1. General<br />
Equipment cubicle <strong>for</strong> <strong>smoke</strong> <strong>funct</strong>ion consists of a control<br />
unit installed in a box with transparent cover.<br />
There are necessary terminals <strong>for</strong> external connection.<br />
The <strong>equipment</strong> cubicle is equipped with knockout grommets.<br />
2. Range of Application<br />
The <strong>equipment</strong> cubicle is used together with <strong>smoke</strong> detectors<br />
<strong>TBLZ</strong>-2-49-a. In the event of an error indication the<br />
unit is designed to control dampers and stop the unit and<br />
give an alarm. Connected damper actuators must be suitable<br />
<strong>for</strong> a 230 V supply.<br />
3. Function control unit <strong>smoke</strong><br />
The control unit is designed to meet the requirements set<br />
to provide reliable fire protection together with our <strong>smoke</strong><br />
detectors. Equipped with relay contactors <strong>for</strong> controlling<br />
dampers and fans. Besides <strong>smoke</strong> alarms, the control unit<br />
is equipped with a service alarm and error alarm relays.<br />
In the event of a <strong>smoke</strong> alarm, a red LED lights and the<br />
alarm relays trip at the same time.<br />
In the event of a service alarm on the <strong>smoke</strong> detector,<br />
the LED <strong>for</strong> the service alarm flashes quickly <strong>for</strong> 1 minute.<br />
Then the service alarm relay is active and the LED lights<br />
continuously. If the service alarm on the detector resets,<br />
the relay trips and the LED starts to flash slowly: Alarm<br />
memory.<br />
Short-circuits and open-circuits cause fault relays and<br />
alarm relays to activate at the same time as the respective<br />
LED lights (open-circuit, approx. 10 seconds delay). If a<br />
short-circuit or open-circuit recurs, the relays trip and the<br />
respective LED starts to flash slowly: Alarm memory.<br />
Exercising the relays: keep the reset button depressed <strong>for</strong><br />
5 seconds.<br />
4. <strong>Installation</strong><br />
Use the four screws to mount the <strong>equipment</strong> <strong>cabinet</strong> on<br />
the wall, unit or similar.<br />
5. Technical Data<br />
Supply voltage<br />
230VAC, 50-60Hz<br />
Power consumption<br />
1.8VA<br />
(control unit)<br />
Degree of protection IP 65<br />
Ambient temperature<br />
0-50°C<br />
Dimensions (WxHxD)<br />
175 x 125 x 100mm<br />
Weight<br />
740g<br />
Specifications are subject to alteration without notice.<br />
www.swegon.com 1
GB.<strong>TBLZ</strong><strong>48</strong>1.090815<br />
6. Electrical Connections<br />
The electrical connections are to be wired by a qualified<br />
electrician in accordance with local electrical safety regulations.<br />
GOLD RX/PX/CX/SD<br />
Terminals on the control<br />
unit<br />
25<br />
26<br />
Smoke <strong>funct</strong>ion<br />
Terminal<br />
Smoke detector terminal<br />
Ext. fire alarm<br />
54<br />
55<br />
52<br />
Ext. alarm 2<br />
53<br />
GOLD LP/COMPACT<br />
Terminals in electrical<br />
<strong>equipment</strong> cubicle<br />
201<br />
202<br />
Terminals on the control<br />
unit<br />
5<br />
*<br />
6<br />
Terminal block<br />
7<br />
**<br />
8<br />
*Should be selected <strong>for</strong> ext. fire alarm in the micro<br />
terminal.<br />
**Should be selected <strong>for</strong> ext. alarm in the micro<br />
terminal.<br />
Function:<br />
In the event of <strong>smoke</strong> detector B7<br />
deploying in the duct the alarm is <strong>for</strong>warded<br />
to GOLD/COMPACT, external<br />
fire alarm. Damper actuator MG7 is<br />
controlled via control unit B6.<br />
When the <strong>smoke</strong> detectors become<br />
dirty a service alarm occurs in control<br />
unit B6 and is <strong>for</strong>warded to GOLD/<br />
COMPACT via the external alarm 2.<br />
The alarm is reset on control unit B6 or<br />
hand terminal P1.<br />
MG7: MG7: B7: B7:<br />
Damper<br />
actuator<br />
Damper<br />
actuator<br />
In the event of more <strong>smoke</strong><br />
damper actuators being connected,<br />
these must be connected<br />
in parallel in the terminal block.<br />
Smoke detector<br />
Smoke detector<br />
In the event of more <strong>smoke</strong> detectors<br />
being connected, these<br />
must be connected in series (<br />
terminating resistor only installed<br />
on the last <strong>smoke</strong> detector).<br />