Construction<br />
How to Use<br />
Surface<br />
Preparation<br />
Mixing<br />
Application<br />
Clean Up<br />
Limitations<br />
Caution<br />
First Aid<br />
Note: For optimum results when grouting in critical items of equipment, it is recommended that the surface preparation<br />
requirements of the latest edition of Chapter 5, API Recommended Practice 686 be followed. This document is the<br />
“Recommended Practices for Machinery Installation and Installation Design” published by the American Petroleum<br />
Institute. Surface and base plate contact area must be clean and sound. It may be dry or damp, but free of standing<br />
water. Remove dust, laitance, oils, grease, curing compounds, impregnations, waxes, foreign particles, coatings, and<br />
disintegrated materials by mechanical means, i. e. chipping with a chisel, sandblasting. Sandblast metal base plates to<br />
a commercial white finish (SP-10) for maximum adhesion. Apply grout immediately to prevent re-oxidizing.<br />
Forming - The consistency of the epoxy grout system requires the use of forms to contain the material around the<br />
base plates. In order to prevent leakage or seepage, all forms must be sealed. Apply polyethylene film or wax to all<br />
forms to prevent adhesion of the grout. Prepare form work to maintain more than 100 mm (4 in) liquid head to facilitate<br />
placement. A grout box equipped with an inclined trough attached to the form will enhance the grout’s flowability and<br />
minimize air encapsulation.<br />
Mix the entire contents of components A and B in the component A pail for 3 min with a paddle attached to a low speed drill<br />
(200-250 rpm). Place the mixed epoxy into an appropriate mixer. Slowly add the contents of component C depending<br />
on flow required and mix until uniformly blended (approx. 5 min). When mixing the first batch of the epoxy adhesive<br />
grout system in a clean and dry mixer, withhold 10 kg (22 lb) of component C to charge the mixer. Mixed grout should<br />
be kept agitated just prior to placement.<br />
Pour the mixed grout into the prepared forms from one or two sides only, to eliminate air entrapment. Maintain the liquid head<br />
to ensure intimate contact to the base plate. Place sufficient epoxy grout in the forms to rise slightly above the underside [3 mm<br />
(1/8 in)] of the base plate. The minimum void depth beneath the base should be 25 mm (1 in). Where the void beneath<br />
the base plate is greater than 150 mm (6 in), place the epoxy grout in successive 150 mm (6 in) lifts or less, once the<br />
preceding lift has cooled.<br />
Sweep into appropriate containers. Dispose of in accordance with applicable local regulations. Uncured material can<br />
be removed with Sika Equipment Cleaner/Epoxy Thinner. Cured material can only be removed mechanically.<br />
■ Minimum substrate temperature: 16°C (61°F).<br />
■ Grouting material must be stored in an area with an ambient temperature between 20°- 30°C (68° - 86°F) for a<br />
minimum of 48 hours before using.<br />
■ Do not thin with solvents. Solvents will prevent proper cure.<br />
■ Material is a vapour barrier after cure.<br />
■ Minimum grout depth: 25 mm (1 in).<br />
■ Maximum grout depth: 150 mm (6 in) per lift.<br />
■ Component C must be kept dry.<br />
■ For bolt grouting applications contact Sika Technical Service.<br />
■ For proper seating, allow grout to rise above the bottom [3 mm (1/8 in)] of the base plate.<br />
■ Do not batch. Mix complete units only.<br />
■ Cold ambient, substrate or material temperatures will inhibit the curing and flow characteristics of <strong>Sikadur</strong> <strong>42</strong> Grout<br />
Pak.<br />
■ Do not subject cured epoxy grout to sudden temperature changes especially during early curing stages.<br />
■ Contact Sika Technical Service for control joint spacing on large base plate grouting projects.<br />
Component A - Irritant - Prolonged contact to skin may cause irritation. Avoid eye contact.<br />
Component B - Irritant - Contact with skin may cause severe burns. Avoid eye contact.<br />
Component C - Contains silica. Avoid breathing dust. <strong>Product</strong> is a strong sensitizer. Use of safety goggles and<br />
chemical resistant gloves recommended. Avoid breathing material. Use adequate ventilation. Use of a NIOSH/MSHA<br />
organic vapour respirator recommended. Consult product label for additional information.<br />
In case of skin contact, wash with soap and water. For eye contact flush immediately with plenty of water for at least<br />
15 min. Contact a physician. For respiratory problems, transport victim to fresh air. Remove contaminated clothing<br />
and wash before re-use.<br />
For more information, consult Sika Material Safety <strong>Data</strong> <strong>Sheet</strong>.<br />
KEEP OUT OF REACH OF CHILDREN<br />
FOR INDUSTRIAL USE ONLY<br />
The information, and in particular, the recommendations relating to the application and end-use of Sika products, are given in good faith based<br />
on Sika’s current knowledge and experience of the products when properly stored, handled and applied under normal conditions, within their<br />
shelf life. In practice, the differences in materials, substrates and actual site conditions are such that no warranty in respect of merchantability or<br />
of fitness for a particular purpose, nor any liability arising out of any legal relationship whatsoever, can be inferred either from this information, or<br />
from any recommendations, or from any other advice offered. The proprietary rights of third parties must be observed. All orders are accepted<br />
subject to our current terms of sale and delivery. Users should always refer to the most recent issue of the Technical <strong>Data</strong> <strong>Sheet</strong> for the product<br />
concerned, copies of which will be supplied on request or can be accessed in the Internet under www.sika.ca.<br />
Sika Canada Inc.<br />
601 Delmar Avenue<br />
Pointe-Claire, QC H9R 4A9<br />
Tel.: (514) 697-2610<br />
Fax: (514) 697-3087<br />
Ontario<br />
6915 Davand Drive<br />
Mississauga, ON L5T 1L5<br />
Tel.: (905) 795-3177<br />
Fax: (905) 795-3192<br />
Alberta<br />
18131–114th Avenue N.W.<br />
Edmonton, AB T5S 1T8<br />
Tel.: (780) 486-6111<br />
Fax: (780) 483-1580<br />
1-800-933-SIKA<br />
www.sika.ca<br />
An ISO 9001:2000 certified company<br />
Pointe-Claire : ISO 14001:2004 certified EMS<br />
<strong>Sikadur</strong> ® <strong>42</strong> Grout Pak <strong>Multi</strong>-Flo<br />
03 63 00 epoxy Grouting 3-435