Nomenclature · Example<br />

Nomenclature<br />

V WK in l/hr: Water volume flow rate, cooling<br />

Q WK in W: Water cooling capacity<br />

q WK in W/m: Specific cooling capacity per m<br />

W/m²: or per m²<br />

t WV in °C: Chilled water flow temperature<br />

t WR in °C: Chilled water return temperature<br />

t WM in °C: Chilled water mean temperature<br />

t R in °C: Maximum room air temperature<br />

t W in K: Temperature difference between water<br />

flow and return temperature<br />

t RW in K: Temperature difference between max.<br />

room air temperature and mean chilled<br />

water temperature<br />

V in m/s: Maximum time averaged air velocity<br />

measured<br />

approx. 1 m below passive chilled beam<br />

B in mm: Width of cooling coil<br />

H in mm: Passive beam stack height<br />

fo in %: Ceiling free area underneath the <strong>TCB</strong>-<strong>RB</strong><br />

Z in mm: Return air gap above beam<br />

K Z/W<br />

Correction factor for Z /W ratio<br />

K fo<br />

Correction factor for airflow % free area<br />

p W in kPa: Water pressure drop<br />

Reference Values<br />

t WV = 16 °C Chilled water flow temperature<br />

t WR = 18 °C Chilled water return temperature<br />

t R = 27 °C Room air temperature<br />

t RW = 10 K Temperature difference between room<br />

air temperature and mean chilled water<br />

temperature<br />

Z/W = 0.5 Ratio of clear height against coil width<br />

Example<br />

Room size: 3 m x 6 m<br />

Room height: 2.8 m<br />

Suspended ceiling: 45% free area<br />

Ceiling void: 400 mm<br />

t R 24 °C<br />

t WV 14 °C<br />

t WR 17 °C<br />

t RW 8.5 K<br />

q WK 60 W/m²<br />

60 x 3 x 6 = 1080 W<br />

Q WK<br />

The architect has specified a row of units maximum 6 m<br />

along the centre line of the room (2 x 3 m)<br />

<br />

<br />

Room sketch<br />

Diagrams I…III (see page 8)<br />

Coil width (B): 410 mm<br />

Unit height (H): 250 mm<br />

Unit length (L 1 ): 3000 mm Q = 550 W<br />

For installation behind a perforated ceiling 45%,<br />

correction factor K fo must be applied.<br />

K fo : 0.99 Q = 550 W x 0.99 = 544 W<br />

Diagrams IV and V<br />

At a differential between water flow and return temperature<br />

of 3 K, the water flow rate V W = 156 l/hr. Since the water flow<br />

rate is greater then the nominal water flow rate of 110 l/hr,<br />

a correction factor K W = 1.07 is applied to the calculated<br />

capacity<br />

Q = 544 W x 1.07 = 582 W<br />

Diagram VII<br />

For installation within a ceiling void, correction factor K Z/W<br />

must be applied.<br />

Z<br />

B<br />

= (400-250) = 0.36<br />

410<br />

K Z/W : 0.97 Q = 582 W x 0.97 = 565 W<br />

For the room as planned with 2 chilled beams units<br />

3000 mm long, the available overall cooling capacity is:<br />

Q WK = 2 x 565 W = 1130 W<br />

Diagram VII<br />

Waterside pressure drop.<br />

p w = 0.7 x 3 m = 2.1 kPa<br />

Diagram VIII<br />

The air velocity 1 m below the chilled beam will be between<br />

0.17 and 0.23 m/s.<br />

NOTE: If required cooling output cannot be achieved with<br />

a 1 row coil, repeat above steps with diagrams on page 9.<br />

5