10 K.<br />

• the minimum permitted inlet water<br />

temperature is 40°C.<br />

ATTENTION!<br />

Units fitted with a heat recovery placed in<br />

series with the compressor must be used in<br />

compliance with current local laws.<br />

Hot water for domestic use can be produced<br />

only with the use of an additional heat<br />

exchanger which is suited to the purpose.<br />

Refer to current laws and standards in the<br />

place of installation.<br />

22


TCAVSZ 2670<br />

ACCESSORIES DS and RC100: performances and pressure drops<br />

MODEL TCAVSZ 2670<br />

SILENT VERSION<br />

Technical data<br />

RC100 - 100% recuperator<br />

Inlet/outlet water temperature °C 35/40 (**) 40/45 (*) 45/50 (**)<br />

Nominal heating capacity(•) kW 882 872 863<br />

Recuperator nominal water flow m 3 /h 153,4 151,9 153,3<br />

Recuperator nominal pressure drops kPa 55 54 55<br />

Recuperator water contents L 76 76 76<br />

DS - Desuperheater<br />

Inlet/outlet water temperature °C 40/50 (***) 50/60 (***) -<br />

Nominal heating capacity(•) kW 142 87 -<br />

Recuperator nominal water flow m 3 /h 12,5 7,6 -<br />

Recuperator nominal pressure drops kPa 8 3 -<br />

Recuperator water contents L 16 16 -<br />

(•) Heating capacity with recuperator and<br />

desuperheater fouling factor of 0,35x10 -4 m 2<br />

K/W.<br />

(*) Conditions refer to the unit complete with<br />

condensation control (FI10) with standard<br />

setting and chilled water temperature 7°C,<br />

with evaporator temperature differential 5 K.<br />

(**) Conditions refer to the unit complete with<br />

condensation control (FI10) with the<br />

appropriate setting (expressly requested at<br />

the time of ordering) and chilled water<br />

temperature 7°C, with evaporator temperature<br />

differential 5 K.<br />

(***) Conditions refer to the unit with chilled<br />

water temperature 7°C, with evaporator<br />

temperature differential 5 K.<br />

Operating limits:<br />

● RC100:<br />

• temperature of hot water produced 35÷50°C<br />

with permitted water temperature differential<br />

4÷6 K.<br />

• the minimum permitted inlet water<br />

temperature is 30°C.<br />

• If the unit is equipped with the accessory<br />

and RC100 the FI10 accessory must be used.<br />

● DS:<br />

• temperature of hot water produced 45÷<br />

60°C with permitted water temperature<br />

differential 5÷10 K.<br />

• the minimum permitted inlet water<br />

temperature is 40°C.<br />

ATTENTION!<br />

Units fitted with a heat recovery placed in<br />

series with the compressor must be used in<br />

compliance with current local laws.<br />

Hot water for domestic use can be produced<br />

only with the use of an additional heat<br />

exchanger which is suited to the purpose.<br />

Refer to current laws and standards in the<br />

place of installation.<br />

23


TCAVBZ - TCAVIZ - TCAVSZ 2310 - 2320 - 2340 - 2360:<br />

overall dimensions and installation clearances<br />

TCAVBZ - TCAVIZ - TCAVSZ 2310 - 2320 - 2340 - 2360. Model with plate exchanger.<br />

