GB.<strong>TBLZ</strong><strong>48</strong>1.090815<br />

<strong>Installation</strong> <strong>equipment</strong> <strong>cabinet</strong> <strong>for</strong> <strong>smoke</strong> <strong>funct</strong>. <strong>TBLZ</strong>-1-<strong>48</strong>-1<br />

GOLD/COMPACT<br />

1. General<br />

Equipment cubicle <strong>for</strong> <strong>smoke</strong> <strong>funct</strong>ion consists of a control<br />

unit installed in a box with transparent cover.<br />

There are necessary terminals <strong>for</strong> external connection.<br />

The <strong>equipment</strong> cubicle is equipped with knockout grommets.<br />

2. Range of Application<br />

The <strong>equipment</strong> cubicle is used together with <strong>smoke</strong> detectors<br />

<strong>TBLZ</strong>-2-49-a. In the event of an error indication the<br />

unit is designed to control dampers and stop the unit and<br />

give an alarm. Connected damper actuators must be suitable<br />

<strong>for</strong> a 230 V supply.<br />

3. Function control unit <strong>smoke</strong><br />

The control unit is designed to meet the requirements set<br />

to provide reliable fire protection together with our <strong>smoke</strong><br />

detectors. Equipped with relay contactors <strong>for</strong> controlling<br />

dampers and fans. Besides <strong>smoke</strong> alarms, the control unit<br />

is equipped with a service alarm and error alarm relays.<br />

In the event of a <strong>smoke</strong> alarm, a red LED lights and the<br />

alarm relays trip at the same time.<br />

In the event of a service alarm on the <strong>smoke</strong> detector,<br />

the LED <strong>for</strong> the service alarm flashes quickly <strong>for</strong> 1 minute.<br />

Then the service alarm relay is active and the LED lights<br />

continuously. If the service alarm on the detector resets,<br />

the relay trips and the LED starts to flash slowly: Alarm<br />

memory.<br />

Short-circuits and open-circuits cause fault relays and<br />

alarm relays to activate at the same time as the respective<br />

LED lights (open-circuit, approx. 10 seconds delay). If a<br />

short-circuit or open-circuit recurs, the relays trip and the<br />

respective LED starts to flash slowly: Alarm memory.<br />

Exercising the relays: keep the reset button depressed <strong>for</strong><br />

5 seconds.<br />

4. <strong>Installation</strong><br />

Use the four screws to mount the <strong>equipment</strong> <strong>cabinet</strong> on<br />

the wall, unit or similar.<br />

5. Technical Data<br />

Supply voltage<br />

230VAC, 50-60Hz<br />

Power consumption<br />

1.8VA<br />

(control unit)<br />

Degree of protection IP 65<br />

Ambient temperature<br />

0-50°C<br />

Dimensions (WxHxD)<br />

175 x 125 x 100mm<br />

Weight<br />

740g<br />

Specifications are subject to alteration without notice.<br />

www.swegon.com 1


GB.<strong>TBLZ</strong><strong>48</strong>1.090815<br />

6. Electrical Connections<br />

The electrical connections are to be wired by a qualified<br />

electrician in accordance with local electrical safety regulations.<br />

GOLD RX/PX/CX/SD<br />

Terminals on the control<br />

unit<br />

25<br />

26<br />

Smoke <strong>funct</strong>ion<br />

Terminal<br />

Smoke detector terminal<br />

Ext. fire alarm<br />

54<br />

55<br />

52<br />

Ext. alarm 2<br />

53<br />

GOLD LP/COMPACT<br />

Terminals in electrical<br />

<strong>equipment</strong> cubicle<br />

201<br />

202<br />

Terminals on the control<br />

unit<br />

5<br />

*<br />

6<br />

Terminal block<br />

7<br />

**<br />

8<br />

*Should be selected <strong>for</strong> ext. fire alarm in the micro<br />

terminal.<br />

**Should be selected <strong>for</strong> ext. alarm in the micro<br />

terminal.<br />

Function:<br />

In the event of <strong>smoke</strong> detector B7<br />

deploying in the duct the alarm is <strong>for</strong>warded<br />

to GOLD/COMPACT, external<br />

fire alarm. Damper actuator MG7 is<br />

controlled via control unit B6.<br />

When the <strong>smoke</strong> detectors become<br />

dirty a service alarm occurs in control<br />

unit B6 and is <strong>for</strong>warded to GOLD/<br />

COMPACT via the external alarm 2.<br />

The alarm is reset on control unit B6 or<br />

hand terminal P1.<br />

MG7: MG7: B7: B7:<br />

Damper<br />

actuator<br />

Damper<br />

actuator<br />

In the event of more <strong>smoke</strong><br />

damper actuators being connected,<br />

these must be connected<br />

in parallel in the terminal block.<br />

Smoke detector<br />

Smoke detector<br />

In the event of more <strong>smoke</strong> detectors<br />

being connected, these<br />

must be connected in series (<br />

terminating resistor only installed<br />

on the last <strong>smoke</strong> detector).<br />

2 www.swegon.com<br />

Specifications are subject to alteration without notice.