Protection concept<br />

The following parameters are monitored<br />

continuously and in parallel by the microcontroller<br />

and displayed on the screen:<br />

· DC overvoltage (Fault 3)<br />

· Frequency error (Fault 4)<br />

· Overheating (Fault 5)<br />

· Grid undervoltage, 1-phase (Fault 6)<br />

· Grid overvoltage, 1-phase (Fault 7)<br />

· Grid undervoltage, 3-phase (Fault 8)<br />

· AFI error (Fault 9)<br />

· Insulation error (Fault 10)<br />

· DC feed (Fault 11)<br />

· Isolated operation (Fault 12)<br />

· Grid overvoltage, 3-phase (Fault 13)<br />

· Surge error (Fault 14)<br />

· Grid voltage 10-minute average value<br />

> 10 % U NOM (Fault 15)<br />

In the event of a fault, the conversion is<br />

blocked immediately and the grid relay is<br />

isolated. An alarm relay with floating<br />

output is activated (not for Fault 6).<br />

In addition, the following protective<br />

devices are provided on both grid and<br />

PV generator side:<br />

· Grid-side varistors<br />

Protect the power semiconductors from<br />

high-energy, time-limited voltage spikes<br />

on the grid and provide for a reduction<br />

of energy in the throttle in the event of<br />

grid disconnection.<br />

· Generator-side varistors<br />

Thermally monitored varistors provide<br />

protection against atmospheric overvoltages<br />

(e.g. due to remote strikes during<br />

storms).<br />