1<br />

2 3<br />

5<br />

9 10<br />

7<br />

15<br />

11<br />

16<br />

13<br />

8<br />

14<br />

4<br />

c<br />

6<br />

f<br />

12<br />

g<br />

h<br />

e<br />

d<br />

b<br />

e<br />

l<br />

p<br />

m<br />

a<br />

q<br />

n<br />

r<br />

o<br />

i<br />

i<br />

1. Electric panel<br />

2. Electrical panel<br />

3. Fan<br />

4. Power input<br />

5. Main isolator switch<br />

6. Hoisting hook<br />

7. Pressure gauges and pressure switches<br />

8. Compressor<br />

9. Coil<br />

10. Coil protection grille (accessory)<br />

11. Lower compartment protection grilles<br />

(accessory)<br />

12. Vibration damper (accessory)<br />

13. Evaporator water inlet “Victaulic fittings”<br />

14. Evaporator water outlet “Victaulic fittings”<br />

15. Electronic expansion valve<br />

16. Soundproofing TCAVIZ<br />

MODEL 2310 2320 2340 2360<br />

Dimensions<br />

a mm 3830 3833 3830 3830<br />

b mm 2260 2260 2260 2260<br />

c mm 2430 2430 2430 2430<br />

d mm 2100 2100 2100 2100<br />

e mm 60 60 60 60<br />

f (*) mm 100 100 100 100<br />

g mm 836 836 836 836<br />

h mm 313 313 313 313<br />

i mm 1113 1113 1113 1113<br />

l mm 356 356 356 356<br />

m mm 1100 1100 1100 1100<br />

n mm 1650 1650 1650 1650<br />

o mm 356 356 356 356<br />

p mm 1306 1306 1306 1306<br />

q mm 1670 1670 1670 1670<br />

r mm 486 486 486 486<br />

Evaporator inlet/outlet water connections DN80 DN80 DN80 DN80<br />

(*) The dimensions are approximate for the<br />

presence of a a leveling jack on the<br />

antivibration mounting.<br />

ATTENTION!<br />

The desuperheater(DS) and heat recovery<br />

(RC100) accessories were not dimensioned<br />

because the data is subject to evaluation and<br />

modification by our technical office.<br />

Contact our pre-sales office for any further<br />

information.<br />

24


TCAVBZ - TCAVIZ - TCAVSZ 2310 - 2320 - 2340 - 2360:<br />

overall dimensions and installation clearances<br />

TCAVBZ - TCAVIZ - TCAVSZ 2310 - 2320 - 2340 - 2360. Model with shell and tube evaporator (STE accessory).<br />

