04.10.2014 Views

Chilled Beam Design Guide - TROX

Chilled Beam Design Guide - TROX

Chilled Beam Design Guide - TROX

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

TB031412<br />

<strong>Chilled</strong> <strong>Beam</strong><br />

<strong>Design</strong> <strong>Guide</strong><br />

Trox USA, Inc.<br />

4305 Settingdown Circle<br />

Cumming<br />

Georgia<br />

USA 30028<br />

Telephone 770-569-1433<br />

Facsimile 770-569-1435<br />

www.troxusa.com<br />

e-mail trox@troxusa.com


Contents<br />

Introduction to <strong>Chilled</strong> <strong>Beam</strong>s 3<br />

Passive chilled beams 3<br />

Active chilled beams 5<br />

System Application <strong>Guide</strong>lines 8<br />

Benefits of chilled beams 8<br />

<strong>Chilled</strong> beam applications 9<br />

Multi-service <strong>Chilled</strong> <strong>Beam</strong>s 11<br />

System <strong>Design</strong> <strong>Guide</strong>lines 14<br />

Comfort considerations 14<br />

Air side design 15<br />

Water side design 19<br />

Control considerations 21<br />

Installation and commissioning 24<br />

<strong>Chilled</strong> <strong>Beam</strong> Selection 27<br />

Passive beams selection 27<br />

Passive beam performance data 28<br />

Active beam selection 31<br />

Active beam selection examples 35<br />

Performance Notes 38<br />

Active <strong>Beam</strong> Performance Data 39<br />

Coil pressure loss data 39<br />

DID600 series beams 44<br />

DID620 series beams 50<br />

DID300 series beams 56<br />

<strong>Chilled</strong> <strong>Beam</strong> Specifications 62<br />

Notice to Users of this <strong>Guide</strong><br />

This <strong>Guide</strong> is intended for the sole use of professionals involved in the design and specification of <strong>TROX</strong> chilled<br />

beam systems. Any reproduction of this document in any form is strictly prohibited without the written consent of<br />

<strong>TROX</strong> USA.<br />

The content herein is a collection of information from <strong>TROX</strong> and other sources that is assumed to be correct and<br />

current at the time of publication. Due to industry and product development, any and all of such content is subject<br />

to change. <strong>TROX</strong> USA will in no way be held responsible for the application of this information to system design<br />

