Quick Selection<br />

1 row coil<br />

Note: Diagram VIII on page 8 shows the maximum time<br />

averaged air velocity measured approximately 1m below the<br />

passive beam as a function of the output per linear meter.<br />

Cooling capacities below should be selected in line with the<br />

required comfort conditions and are subject to corrections by<br />

using the appropriate diagrams on page 8.<br />

Cooling capacity (W/m) at t RW = 10 K Z/W ~ 0.5<br />

1 Row<br />

W =<br />

258 mm,<br />

Z =<br />

130 mm<br />

W =<br />

309 mm,<br />

Z =<br />

150 mm<br />

W =<br />

360 mm,<br />

Z =<br />

180 mm<br />

W =<br />

410 mm,<br />

Z =<br />

200 mm<br />

W =<br />

461 mm,<br />

Z =<br />

230 mm<br />

W =<br />

512 mm,<br />

Z =<br />

250 mm<br />

W =<br />

563 mm,<br />

Z =<br />

280 mm<br />

W =<br />

614 mm,<br />

Z =<br />

300 mm<br />

H (mm) fo 1) 50 % 50 % 50 % 50 % 50 % 50 % 50 % 50 %<br />

150 142 161 185 207 227 247 260 276<br />

200 149 170 194 218 241 260 274 290<br />

250 157 179 204 230 258 273 288 305<br />

300 164 188 213 241 270 286 302 319<br />

Cooling capacity (W/m) at t RW = 8 K Z/W ~ 0.5<br />

1 Row<br />

W =<br />

258 mm,<br />

Z =<br />

130 mm<br />

W =<br />

309 mm,<br />

Z =<br />

150 mm<br />

W =<br />

360 mm,<br />

Z =<br />

180 mm<br />

W =<br />

410 mm,<br />

Z =<br />

200 mm<br />

W =<br />

461 mm,<br />

Z =<br />

230 mm<br />

W =<br />

512 mm,<br />

Z =<br />

250 mm<br />

W =<br />

563 mm,<br />

Z =<br />

280 mm<br />

W =<br />

614 mm,<br />

Z =<br />

300 mm<br />

H (mm) fo 1) 50 % 50 % 50 % 50 % 50 % 50 % 50 % 50 %<br />

150 114 131 148 168 188 199 210 221<br />

200 120 138 157 176 198 209 221 233<br />

250 127 146 165 186 208 220 233 245<br />

300 133 153 173 194 218 230 244 257<br />

Cooling capacity (W/m) at t RW = 7 K Z/W ~ 0.5<br />

1 Row<br />

W =<br />

258 mm,<br />

Z =<br />

130 mm<br />

W =<br />

309 mm,<br />

Z =<br />

150 mm<br />

W =<br />

360 mm,<br />

Z =<br />

180 mm<br />

W =<br />

410 mm,<br />

Z =<br />

200 mm<br />

W =<br />

461 mm,<br />

Z =<br />

230 mm<br />

W =<br />

512 mm,<br />

Z =<br />

250 mm<br />

W =<br />

563 mm,<br />

Z =<br />

280 mm<br />

W =<br />

614 mm,<br />

Z =<br />

300 mm<br />

H (mm) fo 1) 50 % 50 % 50 % 50 % 50 % 50 % 50 % 50 %<br />

150 100 114 130 147 165 175 184 195<br />

200 105 120 137 155 174 184 194 206<br />

250 111 127 144 163 183 194 204 216<br />

300 116 133 151 171 192 203 214 227<br />

1)<br />

fo: ceiling free area underneath the <strong>TCB</strong>-<strong>RB</strong><br />