1<br />

2 3<br />

5<br />

9<br />

10<br />

16<br />

7<br />

11<br />

13<br />

4<br />

c<br />

8<br />

14<br />

15<br />

6<br />

f<br />

12<br />

g<br />

e<br />

d<br />

b<br />

e<br />

p<br />

m<br />

q<br />

n<br />

h i l<br />

a<br />

r<br />

o<br />

1. Electric panel<br />

2. Electrical panel<br />

3. Fan<br />

4. Power input<br />

5. Main isolator switch<br />

6. Hoisting hook<br />

7. Pressure gauges and pressure switches<br />

8. Compressor<br />

9. Coil<br />

10. Coil protection grille (accessory)<br />

11. Lower compartment protection grilles<br />

(accessory)<br />

12. Vibration damper (accessory)<br />

13. Evaporator water inlet “Victaulic fittings”<br />

14. Evaporator water outlet “Victaulic fittings”<br />

15. Electronic expansion valve<br />

16. Soundproofing TCAVIZ<br />

MODEL 2310 2320 2340 2360<br />

Dimensions<br />

a mm 3830 3830 3830 3830<br />

b mm 2260 2260 2260 2260<br />

c mm 2430 2430 2430 2430<br />

d mm 2100 2100 2100 2100<br />

e mm 60 60 60 60<br />

f (*) mm 100 100 100 100<br />

g mm 471 471 471 471<br />

h mm 371 371 371 371<br />

i mm 2150 2150 2150 2150<br />

l mm 941 941 941 941<br />

m mm 356 356 356 356<br />

n mm 2750 2750 2750 2750<br />

o mm 356 356 356 356<br />

p mm 526 526 526 526<br />

q mm 2450 2450 2450 2450<br />

r mm 486 486 486 486<br />

Evaporator inlet/outlet water connections DN125 DN125 DN125 DN125<br />

(*) The dimensions are approximate for the<br />

presence of a a leveling jack on the<br />

antivibration mounting.<br />

ATTENTION!<br />

The desuperheater(DS) and heat recovery<br />

(RC100) accessories were not dimensioned<br />

because the data is subject to evaluation and<br />

modification by our technical office.<br />

Contact our pre-sales office for any further<br />

information.<br />

25


TCAVBZ - TCAVIZ - TCAVSZ 2400 - 2430 - 2470:<br />

overall dimensions and installation clearances<br />

TCAVBZ - TCAVIZ - TCAVSZ 2400 - 2430 - 2470. Model with plate exchanger.<br />

1<br />

2 5<br />

3<br />

9 10<br />

15<br />

7<br />

6<br />

11<br />

16<br />

13<br />

8<br />

14<br />

4<br />

c<br />

g<br />

12<br />

f<br />

h<br />

e<br />

d<br />

e<br />

p<br />

q<br />

r<br />

i<br />

i<br />

b<br />

l<br />

m<br />

n<br />

o<br />

a<br />

1. Electric panel<br />

2. Electrical panel<br />

3. Fan<br />

4. Power input<br />

5. Main isolator switch<br />

6. Hoisting hook<br />

7. Pressure gauges and pressure switches<br />

8. Compressor<br />

9. Coil<br />

10. Coil protection grille (accessory)<br />

11. Lower compartment protection grilles<br />

(accessory)<br />

12. Vibration damper (accessory)<br />

13. Evaporator water inlet “Victaulic fittings”<br />

14. Evaporator water outlet “Victaulic fittings”<br />

15. Electronic expansion valve<br />

16. Soundproofing TCAVIZ<br />

MODEL 2400 2430 2470<br />

Dimensions<br />

a mm 4830 4830 4830<br />

b mm 2260 2260 2260<br />

c mm 2430 2430 2430<br />

d mm 2100 2100 2100<br />

e mm 60 60 60<br />

f (*) mm 100 100 100<br />

g mm 836 836 836<br />

h mm 313 313 313<br />

i mm 1113 1113 1113<br />

l mm 806 806 806<br />

m mm 2000 2000 2000<br />

n mm 850 850 850<br />

o mm 806 806 806<br />

p mm 1656 1656 1656<br />

q mm 2051 2051 2051<br />

r mm 755 755 755<br />

Evaporator inlet/outlet water connections DN80 DN80 DN80<br />

(*) The dimensions are approximate for the<br />

presence of a a leveling jack on the<br />

antivibration mounting.<br />

ATTENTION!<br />

The desuperheater(DS) and heat recovery<br />

(RC100) accessories were not dimensioned<br />

because the data is subject to evaluation and<br />

modification by our technical office.<br />

Contact our pre-sales office for any further<br />

information.<br />

26


TCAVBZ - TCAVIZ - TCAVSZ 2400 - 2430 - 2470:<br />

overall dimensions and installation clearances<br />

TCAVBZ - TCAVIZ - TCAVSZ 2400 - 2430 - 2470. Model with shell and tube evaporator (STE accessory).<br />

1<br />

2 3<br />

5 8 10<br />

16<br />

7<br />

9<br />

11<br />

14<br />

13<br />

6<br />

4<br />

c<br />

f<br />

12<br />

g<br />

15<br />

e<br />

d<br />

e<br />

p<br />

q<br />

r<br />

b<br />

m<br />

n<br />

o<br />

h i l<br />

a<br />

1. Electric panel<br />

2. Electrical panel<br />

3. Fan<br />

4. Power input<br />

5. Main isolator switch<br />

6. Hoisting hook<br />

7. Pressure gauges and pressure switches<br />

8. Compressor<br />

9. Coil<br />

10. Coil protection grille (accessory)<br />

11. Lower compartment protection grilles<br />

(accessory)<br />

12. Vibration damper (accessory)<br />

13. Evaporator water inlet “Victaulic fittings”<br />

14. Evaporator water outlet “Victaulic fittings”<br />

15. Electronic expansion valve<br />

16. Soundproofing TCAVIZ<br />

MODEL 2400 2430 2470<br />

Dimensions<br />

a mm 4830 4830 4830<br />

b mm 2260 2260 2260<br />

c mm 2430 2430 2430<br />

d mm 2100 2100 2100<br />

e mm 60 60 60<br />

f (*) mm 100 100 100<br />

g mm 471 471 471<br />

h mm 996 996 996<br />

i mm 2400 2400 2400<br />

l mm 1066 1066 1066<br />

m mm 806 806 806<br />

n mm 2850 2850 2850<br />

o mm 806 806 806<br />

p mm 1204 1204 1204<br />

q mm 1204 1204 1204<br />

r mm 2503 2503 2503<br />

s mm 755 755 755<br />

Evaporator inlet/outlet water connections DN125 DN125 DN125<br />

(*) The dimensions are approximate for the<br />

presence of a a leveling jack on the<br />

antivibration mounting.<br />

ATTENTION!<br />

The desuperheater(DS) and heat recovery<br />

(RC100) accessories were not dimensioned<br />

because the data is subject to evaluation and<br />

modification by our technical office.<br />

Contact our pre-sales office for any further<br />

information.<br />

27


TCAVBZ - TCAVIZ - TCAVSZ 2500 - 2540 - 2580 - 2600:<br />

overall dimensions and installation clearances<br />

TCAVBZ - TCAVIZ - TCAVSZ 2500 - 2540 - 2580 - 2600. Model with shell and tube evaporator.<br />