nor will they be responsible for keeping the information up to date.<br />

2


Introduction<br />

<strong>Chilled</strong> beams have been employed in European HVAC<br />

sensible cooling only applications for over twenty years.<br />

Within the past few years they have become a popular<br />

alternative to VAV systems in North America. The<br />

growing interest in chilled beams has been fueled by<br />

their energy saving potential, ease of use as well as<br />

their minimal space requirements.<br />

<strong>Chilled</strong> beams were originally developed to supersede<br />

the outputs achieved by passive radiant cooling ceiling<br />

systems. Sensible cooling capacities of “chilled” ceilings<br />

are limited by the chilled water supply temperature<br />

(must be maintained above dew point to prevent<br />

condensation from forming on their surfaces) and the<br />

total surface area available that can be „chilled‟.<br />

Obviously, this area is limited as other services<br />

(lighting, fire protection, air distribution & extract etc.)<br />

limit the degree of employment of the active ceiling<br />

surface such that their maximum space sensible cooling<br />

capacity is very typically less than 25 BTUH per square<br />

foot of floor area. As this is not sufficient for maintaining<br />

comfort especially in perimeter areas, chilled beams<br />

very quickly became the preferred solution in so much<br />

as they occupied less space, had fewer connection and<br />

most importantly offered sensible cooling outputs 2 to 3<br />

times that of „chilled‟ ceilings.<br />

INTRODUCTION TO CHILLED BEAMS<br />

<strong>Chilled</strong> beams feature finned chilled water heat exchanger<br />

cooling coils, capable of providing up to 1100<br />

BTUH of sensible cooling per foot of length and are<br />

designed to take advantage of the significantly higher<br />

cooling efficiencies of water. Figure 1 illustrates that a<br />

one inch diameter water pipe can transport the same<br />

cooling energy as an 18 inch square air duct. The use<br />

of chilled beams can thus dramatically reduce air<br />

handler and ductwork sizes enabling more efficient use<br />

of both horizontal and vertical building space.<br />

There are two basic types of chilled beams (see figure<br />

2). Passive chilled beams are simply finned tube heat<br />

exchanger coil within a casing that provides primarily<br />

convective cooling to the space. Passive beams do not<br />

incorporate fans or any other components (ductwork,<br />

nozzles, etc.) to affect air movement. Instead they rely<br />

on natural buoyancy to recirculate air from the<br />

conditioned space and therefore needs a high free area<br />

passage to allow room air to get above the coil and<br />

cooled air to be discharge from below the coil. As they<br />

have no provisions for supplying primary air to the<br />

space, a separate source must provide space<br />

ventilation and/or humidity control, very typically<br />

combined with, but not limited to, UFAD. The air source<br />

commonly contributes to the sensible cooling of the<br />

space as well as controlling the space latent gains.<br />

Passive <strong>Chilled</strong> <strong>Beam</strong><br />

(Exposed <strong>Beam</strong> Shown)<br />

18“ x 18“<br />

Air Duct<br />

Active <strong>Chilled</strong> <strong>Beam</strong><br />

1“ diameter<br />

Water Pipe<br />

Figure 1: Cooling Energy Transport<br />

Economies of Air and Water<br />

Figure 2: Basic <strong>Beam</strong> Types<br />

Active chilled beams utilize a ducted (primary) air supply<br />

to induce secondary (room) air across their integral<br />

heat transfer coil where it is reconditioned prior to its<br />

mixing with the primary air stream and subsequent discharge<br />

into the space. The primary air supply is typically<br />

pretreated to maintain ventilation and humidity control<br />

of the space. The heat transfer coil<br />

3


Passive <strong>Chilled</strong> <strong>Beam</strong>s<br />

provides sensible cooling, it is not used to condense or<br />

provide latent cooling.<br />

Further discussion of the performance, capacities and<br />

design considerations for each type of beam is provided<br />

in the following sections of this document.<br />

PASSIVE CHILLED BEAMS<br />

Passive chilled beams are completely decoupled from<br />

the space air supply and only intended to remove sensible<br />

heat from the space. They operate most efficiently<br />

when used in thermally stratified spaces.<br />

Figure 3. illustrates the operational principle of a passive<br />

beam. Warm air plumes from heat sources rise<br />

naturally and create a warm air pool in the upper portion<br />

of the space (or ceiling cavity). As this air contacts the<br />

coil surface, the heat is removed which causes it to drop<br />

back into the space due to its negative buoyancy<br />

relative to the air surrounding it. The heat is absorbed<br />

lifting the chilled water temperature and is removed<br />

from the space via the return water circuit. About 85%<br />

of the heat removal is by convective means, therefore<br />

the radiant cooling contribution of passive chilled beams<br />

is minimal and typically ignored.<br />

combine resulting in a higher velocity in the occupied<br />

space. Air discharge across the face of the beam<br />

should be avoided as this can reduce the cooling output<br />

by inhibiting the flow of warm air into the heat exchanger<br />

coil.<br />

Passive <strong>Chilled</strong> <strong>Beam</strong> Variations<br />

Passive chilled beams may be located above or below<br />

the ceiling plane. When used with a suspended ceiling<br />

system recessed beams, <strong>TROX</strong> TCB-RB, are located a<br />

few inches above the ceiling and finished to minimize<br />

their visibility from below. Figure 4. illustrates such a<br />

recessed beam application.<br />

Figure 4: Recessed <strong>Beam</strong> Installation<br />

Recessed beams are concealed above the hung ceiling<br />

and should also include a separation skirt (TCB-RB-<br />

Skirt) which assures that the cooled air does not short<br />

circuit back to the warm air stream feeding the beam.<br />

Recessed beams (<strong>TROX</strong> series TCB) may be either<br />

uncapped (standard) or capped (more commonly<br />

known as shrouded) (see figure 5). Capped or shrouded<br />

beams have a sheet metal casing which maintains<br />

separation between the beam and the ceiling air cavity<br />

which is often used for the space return air passage.<br />

This also provides acoustical separation between adjacent<br />

spaces.<br />

Figure 3: Passive <strong>Beam</strong> Operation<br />

Passive chilled beams are capable of removing 200 to<br />

650 BTUH of sensible heat per linear foot of length<br />

depending upon their width and the temperature<br />

difference between their entering air and chilled water<br />

mean temperature. The output of the chilled beam is<br />

usually limited to ensure that the velocity of the air<br />

dropping out of the beam face and back into the<br />

occupied zone does not create drafts.<br />

It should also be noted that the air descending from a<br />

passive beam „necks‟ rather like slow running water out<br />

of a faucet. This slow discharge can be effected by other<br />

air currents around it and should passive beams be<br />

installed side by side, the two airstreams will join and<br />

Separation Skirt<br />

Figure 5: Capped Passive <strong>Beam</strong><br />

Passive beams mounted flush with or below the ceiling<br />

surface are referred to as exposed beams. Most exposed<br />

beams (e.g., <strong>TROX</strong> TCB-EB and PKV series) are<br />

furnished within cabinets designed to enhance the architectural<br />

features of the space as well as assure the<br />

necessary air passages for the beam.<br />

4


Active <strong>Chilled</strong> <strong>Beam</strong>s<br />

<strong>TROX</strong> Passive <strong>Chilled</strong> <strong>Beam</strong>s<br />

