01.11.2012 Views

Nockenschalter Cam switches - ELEKTRA Tailfingen

Nockenschalter Cam switches - ELEKTRA Tailfingen

Nockenschalter Cam switches - ELEKTRA Tailfingen

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

SL<br />

104<br />

MZ<br />

Frontbefestigung<br />

Front fixing<br />

<strong>Nockenschalter</strong> V3L<br />

<strong>Cam</strong> <strong>switches</strong> V3L<br />

Technische Daten nach EN 60 947<br />

Bemessungsisolationsspannung (III/3) EN 60 947 Ui<br />

Bemessungsstoßspannungsfestigkeit<br />

690 V~<br />

(III/3) EN 60 947 Uimp. 6 kV<br />

Bemessungsdauerstrom Iu offen/Ithe gekapselt 32 A<br />

Anschließbare Querschnitte ein- bzw. mehrdrähtig 1–6 mm2 feindrähtig mit Aderendhülse (DIN 46228) 0,75–4 mm2 Anschlussschrauben M4<br />

Kurzschlussschutz, Schmelzsicherung<br />

Hauptschaltereigenschaften nach EN 60 204<br />

(gL) 35 A max.<br />

Trennerbedingungen nach EN 60 947 erfüllt bis < 480 V<br />

Schaltvermögen bei Wechselspannung nach EN 60 947<br />

AC-21A/B Lastschalter<br />

Bemessungsbetriebsstrom Ie 32 A<br />

Bemessungsbetriebsspannung Ue 690 V~<br />

AC-23A/B Motorschalter (Hauptschalter) 220...240 V, 7,5 kW, 3~<br />

380...440 V, 15 kW, 3~<br />

AC-3 Motorschalter, für betriebsm. Schalten 220...240 V, 7,5 kW, 3~<br />

380...440 V, 11 kW, 3~<br />

AC-4 Motorschalter, Tippen, 220...240 V, 2,2 kW, 3~<br />

Gegenstrombremsen 380...440 V, 3 kW, 3~<br />

AC-15 Steuerschalter Ie bei 220–240/380–440 V 9/6 A<br />

Maßzeichnungen Dimensions<br />

Frontschild<br />

Face plate<br />

Xmax<br />

4<br />

Maß/Dimension<br />

Schaltereinsatz<br />

Insert<br />

Technical data as per EN 60 947<br />

25 A<br />

Bei diesem <strong>Nockenschalter</strong> sind 2 voneinander getrennte<br />

Kontaktsysteme in einer Kontaktkammer so angeordnet, dass<br />

sämtliche Anschlussklemmen aus einer Richtung zugänglich sind.<br />

Daher ist die Baureihe V3L prädestiniert für Anwendungen, bei<br />

denen die Anschlussschrauben nur aus einer Richtung zugänglich<br />

sind, wie z.B. bei Gehäuse einbau.<br />

This kind of cam switch has one contact chamber equipped with<br />

2 contact systems separated from each other. All terminals are<br />

therefore accessible from one direction. The switch series V3L is<br />

predestined for applications where connecting terminals are only<br />

accessible from one direction as for example by enclosure fixing.<br />

Rated insulating voltage (III/3) EN 60 947 Ui 690 V~<br />

Rated impulse voltage rigidity (III/3) EN 60 947 Uimp. 6 kV<br />

Rated permanent current Iu switch insert/Ithe<br />

under enclosure 32 A<br />

Connectable cross sections single resp. multi-strand 1–6 mm 2<br />

fine wire with core end bush (DIN 46228) 0,75–4 mm 2<br />

Terminal screws M4<br />

Short-circuit protection, fusible cut-out (gL) 35 A max.<br />

Features of main <strong>switches</strong> as per EN 60 204<br />

Requirements for isolators as per EN 60 947<br />

complied with up to < 480 V<br />

Switching capacity under alternating voltage conditions<br />

as per EN 60 947<br />

Load break <strong>switches</strong><br />

Rated operating current Ie 32 A<br />

Rated operating voltage Ue 690 V~<br />

Motor <strong>switches</strong> (main <strong>switches</strong>) 220...240 V, 7,5 kW, 3~<br />

380...440 V, 15 kW, 3~<br />

Motor <strong>switches</strong>, for operational switching 220...240 V, 7,5 kW, 3~<br />

380...440 V, 11 kW, 3~<br />

Motor <strong>switches</strong>, inching, 220...240 V, 2,2 kW, 3~<br />

reverse current braking 380...440 V, 3 kW, 3~<br />

Control <strong>switches</strong> Ie at 220–240/380–440 V 9/6 A<br />

Schalterstirnseite<br />

Front view<br />

Winkel zur Abstützung bei großer Schalterlänge<br />

Angle to support <strong>switches</strong> with large dimension in length<br />

Maß Dimension L<br />

1 2 3 4 5 6 7 8 9<br />

L 34 47 60 73 86 99 112 125 138<br />

L1 - - - - - 103 116 129 142<br />

Bohrbild in der Befestigungswand<br />

Panel drilling