1<br />

2 3<br />

5 9 13<br />

10 16<br />

7<br />

11<br />

8<br />

14<br />

6<br />

4<br />

c<br />

15<br />

12<br />

f<br />

12<br />

g<br />

e<br />

d<br />

b<br />

e<br />

m<br />

q<br />

n<br />

r<br />

o<br />

s<br />

p<br />

h i l<br />

a<br />

1. Electric panel<br />

2. Electrical panel<br />

3. Fan<br />

4. Power input<br />

5. Main isolator switch<br />

6. Hoisting hook<br />

7. Pressure gauges and pressure switches<br />

8. Compressor<br />

9. Coil<br />

10. Coil protection grille (accessory)<br />

11. Lower compartment protection grilles<br />

(accessory)<br />

12. Vibration damper (accessory)<br />

13. Evaporator water inlet “Victaulic fittings”<br />

14. Evaporator water outlet “Victaulic fittings”<br />

15. Electronic expansion valve<br />

16. Soundproofing TCAVIZ<br />

MODEL 2500 2540 2580 2600<br />

Dimensions<br />

a mm 5830 5830 5830 5830<br />

b mm 2260 2260 2260 2260<br />

c mm 2430 2430 2430 2430<br />

d mm 2100 2100 2100 2100<br />

e mm 60 60 60 60<br />

f (*) mm 100 100 100 100<br />

g mm 426 426 426 426<br />

h mm 746 746 746 746<br />

i mm 2412 2412 2412 2412<br />

l mm 2304 2304 2304 2304<br />

m mm 806 806 806 806<br />

n mm 1925 1925 1925 1925<br />

o mm 1925 1925 1925 1925<br />

p mm 806 806 806 806<br />

q mm 1656 1656 1656 1656<br />

r mm 3430 3430 3430 3430<br />

s mm 376 376 376 376<br />

Evaporator inlet/outlet water connections DN150 DN150 DN150 DN150<br />

(*) The dimensions are approximate for the<br />

presence of a a leveling jack on the<br />

antivibration mounting.<br />

ATTENTION!<br />

The desuperheater(DS) and heat recovery<br />

(RC100) accessories were not dimensioned<br />

because the data is subject to evaluation and<br />

modification by our technical office.<br />

Contact our pre-sales office for any further<br />

information.<br />

28


TCAVBZ - TCAVIZ - TCAVSZ 2650 - 2670:<br />

overall dimensions and installation clearances<br />

TCAVBZ - TCAVIZ - TCAVSZ 2650 - 2670. Model with shell and tube evaporator.<br />