<strong>TROX</strong> USA offers 2 ranges of passive chilled beam as<br />

the core engine behind the variants.<br />

Primary air<br />

supply<br />

TCBU series beams offer a full range of 1 & 2 row<br />

recessed and exposed passive beams.<br />

PKVU series beams are 1 row passive beams<br />

with or without exposed cabinets.<br />

Figure 6 illustrates an exposed passive beam in whose<br />

cabinet other space services (lighting, smoke and<br />

occupancy detectors, etc.) have been integrated. Such<br />

integrated beams are referred to as integrated or multiservice<br />

chilled beams (MSCB). As with recessed<br />

beams, it is generally recommended that the cross<br />

sectional free area of the passage into an exposed<br />

chilled beam be equal to at least one its width. For more<br />

information on these beams see pages 11-13.<br />

Suspended<br />

ceiling<br />

Figure 7: Active <strong>Chilled</strong> <strong>Beam</strong> Operation<br />

well. In these cases, displacement ventilation and conditioning<br />

will be used to produce a thermally stratified<br />

room environment.<br />

Active chilled beams typically operate at a constant air<br />

volume flow rate, producing a variable temperature<br />

discharge to the space determined by the recirculated<br />

air heat extraction. As the water circuit can generally<br />

extract 50 to 70% of the space sensible heat generation,<br />

the ducted airflow rate can often be reduced accordingly,<br />

resulting in reduced air handling requirements<br />

as well as significantly smaller supply (and exhaust/return)<br />

ductwork and risers.<br />

Figure 6: Exposed <strong>Beam</strong> Installation<br />

ACTIVE CHILLED BEAMS<br />

In addition to chilled water coil(s), active chilled beams<br />

incorporate ducted air connections to receive pretreated<br />

supply air from a central air handling unit. This air is<br />

injected through a series of nozzles within the beam to<br />

entrain room air. Figure 7 illustrates an active beam that<br />

induces room air through a high free area section within<br />

its face and through the integral heat transfer coil where<br />

it is reconditioned in response to a space thermostat<br />

demand. The reconditioned air then mixes with the<br />

ducted (primary) air and is discharged into the space by<br />

means of linear slots located along the outside edges of<br />

the beam.<br />

Active beams mounted above the occupied zone<br />

maintain a sufficient discharge velocity to maintain a<br />

fully mixed room air distribution. As such, they employ a<br />

dilution ventilation strategy to manage the level of<br />

airborne gaseous and particulate contaminants. Certain<br />

variants of active beams (see discussion below) may be<br />

mounted in low sidewall or floor level applications as<br />

Active chilled beams can provide sensible cooling rates<br />

as high as 1100 BTUH per linear foot, depending on<br />

their induction capabilities, coil circuitry, and chilled<br />

water supply temperature. Later in this guide, you will<br />

see that careful selection of the beam must be made to<br />

ensure that high terminal velocities are avoided to maintain<br />

comfort, a beam is not just a method of providing<br />

cooling, but also a terminal discharge device that has to<br />

be selected to suit the location, space and how the<br />

space is being utilized.<br />

Active chilled beams can be used for heating as well,<br />

provided the façade heat losses are moderate.<br />

Active <strong>Chilled</strong> <strong>Beam</strong> Variations<br />

Active chilled beams come in a number of lengths and<br />

widths allowing their use in exposed mounting or<br />

integration into suspended ceiling systems, (their weight<br />

requires they be independently supported). They can be<br />

furnished with a variety of nozzle types that affect the<br />

induction rate of room air. Their discharge pattern can<br />

be supplied as either one or two way while some beams<br />

allow modification of their discharge characteristics<br />

once installed. Finally, some variants are available with<br />

condensate trays designed to collect a limited amount<br />

of unexpected condensation.<br />

5


Active <strong>Chilled</strong> <strong>Beam</strong>s<br />

DID620 series beams are a low profile beam designed to allow<br />

integration into standard 24 inch wide ceiling grids. They are ideal for<br />

applications with limited ceiling plenum spaces.<br />

DID600 series beams are also designed to allow their integration into<br />

standard 24 inch wide acoustical ceiling grids. Though slightly taller<br />

than the DID620, their construction allows easy modification to<br />

specific customer requirements.<br />

DID604 series beams are designed for four-way discharge patterns<br />

which may be suitable for location certain room sizes.<br />

DID300 series beams have a nominal face width of 12 inches and<br />

utilize two vertical chilled water coils. As such they can be furnished<br />

with condensate trays to catch any moisture that might have<br />

unexpectedly formed on the coil surfaces during periods of unusual<br />

operation.<br />

Figure 8: <strong>TROX</strong> Ceiling Mounted Active <strong>Chilled</strong> <strong>Beam</strong>s<br />