1<br />

2 3 5 9 10<br />

7<br />

13 16<br />

11<br />

8<br />

4<br />

c<br />

14<br />

15<br />

6<br />

f<br />

12<br />

g<br />

e<br />

d<br />

b<br />

e<br />

m<br />

r<br />

n<br />

s<br />

t<br />

o p q<br />

h i l<br />

a<br />

1. Electric panel<br />

2. Electrical panel<br />

3. Fan<br />

4. Power input<br />

5. Main isolator switch<br />

6. Hoisting hook<br />

7. Pressure gauges and pressure switches<br />

8. Compressor<br />

9. Coil<br />

10. Coil protection grille (accessory)<br />

11. Lower compartment protection grilles<br />

(accessory)<br />

12. Vibration damper (accessory)<br />

13. Evaporator water inlet “Victaulic fittings”<br />

14. Evaporator water outlet “Victaulic fittings”<br />

15. Electronic expansion valve<br />

16. Soundproofing TCAVIZ<br />

MODEL 2650 2670<br />

Dimensions<br />

a mm 6680 6680<br />

b mm 2260 2260<br />

c mm 2430 2430<br />

d mm 2100 2100<br />

e mm 60 60<br />

f (*) mm 100 100<br />

g mm 426 426<br />

h mm 746 746<br />

i mm 2412 2412<br />

l mm 3454 3454<br />

m mm 1456 1456<br />

n mm 1650 1650<br />

o mm 1650 1650<br />

p mm 1650 1650<br />

q mm 206 206<br />

r mm 1976 1976<br />

s mm 3760 3760<br />

t mm 876 876<br />

Evaporator inlet/outlet water connections DN150 DN150<br />

(*) The dimensions are approximate for the<br />

presence of a a leveling jack on the<br />

antivibration mounting.<br />

ATTENTION!<br />

The desuperheater(DS) and heat recovery<br />

(RC100) accessories were not dimensioned<br />

because the data is subject to evaluation and<br />

modification by our technical office.<br />

Contact our pre-sales office for any further<br />

information.<br />

29


overall dimensions and installation clearances<br />

Clearances TCAVBZ-TCAVIZ-TCAVSZ 2310 ÷ 2670<br />

L1<br />

L4<br />

L3<br />

L2<br />

Installation<br />

● The unit features Victaulic fittings on the<br />

air-conditioning system water inlet and outlet<br />

and on the inlets and outlets to the heat<br />

recovery/desuperheaters, as well as welded<br />

carbon steel stubs.<br />

● The unit should be installed observing the<br />

minimum clearances recommended in figure,<br />

considering access to the hydraulic and<br />

electrical connections.<br />

● The unit can be fitted on antivibration<br />

mountings, supplied upon request (KSA and<br />

KSAM).<br />

● It is recommended to install air vent valves,<br />

on-off valves that isolate the unit from the rest<br />

of the system, and a filter. with a low pressure<br />

drop on the water inlet to the chiller or heat<br />

pump.<br />

Important note:<br />

● The space above the unit must be free of obstacles. If the unit is completely surrounded by<br />

walls, the distances indicated are still valid, as long as at least two adjacent walls are no higher<br />

than the unit itself. The minimum space allowed in height between the top of the unit and any<br />

obstacle must not be less than 3.5m.<br />

● If a series of units are installed together, the minimum space between the finned coils must<br />

not be less than 2,5 m.<br />

● For further information contact RHOSS sales support service.<br />

MODEL L1 L2 L3 L4<br />

2310 ÷ 2470 mm 1800 1500 1800 1500<br />

2310 ÷ 2470 STE (*) mm 1800 1500 2000 3500 (**)<br />

2500 ÷ 2670 mm 1800 1500 2000 3500 (**)<br />

(*) Accessory shell and tube evaporator (STE).<br />

(**) Maximum distance in order to remove the shell<br />

and tube exchanger.<br />

TCAVBZ-TCAVIZ-TCAVSZ 2310 ÷ 2670<br />

Lifting and handling<br />

● The unit must be handled and lifted up with<br />

care, so as to avoid damage to the external<br />

structure and to the mechanical and electrical<br />

parts on the inside.<br />

The unit should be moved and/or lifted by the<br />

specially provided lifting-points in the base<br />

framework. Use chains of lengths suitable to<br />

ensure stable lifting.<br />

30


weight distribution between the fixing points<br />

KSAM - Antivibration mountings<br />

models TCAVBZ-TCAVIZ-TCAVSZ 2310 ÷ 2670<br />

HF<br />

E<br />

D<br />

H<br />

G<br />

F<br />

E<br />

Top view<br />

Top view<br />

A B C<br />

A B C D<br />

TCAVBZ 2310 ÷ 2670<br />

MODEL 2310 2320 2340 2360 2400 2430 2470 2500 2540 2580 2600 2650 2670<br />

Empty weight (*) kg 3420 3490 3500 3580 3920 4100 4280 4760 4780 4800 4820 5160 5210<br />

Weight (**) kg 3485 3555 3565 3656 3996 4182 4362 5016 5036 5050 5070 5410 5460<br />

Support point (**)<br />

A kg 939 963 966 974 850 900 919 1185 1189 1193 1197 548 553<br />

B kg 526 546 546 553 731 780 800 842 846 848 851 671 677<br />

C kg 264 279 277 283 404 445 462 482 484 485 487 733 740<br />

D kg 306 307 308 328 438 452 489 506 508 510 512 740 747<br />

E kg 544 547 549 573 734 750 793 844 847 849 853 742 748<br />

F kg 906 913 919 945 839 855 899 1157 1162 1165 1170 736 743<br />

G kg - - - - - - - - - - - 678 684<br />

H kg - - - - - - - - - - - 562 568<br />

TCAVIZ - TCAVSZ 2310 ÷ 2670<br />

MODEL 2310 2320 2340 2360 2400 2430 2470 2500 2540 2580 2600 2650 2670<br />

Empty weight (*) kg 3720 3790 3800 3880 4220 4400 4580 5060 5080 5100 5120 5460 5510<br />