6


Active <strong>Chilled</strong> <strong>Beam</strong>s<br />

DID-E series beams are designed for high sidewall mounting in<br />

hotels and other domiciliary applications.<br />

BID series beams condition perimeter areas in UFAD applications.<br />

Conditioned air is delivered by a dedicated perimeter area air<br />

handling unit. This relieves the UFAD system of the responsibility of<br />

providing sensible cooling and heating to the perimeter, resulting in<br />

substantially reduced building airflow requirements.<br />

QLCI series beams are integrated into low sidewall mounted cabinets and<br />

to discharge conditioned air to the space in a displacement fashion. They<br />

are most commonly used for classroom HVAC as they offer significant air<br />

quality and acoustical advantages. In fact, they are the only available<br />

terminal capable of maintaining classroom sound pressure levels compliant<br />

with ANSI Standard S12.60.<br />

Figure 9: Other <strong>TROX</strong> Air-Water Products<br />

7


Benefits of <strong>Chilled</strong> <strong>Beam</strong>s<br />

CHILLED BEAM SYSTEM APPLICATION<br />

GUIDELINES<br />

<strong>Chilled</strong> beams (both passive and active) posses certain<br />

inherent advantages over all-air systems. These benefits<br />

can be divided into the three categories as follows:<br />

First cost benefits of chilled beam systems<br />

<strong>Chilled</strong> beams afford the designer an opportunity to<br />

replace large supply and return air ductwork with small<br />

chilled water pipes. This results in significant savings in<br />

terms of plenum space and increases usable floor<br />

space.<br />

• <strong>Chilled</strong> beams can be mounted in ceiling spaces<br />

as small as 8 to 10 (vertical) inches while<br />

all-air systems typically require 2 to 2.5 times<br />

that. This vertical space savings can be used<br />

to either increase the space ceiling height or<br />

reduce the slab spacing and thus the overall<br />

building height requirements.<br />

• The low plenum requirements of chilled beam<br />

systems make them ideal choices for retrofit of<br />

buildings that have previously used sidewall<br />

mounted equipment such as induction units,<br />

fan coils and other unitary terminals.<br />

• <strong>Chilled</strong> beams contribute to horizontal space<br />

savings as their significantly lower supply<br />

airflow rates result in smaller supply and return/exhaust<br />

air risers. The capacity of the air<br />

handling units providing conditioned air to the<br />

chilled beam system is also reduced, resulting<br />

in considerably smaller equipment room foot<br />

prints.<br />

• LEED TM also requires that certified buildings<br />

be purged for a period of time before<br />

occupancy in order to remove airborne<br />

contaminants related to the construction process.<br />

The significantly reduced airflow requirement<br />

of chilled beam systems reduces<br />

the fan energy required to accomplish this<br />

task.<br />

Operational cost benefits of chilled beam systems<br />

The energy costs of operating chilled beam systems are<br />

considerably lower than that of all-air systems. This is<br />

largely due to the following:<br />

<br />

Reduced supply air flow rates result in lower<br />

fan energy consumption.<br />

• Higher chilled water temperatures used by<br />

chilled beams may allow chiller efficiencies to<br />

be increased by as much as 35%.<br />

• <strong>Chilled</strong> beam systems offer attractive water<br />

side economizer. Unlike the case with air side<br />

economizers, these free cooling opportunities<br />

are not as restrictive in climates that are also<br />

humid.<br />

• Maintenance costs are considerably lower<br />

than all-air systems. <strong>Chilled</strong> beams do not<br />

incorporate any moving parts (fans, motors,<br />

damper actuators, etc.) or complicated control<br />

devices. Most chilled beams do not require<br />

filters (and thus regular filter changes) or<br />

condensate trays. As their coils operate „dry‟,<br />

regular cleaning and disinfection of<br />

condensate trays is not necessary. Normal<br />

maintenance history suggests that the coils be<br />

vacuumed every five years (more frequently in<br />

applications such as hospital patient rooms<br />

where linens are regularly changed). Figure<br />

10 compares the lifetime maintenance and<br />

replacement costs for active chilled beams to<br />

fan coil units (FCU), based on an expected<br />

FCU lifetime of 20 years. It assumes that<br />

each beam or FCU serves a perimeter floor<br />

area of 150 square feet.<br />

Filter Changes:<br />

Frequency:<br />

Fan Coil Unit<br />

Twice Yearly<br />

Cost per Change: $30.00<br />

Cost over Lifetime (20 Years): $1,200.00<br />

Clean Coil and Condensate System:<br />

Fan Motor Replacement:<br />

Frequency:<br />

Twice Yearly<br />

Cost per Event: $30.00<br />

Cost Over Lifetime: $1,200.00<br />

Frequency:<br />

Once during life<br />

Cost per Event: $400.00<br />

Cost Over Lifetime: $400.00<br />

Life Cycle (20 years) maintenance cost: $2,800.00<br />

Source: REHVA <strong>Chilled</strong> <strong>Beam</strong> Application <strong>Guide</strong>book (2004)<br />

Active <strong>Chilled</strong><br />

<strong>Beam</strong><br />

NA<br />

$0.00<br />

Every four Years<br />

$30.00<br />

$150.00<br />

NA<br />

$0.00<br />

$150.00<br />

Figure 10: Life Cycle Maintenance Costs<br />

Active <strong>Chilled</strong> <strong>Beam</strong>s versus Fan Coils<br />

• Operational efficiencies of pumps are<br />

intrinsically higher than fans, leading to much<br />

lower cooling and heating energy transport<br />

costs.<br />

8


Applications<br />

Comfort and IAQ benefits of chilled beam systems<br />

Properly designed chilled beam systems generally<br />

result in enhanced thermal comfort and indoor air<br />

quality compared to all-air systems.<br />

<br />

Active chilled beams generally deliver a<br />

constant air volume flow rate to the room. As<br />

such, variations in room air motion and cold air<br />

dumping that are inherent to variable volume<br />

all-air systems are minimized.<br />

• The constant air volume delivery of primary air<br />

to the active chilled beam helps assure that<br />

the design space ventilation rates and relative<br />

humidity levels are closely maintained.<br />

<strong>Chilled</strong> beam application criteria<br />

Although the advantages of using chilled beams are<br />

numerous, there are restrictions and qualifications that<br />

should be considered when determining their suitability<br />

to a specific application. <strong>Chilled</strong> beams are suitable for<br />

use where the following conditions exist:<br />

• Mounting less than 20 feet. Ceiling heights<br />

may be greater, but the beam should generally<br />

not be mounted more than 20 feet above the<br />

floor.<br />

• The tightness of the building envelope is<br />

adequate to prevent excessive moisture<br />

transfer. Space moisture gains due to<br />

occupancy and/or processes are moderate.<br />

• Space humidity levels can be consistently<br />

maintained such that the space dew point<br />

temperature remains below the temperature of<br />

the chilled water supply.<br />

• Passive beams should not be used in areas<br />

where considerable or widely variable air<br />

velocities are expected.<br />

• Passive beams should only be considered<br />

when an adequate entry and discharge area<br />

can be assured.<br />

• Passive <strong>Chilled</strong> beams can not be used to<br />

heat.<br />

Applications best served by chilled beams<br />

<strong>Chilled</strong> beams are ideal for applications with high space<br />

sensible cooling loads, relative to the space ventilation<br />

and latent cooling requirements. These applications<br />

include, but are not limited to:<br />

1) Brokerage trading areas<br />

Trading areas consists of desks where a<br />

single trader typically has access to multiple<br />

computer terminals and monitors. This high<br />

equipment density results in space sensible<br />

cooling requirements considerably higher than<br />

conventional interior spaces while the ventilation<br />

and latent cooling requirements are essentially<br />

the same. Active chilled beams remove<br />

60 to 70% of the sensible heat by<br />

means of their water circuit, reducing the<br />

ducted airflow requirement proportionally.<br />

2) Broadcast and recording studios<br />

Broadcast and recording studios typically<br />

have high sensible heat ratios due to their<br />

large electronic equipment and lighting loads.<br />

In addition, space acoustics and room air<br />

velocity control are critical in these spaces.<br />

Passive chilled beams are silent and capable<br />

of removing large amounts of sensible heat,<br />

enabling the use of a low velocity supply air<br />

discharge.<br />

3) Heat driven laboratory spaces<br />

<strong>Design</strong>ers often classify laboratories according<br />

to their required supply airflow rate. In<br />

laboratories that are densely populated by<br />

fume hoods, the make up air requirement is<br />

typically 12 air changes per hour or more.<br />

These laboratory spaces are classified as air<br />

driven. Laboratories whose make up air<br />

requirement is less than that are typically<br />

considered heat driven. This category includes<br />

most biological, pharmaceutical, electronic<br />

and forensic laboratories. The ventilation requirement<br />

in these laboratories is commonly 6<br />

to 8 air changes per hour, however, the processes<br />

and equipment in the laboratory can<br />

often result in sensible heat gains that require<br />

18 to 22 air changes with an all-air system. To<br />

make matters worse, recirculation of air<br />

exhausted from these laboratories is not<br />

allowed if their activities involve the use of<br />

gases or chemicals.<br />

Active chilled beams remove the majority (60<br />

to 70%) of the sensible heat by means of their<br />

chilled water coil, enabling ducted airflow rates<br />

to be reduced accordingly. Not only is the<br />

space more efficiently conditioned, but the<br />

ventilation (cooing and heating) load at the air<br />

handler is substantially reduced as far less<br />

outdoor air is required.<br />

9


Applications<br />

4) High outdoor air percentage applications<br />

Applications such as patient rooms in hospitals<br />

typically demand higher ventilation rates as<br />

well as accurate control of those rates. <strong>Chilled</strong><br />

beam systems are ideal for these applications<br />

as their hydronic sensible cooling regulates the<br />

space temperature while allowing a constant<br />

volume delivery of supply and ventilation air to<br />

the space. Displacement chilled beams such<br />

as the „<strong>TROX</strong> QLCI‟ also offer opportunities for<br />

improved contaminant removal efficiencies,<br />

reducing the likelihood of communicable<br />

diseases spreading to health care staff<br />

members.<br />

5) Perimeter treatment for UFAD systems<br />

Blind Box<br />

Passive<br />