Weight (**) kg 3785 3855 3865 3956 4296 4482 4662 5316 5336 5350 5370 5710 5760<br />

Support point (**)<br />

A kg 1024 1048 1051 1059 935 985 1004 1270 1274 1278 1282 621 626<br />

B kg 589 609 609 616 794 843 863 905 909 911 914 744 750<br />

C kg 266 281 279 285 406 447 464 484 486 487 489 736 743<br />

D kg 308 309 310 330 440 454 491 508 510 512 514 741 748<br />

E kg 607 610 612 636 797 813 856 907 910 912 916 743 749<br />

F kg 991 998 1004 1030 924 940 984 1242 1247 1250 1255 739 746<br />

G kg - - - - - - - - - - - 751 757<br />

H kg - - - - - - - - - - - 635 641<br />

(*) The weight includes the accessories RPE and KRP.<br />

(**) The weight and its distribution in support points includes the accessories RPE and KRP and the amount of water contained in the heat<br />

exchanger. For TANK & PUMP <strong>version</strong>s, the weight includes the buffer tank water (1100 litre).<br />

N.B.:<br />

With the accessories RC100, DS and PUMP the weight of the unit must be added to the weight of the accessory indicated in the tables below.<br />

The weight of the TANK&PUMP <strong>version</strong> includes the weight of PUMP accessory.<br />