<strong>Chilled</strong> <strong>Beam</strong><br />

Return Air<br />

Grille<br />

As conditioned air passes through the open<br />

floor plenum in UFAD systems, it picks up heat<br />

transferred through the structural slab from the<br />

return plenum of the floor below. The amount<br />

of heat transfer that is likely to occur is very<br />

hard to predict as many factors influence it.<br />

However, the resultant temperature rise in the<br />

conditioned air can often lead to discharge<br />

temperatures 4 to 5˚F higher than those<br />

encountered in interior zones nearer the point<br />

of entry into the supply air plenum. Such higher<br />

temperatures contribute to perimeter zone<br />

airflow requirements that are typically 35 to<br />

40% higher than that of conventional (ducted)<br />

all-air systems.<br />

Passive chilled beams such as the <strong>TROX</strong> TCB<br />

series provide effective and reliable cooling of<br />

perimeter spaces in UFAD applications. Figure<br />

11 illustrates such an application where the<br />

passive beam is mounted above the acoustical<br />

ceiling and adjacent to the blind box above an<br />

exterior window. Floor diffusers fed directly<br />

from the pressurized supply plenum continue<br />

to provide space ventilation and humidity<br />

control. Heating cannot be effectively<br />

accomplished by passive beams, so an<br />

underfloor finned tube heating system or<br />

radiant panel heating system typically<br />

compliments the chilled beams.<br />

Use of passive beams for perimeter area<br />

sensible cooling can reduce overall supply<br />

airflow rates in UFAD systems by as much as<br />

50%. This also results in a) smaller air<br />

handling units and ductwork, smaller supply<br />

and return air risers, c) reduced maintenance<br />

requirements and occupier disruption, d)<br />

improved space acoustics and air quality.<br />

Finned Tube<br />

Heating Coil<br />

Swirl Type<br />

Floor Diffuser<br />

Figure 11: Passive <strong>Chilled</strong> <strong>Beam</strong>s for<br />

Perimeter Treatment in a UFAD System<br />

<strong>Chilled</strong> beams are also an excellent choice where the<br />

vertical height of the ceiling cavity is limited. These<br />

include applications involving:<br />

1) Building height restrictions<br />

Building codes may restrict the overall height<br />

of buildings in certain locales. This commonly<br />

promotes the use of tighter slab spacing which<br />

reduces the depth of the ceiling cavity. Passive<br />

chilled beams can often be fit between<br />

structural beams in these applications. Active<br />

chilled beam systems can easily be designed<br />

to require 10 inches or less clearance when<br />

integrated into the ceiling grid system.<br />

2) Retrofits involving reduced slab spacing<br />

Many buildings that are candidates for HVAC<br />

system retrofits utilize packaged terminal units<br />

(induction units, vertical fan coil units, etc.)<br />

that are installed below the ceiling level. As<br />

such, many of these structures have ceiling<br />

cavities with limited depth. <strong>Chilled</strong> beams are<br />

ideal for such retrofits.<br />

a<br />

10


Multi-Service <strong>Chilled</strong> <strong>Beam</strong>s<br />

Multi-service (or integrated) chilled beams incorporate<br />

other space services into the linear enclosures associated<br />

with the chilled beams. This allows fitting of the selected<br />

services to the beams within the factory and delivery<br />

of elements that house all of these services to the<br />

job site in a “just-in-time” fashion. Upon arrival, these<br />

devices are hung, attached in a linear fashion and modular<br />

connections facilitate the installation of the various<br />

service systems.<br />

Figure 12 below illustrates an active multi-service beam<br />

and the services that can be easily integrated with it.<br />

The core of this device is a DID302 active chilled beam<br />

which incorporates a primary air duct (and plenum) a<br />

chilled water coil as well as inlet (perforated face) and<br />

discharge (linear slot) air passages. The outer frame of<br />

the device is designed to provide mounting surfaces<br />

and provisions for other services which are installed at<br />

the factory prior to shipment to the job site. Some of the<br />

services that can be integrated include:<br />

1. Lighting fixtures and controls<br />

2. Speakers<br />

3. Occupancy sensors<br />

4. Smoke detectors<br />

In addition, the outer frame is often customized to provide<br />

a visual appeal that is consistent with the architecture<br />

of the space in which it is mounted.<br />

Multi-service chilled beams can be provided as either<br />

active or passive versions. In cases where passive<br />

beams are used, a separate air distribution system must<br />

be provided. Oftentimes this air supply utilizes the cavity<br />

beneath a raised access flooring system as a supply<br />

plenum and is referred to as Underfloor Air Distribution.<br />

The service fixtures provided with multi-service beams<br />

are usually provided by others and issued tom the factory<br />

for mounting and connection where possible. Upon<br />

completion, the beams are shipped to the job site for<br />

mounting and final connection.<br />

Lighting provided with these beams may be direct, indirect<br />

or both. In all cases, the lighting system designer<br />

should be consulted to assure that the beam design and<br />

placement also provides sufficient space lighting. Fire<br />

protection designers should also be consulted in order<br />

to assure that the placement of the beams does not<br />

conflict with that of the fire sprinklers.<br />

Figure 12: Multi-service <strong>Chilled</strong> <strong>Beam</strong>s<br />

11


Multi-Service <strong>Chilled</strong> <strong>Beam</strong>s<br />

Multi-service <strong>Chilled</strong> <strong>Beam</strong> <strong>Design</strong>s<br />

Figures 13 and 14 below illustrate passive and active<br />

multi-service beam installations.<br />

Note that the photograph in figure 13 includes a swirl<br />

type diffuser mounted in the floor near the window. This<br />

diffuser supplies conditioned air for the ventilation and<br />

dehumidification of the space. The beams include a<br />

linear bar grille for the room air discharge and are<br />

curved to conform to the curvature of the ceiling. Both<br />

direct and indirect lighting is provided.<br />

Figure 14 illustrates an active beam version where the<br />

facial slots have been relocated such that they are not<br />

visible and are integrated into the top of the beam, discharging<br />

supply air across the surface of the exposed<br />

slab. Again lighting is both direct and indirect in the<br />

case of these beams.<br />

The photographs in these figures do not show a services<br />

corridor that runs perpendicular to the beams toward<br />

the interior of the space. This corridor is approximately<br />

the depth of the beams themselves and houses<br />

the main ductwork, piping and other services that feed<br />

the beams. These corridors may also house the return<br />

air passage in case where the slab is exposed. As a<br />

rule of thumb, about thirty (30) linear feet of beams may<br />

be connected to each run leaving the service corridor.<br />

Most multi-service beams are provided for exposed slab<br />

applications but other versions can be provided to integrate<br />

with acoustical ceiling grids.<br />

The Case for Multi-service <strong>Beam</strong>s<br />

Multi-service chilled beams offer numerous advantages<br />

over conventional service delivery systems, notably:<br />

1. As the services are integrated into the beams in the<br />

factory, quality control can be much better maintained<br />

than with field mounted services. Factory<br />

mounting involves the provision of proper fixtures<br />

to do the work and facilitates difficult piping and<br />

valve connection. This also allows the final piping<br />

to be leak tested after the components are assembled.<br />

2. Factory mounting of the space services reduces<br />

the amount of required trade coordination on the<br />

job site.<br />

3. All of the space services mounted in the common<br />

housing can be easily accessed for final connection<br />

and commissioning as well as future maintenance.<br />

4. The design of the housing involves the project architects<br />

as well as the engineering consultants and<br />

drives early coordination efforts as opposed to last<br />

minute panics.<br />

5. The above advantages can result in significant<br />

reductions in the time required to construct the<br />

building.<br />

The construction time reduction has made multi-service<br />

beams very popular in the Europe, especially the United<br />

Kingdom. Cases where the building construction time<br />

has been reduced by 25 to 30 percent have been well<br />

documented in a number of publications. Construction<br />

schedule reductions of ten to fifteen percent result in<br />

Figure 13: Passive Multi-service <strong>Beam</strong>s<br />

Figure 14: Active Multi-service <strong>Beam</strong>s<br />

12


Multi-Service <strong>Chilled</strong> <strong>Beam</strong>s<br />

significant cost savings. In particular, fixed site costs<br />

can be retired much earlier. These fixed site costs<br />

include but are not limited to:<br />

1. Communication and utilities services<br />

2. Sanitation services<br />

3. Equipment rentals<br />

4. Insurance costs<br />

On a job with a two year construction schedule, these<br />

fixed costs (which contribute nothing to the value of<br />

the project) typically amount to 12 to 14% of the value<br />

of the construction itself. Terminating the project<br />

sooner allows these costs to be cut proportionally.<br />

The use of multi-service beams can also allow the<br />

elimination of the acoustical ceiling system and, on<br />

new construction projects, may afford the use of lesser<br />

slab spacing. This may reduce the structure costs<br />

as well or may allow more floors to be housed within<br />

in a similar structure height (see next section).<br />

Finally, earlier completion allows the building owner to<br />

begin realizing revenue faster. The combination of<br />

these financial impacts typically offsets the cost difference<br />

between the multi-service approach and that of<br />

conventional HVAC and space services delivery.<br />

Building Height Requirements<br />

Multi-service beams may also afford opportunities for<br />

reduced building height and/or facilitate the retrofit of<br />

buildings with limited slab spacing. The integration of<br />

space services in the beam often eliminates the need<br />

for an acoustical ceiling and allows the beams to be<br />

pendant mounted directly to the structural slab.<br />

Figure 15 below illustrates the slab spacing requirements<br />

of a VAV system with fan powered terminals<br />

versus an exposed mounted multi-service active<br />

chilled beam. The ductwork in the VAV system is<br />

must be located such it remains below the horizontal<br />

structural supports. It also must be supported several<br />

inches above the ceiling grid to allow the installation<br />

of light fixtures and sprinkler systems. In order to provide<br />

a floor to ceiling height of nine (9) feet, the slab<br />

spacing is typically thirteen (13) feet.<br />

Multi-service beams which are mounted to the slab<br />

allow the provision of a ten (10) foot distance from the<br />

floor to the overhead slab while maintaining an 8.5<br />

foot clearance under the beams when used with a<br />

10.5 foot slab spacing. This savings essentially allows<br />

the addition twenty percent more floors in a building<br />

when multi-service beams are used instead of a VAV<br />

system.<br />

13'-0"<br />

Light fixture<br />

Suspended ceiling<br />

VAV with Fan Terminals<br />

9'-0"<br />

10'-6"<br />

Multiservice <strong>Chilled</strong> <strong>Beam</strong>s<br />

10'-0"<br />

8'-6"<br />

Figure 15: Slab Spacing Reduction with Multi-service <strong>Beam</strong>s<br />