Pump accessory weights<br />

MODEL 2310 2320 2340 2360 2400 2430 2470 2500 2540 2580 2600 2650 2670<br />

Weight kg 120 120 120 120 130 130 130 230 230 230 230 230 230<br />

RC100 - Weights 100% recuperators<br />

MODEL 2310 2320 2340 2360 2400 2430 2470 2500 2540 2580 2600 2650 2670<br />

Weight kg 550 550 550 550 600 600 600 530 530 530 530 530 530<br />

DS - Weights desuperheaters<br />

MODEL 2310 2320 2340 2360 2400 2430 2470 2500 2540 2580 2600 2650 2670<br />

Weight kg 140 140 140 140 160 160 160 220 220 220 220 220 220<br />

31


weight distribution between the fixing points<br />

with TANK&PUMP accessory<br />

KSAM - Antivibration mountings<br />

models TCAVBZ-TCAVIZ-TCAVSZ 2310 ÷ 2470<br />

with STE accessory<br />

KSAM - Antivibration mountings<br />

models TCAVBZ-TCAVIZ-TCAVSZ 2310 ÷ 2470<br />

HF<br />

E<br />

D<br />

HD<br />

C<br />

Top view<br />

Top view<br />

A B C<br />

A<br />

B<br />

TCAVBZ 2310 ÷ 2470<br />

with TANK&PUMP accessory<br />

MODEL 2310 2320 2340 2360 2400 2430 2470<br />

Empty weight (*) kg 3930 4000 4010 4090 4470 4650 4830<br />

Weight (**) kg 5095 5165 5175 5266 5646 5832 6012<br />

Support point<br />

A kg 848 869 873 882 641 658 712<br />

B kg 852 871 871 878 886 1201 955<br />

C kg 787 803 802 808 1221 1185 1279<br />

D kg 828 831 832 852 1234 1177 1283<br />

E kg 890 895 897 920 939 907 998<br />

F kg 890 896 900 926 725 704 785<br />

TCAVBZ 2310 ÷ 2470<br />

with STE accessory<br />

MODEL 2310 2320 2340 2360 2400 2430 2470<br />

Empty weight (*) kg 3390 3450 3520 3530 3940 4120 4290<br />

Weight (**) kg 3501 3561 3631 3641 4053 4233 4403<br />

Support point<br />

A kg 828 842 859 861 1093 1142 1187<br />

B kg 918 933 952 954 926 967 1006<br />

C kg 917 933 951 954 942 983 1023<br />

D kg 838 853 869 872 1092 1141 1187<br />

TCAVIZ - TCAVSZ 2310 ÷ 2470<br />

with TANK&PUMP accessory<br />

MODEL 2310 2320 2340 2360 2400 2430 2470<br />

Empty weight (*) kg 4230 4300 4310 4390 4770 4950 5130<br />

Weight (**) kg 5395 5465 5475 5566 5946 6132 6312<br />

Support point<br />

A kg 933 954 958 967 726 743 797<br />

B kg 915 934 934 941 949 1264 1018<br />

C kg 789 805 804 810 1223 1187 1281<br />

D kg 830 833 834 854 1236 1179 1285<br />

E kg 953 958 960 983 1002 970 1061<br />

F kg 975 981 985 1011 810 789 870<br />

TCAVIZ - TCAVSZ 2310 ÷ 2470<br />

with STE accessory<br />

MODEL 2310 2320 2340 2360 2400 2430 2470<br />

Empty weight (*) kg 3690 3750 3820 3830 4240 4420 4590<br />

Weight (**) kg 3801 3861 3931 3941 4353 4533 4703<br />

Support point<br />

A kg 903 917 934 936 1168 1217 1262<br />

B kg 993 1008 1027 1029 1001 1042 1081<br />

C kg 992 1008 1026 1029 1017 1058 1098<br />

D kg 913 928 944 947 1167 1216 1262<br />

(*) The weight includes the accessories RPE and KRP.<br />

(**) The weight and its distribution in support points includes the accessories RPE and KRP and the amount of water contained in the heat<br />

exchanger. For TANK & PUMP <strong>version</strong>s, the weight includes the buffer tank water (1100 litre).<br />

N.B.:<br />

With the accessories RC100, DS and PUMP the weight of the unit must be added to the weight of the accessory indicated in the tables below.<br />

The weight of the TANK&PUMP <strong>version</strong> includes the weight of PUMP accessory.<br />

Pump accessory weights<br />

MODEL 2310 2320 2340 2360 2400 2430 2470<br />

Weight kg 120 120 120 120 130 130 130<br />

RC100 - Weights 100% recuperators<br />

MODEL 2310 2320 2340 2360 2400 2430 2470<br />

Weight kg 550 550 550 550 600 600 600<br />

DS - Weights desuperheaters<br />

MODEL 2310 2320 2340 2360 2400 2430 2470<br />

Weight kg 140 140 140 140 160 160 160<br />

32


electrical connections<br />

G<br />

10.1<br />

MI<br />

L1<br />

L2 400V-3ph-50Hz<br />

L3<br />

PE<br />

ME<br />

AG<br />

Electrical connections<br />

● The electric panel (IP55) is accessible from<br />

the front panel of the unit.<br />

● The connections must be carried out in<br />

accordance with the regulations in force and<br />

the electrical wiring diagrams included with<br />

the machine.<br />

● Earthing of the machine is compulsory by<br />

law.<br />

● Always install the unit in a sheltered area,<br />

and near the machine place an automatic<br />

main switch, or fuses, of suitable capacity and<br />

breaking power.<br />

N<br />

12.1<br />

N<br />

12.2<br />

G<br />

12.3<br />

G<br />

12.4<br />

12.5<br />

12.6<br />

12.7<br />

12.8<br />

N<br />

12.9<br />

N<br />

12.10<br />

ATTENTION!<br />

The above diagrams only show the<br />

connections to be made by the installer.<br />

CKP1<br />

CKP2 (*)<br />

SCR<br />

SDS<br />

LFC1<br />

LFC2<br />

LBG1<br />

LBG2<br />

MI<br />

ME<br />

AG<br />

CKP<br />

LBG<br />

= Internal terminal board<br />

= External terminal board<br />

= General alarm<br />

= Evaporator pump wiring harness<br />

(230 VAC voltage signal)<br />

= General lockout warning lamp (max<br />

supply 230 VAC)<br />

LBG1 = General lockout warning lamp -<br />

compressor 1 (230 VAC supply<br />

consent)<br />

LBG2 = General lockout warning lamp -<br />

compressor 2 (230 VAC supply<br />

consent)<br />

LFC<br />

= Warning lamp: compressor<br />

operating (max supply 230 VAC)<br />

LFC1 = Warning lamp: compressor 1<br />

operating (max supply 230 VAC)<br />

LFC2 = Warning lamp: compressor 2<br />

operating (max supply 230 VAC)<br />

L<br />

PE<br />

SCR<br />

SDS<br />

= Line<br />

= Earth connection<br />

= Remote control selector (clean<br />

contact control)<br />

= Double set-point selector (clean<br />

contact control)<br />

= Connection to be made by the<br />

installer<br />

(*) If double pump accessory is provided<br />

MODEL 2310 2320 2340 2360 2400 2430 2470 2500 2540 2580 2600 2650 2670<br />

Electrical data<br />

Line section mm 2 185 185 185 240 240 240 240 300 300 400 400 400 400<br />

PE section mm 2 95 95 95 120 120 120 120 150 150 185 185 185 185<br />

Remote control line section mm 2 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5 1,5<br />

Max. absorbed current TCAVBZ-TCAVIZ A 284 299 314 341 376 386 396 424 444 470 496 504 504<br />

Starting current TCAVBZ-TCAVIZ A 313 347 362 423 458 522 532 583 603 603 629 637 637<br />

Max. absorbed current TCAVSZ A 284 299 314 341 376 386 396 424 444 470 496 504 504<br />

Starting current TCAVSZ A 304 338 353 414 446 510 520 568 588 588 614 619 619<br />

Standard pressure pumps (P1) - electrical data<br />

MODEL 2310 2320 2340 2360 2400 2430 2470 2500 2540 2580 2600 2650 2670<br />

Electric pump<br />

Power supply V-ph-Hz 400-3-50<br />

Absorbed power kW 3 3 3 3 4 4 4 5,5 5,5 5,5 5,5 5,5 5,5<br />

Absorbed current A 6 6 6 6 8 8 8 11,5 11,5 11,5 11,5 11,5 11,5<br />

High pressure pumps (P2) - electrical data<br />

MODEL 2310 2320 2340 2360 2400 2430 2470 2500 2540 2580 2600 2650 2670<br />

Electric pump<br />

Power supply V-ph-Hz 400-3-50<br />

Absorbed power kW 4 4 4 4 5,5 5,5 5,5 7,5 7,5 7,5 7,5 7,5 7,5<br />

Absorbed current A 8 8 8 8 10 10 10 15,5 15,5 15,5 15,5 15,5 15,5<br />

33


NOTES


TCAVZ 2310÷2670<br />

Z-Power range<br />

RHOSS S.P.A.<br />

Via Oltre Ferrovia, 32 - 33033 Codroipo (UD) - Italy<br />

tel. +39 0432 911611 - fax +39 0432 911600<br />

rhoss@rhoss.it - www.rhoss.it - www.rhoss.com<br />

IR GROUP S.A.S.<br />

7 rue du Pont à Lunettes - 69390 Vourles - France<br />

tél. +33 (0)4 72318631 - fax +33 (0)4 72318630<br />

exportsales@rhoss.it<br />

RHOSS Deutschland GmbH<br />

Hölzlestraße 23, D-72336 Balingen, OT Engstlatt - Germany<br />

tel. +49 (0)7433 260270 - fax +49 (0)7433 2602720<br />

info@rhoss.de - www.rhoss.de<br />

RHOSS MERCOSUR<br />

Benjamin Constant 576 - 1er Piso C.P. 1214 - Asuncion Paraguay<br />

tel/fax +595 21 493 897 - www.rhossmercosur.com<br />

Sedi commerciali Italia: / Italy branch offices:<br />

Area Nord-Est: 33033 Codroipo (UD) - Via Oltre Ferrovia, 32<br />

tel. +39 0432 911611 - fax +39 0432 911600<br />

Area Nord-Ovest: 20041 Agrate Brianza (MI)<br />

Centro Colleoni - Palazzo Taurus, 1<br />

tel. +39 039 6898394 - fax +39 039 6898395<br />

Area Centro-Sud: 00199 Roma - Viale Somalia, 109<br />

tel. +39 06 8600699-707 - fax +39 06 8600747<br />

Area Sud: 80143 Napoli - Via G. Porzio - Centro Direzionale - Isola G8<br />

tel. +39 081 7879121 - fax +39 081 7879135<br />

RHOSS S.P.A. declines all responsabilities for<br />

possible mistakes in the catalogue and reserves the<br />

right to alter the features of their products without<br />

notice in the interests of continuous improvement.<br />

K20301EN ed.2<br />

07.08 - 0.000 - Stampa:

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!