13


Comfort Considerations<br />

CHILLED BEAM SYSTEM DESIGN<br />

GUIDELINES<br />

The HVAC system is responsible for three important<br />

tasks that help assure occupant comfort and a healthy<br />

indoor environment:<br />

1) Removal of the space sensible heat gains.<br />

2) Delivery of a prescribed volume flow rate of<br />

outdoor air to properly ventilate the space.<br />

3) Sufficient dehumidification to offset the space<br />

latent heat gains.<br />

As the water circuit in chilled beams is designed only to<br />

assist in achieving the sensible cooling objective, the air<br />

supply to the space must be properly maintained to<br />

accomplish the ventilation and dehumidification goals.<br />

In order to achieve efficient chilled beam system<br />

operation, certain considerations should be factored into<br />

the development of the system design and operational<br />

objectives. The following sections identify and briefly<br />

discuss such considerations that apply to the design,<br />

selection and specification of the equipment that<br />

supplies and controls the chilled beams.<br />

• General design objectives.<br />

• Air-side design goals and considerations.<br />

• Water-side design goals and considerations.<br />

• Control and operational considerations.<br />

The following sections discuss design decisions that<br />

affect the sizing and selection of the air and water<br />

system equipment and accessories.<br />

<strong>Design</strong>ing for occupant thermal comfort<br />

The maintenance of a high level of occupant thermal<br />

comfort is the primary objective of most chilled beam<br />

applications. ANSI/ASHRAE Standard 55-2004 Thermal<br />

Environmental Conditions for Human Occupancy 2<br />

identifies key factors that contribute to thermal comfort<br />

and defines environmental conditions that are likely to<br />

produce such. The Standard generally states that during<br />

cooling operation, the space (operative) dry bulb<br />

temperature should be maintained between 68 and<br />

77˚F and the space dew point temperature should not<br />

exceed 60.5˚F. If the space operative temperature is<br />

75˚F, this maximum dew point temperature corresponds<br />

to a relative humidity of 60%.<br />

<strong>Design</strong>ing for acceptable space acoustical levels<br />

The space acoustical requirements are usually dictated<br />

by its intended use. The 2007 ASHRAE Handbook<br />

(Applications) 3 prescribes design guidance (including<br />

recommended space acoustical levels) for various types<br />

of facilities and their use.<br />

AIR SIDE DESIGN CONSIDERATIONS<br />

Room and primary air design considerations<br />

When chilled beam systems are being contemplated,<br />

the relationship between the room design conditions<br />

and the primary air requirements should be closely evaluated.<br />

As previously stated, the chilled water circuit within<br />

chilled beams is capable of considerably higher<br />

sensible heat removal efficiencies than does<br />

conditioned air supplied to the space. As such, it is<br />

advantageous to remove as much sensible heat as<br />

possible by means of the chilled water circuit. In theory,<br />

this practice would allow the supply airflow rate to the<br />

space to be reduced proportionally and result in both<br />

energy savings and reduced HVAC services space<br />

requirements. However, the airflow supply to the space<br />

is also the sole source of space ventilation and dehumidification<br />

so consideration of these functions is imperative<br />

in the design of chilled beam systems. The primary<br />

(conditioned) airflow rate to the beam must be sufficient<br />

to provide space humidity control, ventilation and<br />

supplement the chilled water circuit in satisfying the<br />

space sensible heat gains. The space primary airflow<br />

rate must be the maximum of that needed to adequately<br />

accomplish all of those individual tasks.<br />

Space ventilation requirements are usually based on<br />

the number of space occupants and the floor area in<br />

which they reside. ASHRAE Standard 62-2004<br />

provides guidance in the calculation of these<br />

requirements. Some spaces (laboratories, healthcare<br />

facilities, etc.) may require higher ventilation rates due<br />

to processes they support. Identification of the required<br />

space ventilation rate should be the first step in<br />

the design process.<br />

a<br />

The standard also defines the occupied zone as the<br />

portion of the bounded by the floor and the head level of<br />

the predominant stationary space occupants (42 inches<br />

if seated, 72” if standing) and no closer than 3 feet from<br />

outside walls/windows or 1 foot from internal walls. It is<br />

generally accepted that velocities within the occupied<br />

zone should not exceed 50 to 60 feet per minute.<br />

14


Airside <strong>Design</strong> Consideration<br />

In order to maintain specified room humidity levels, the<br />

primary airflow must remove moisture (latent) heat at<br />

the rate at which it is generated. The supply airflow rate<br />

required to do this is determined by the equation:<br />

CFM LATENT = q LATENT / 4840 x (W ROOM - W SUPPLY )<br />

where, q LATENT is the space latent heat gain and W ROOM<br />

and W SUPPLY is the humidity ratio (LBS H 2 O per LB Dry<br />

Air) of the room and supply air, respectively.<br />

When chilled beam systems are used, the chilled water<br />

sensible heat extraction rate allows reduction of design<br />

supply airflow rates by 50 to 60% over conventional allair<br />

systems. Reductions of this magnitude may, however,<br />

compromise space ventilation and dehumidification.<br />

When chilled beams are used in applications where a)<br />

the design outdoor dew point temperature is above 50˚F<br />

and b) preconditioning outdoor air to a dew point temperature<br />

below that (50˚F) is not feasible, careful consideration<br />

should be given to the determination of design<br />

room air humidity levels.<br />

Figure 16 illustrates relationships between the primary<br />

air supply and the space design conditions for a typical<br />

interior space. This figure uses the specified room relative<br />

humidity and the primary air dew point temperature<br />

to establish a factor (F LATENT ) that relates the primary<br />

airflow requirement to maintain the desired room<br />

relative humidity as a ratio of the space ventilation requirement.<br />

It assumes a ventilation rate of 20 CFM per<br />

person.<br />

A<br />

Latent Airflow Factor, FLATENT<br />

4.5<br />

4.0<br />

3.5<br />

3.0<br />

2.5<br />

2.0<br />

1.5<br />

Space Relative<br />

Humidity<br />

Optimized <strong>Design</strong><br />

Range<br />

50%<br />

51%<br />

52%<br />

53%<br />

54%<br />

1.0<br />

48 49 50 51 52 53 54 55<br />

Primary Air Dewpoint Termperature, ˚F<br />

55%<br />

56%<br />

57%<br />

Figure 16: Pschrometric relationship<br />

Between Space and Primary Airflow<br />

56<br />

The primary airflow rate required to accomplish the<br />

desired space ventilation and dehumidification can be<br />

calculated as:<br />

CFM LATENT = F LATENT x CFM VENT<br />

Note that maintenance of 50% relative humidity with<br />

primary air supplied at a 52˚F dew point temperature<br />

will require that the primary airflow rate for the required<br />

space dehumidification be some 2.3 times the space<br />

ventilation rate. If the design relative humidity of the<br />

space were 55% (well within ASHRAE recommendations),<br />

the primary airflow requirement could be halved.<br />

Alternatively, the primary air could be conditioned to a<br />

48˚F dew point in order to maintain 50% relative humidity<br />

with a similar primary airflow rate. As the beams are<br />

generally operated at a constant volume flow rate, the<br />

room relative humidity levels will remain constant during<br />

occupied periods.<br />

Perimeter airflow requirements in chilled beam systems<br />

are generally driven by space sensible heat gains,<br />

therefore, space relative humidity levels in those areas<br />

will typically remain lower than in interior spaces.<br />

In summary, designing for slightly higher relative<br />

humidity levels can result in significant reductions<br />

in space primary airflow requirements!<br />

15


Local Velocity, FPM<br />

Airside <strong>Design</strong> Considerations<br />

Room air distribution in passive beam applications<br />

As passive beams rely only upon natural forces to<br />

recirculate the air to and from the space, it is critical that<br />

excessive restrictions in the air passages to and from<br />

the beams be avoided. As such, passive beams utilize<br />

very wide fin spacing (typically 3 to 4 fins per inch) as<br />

opposed to conventional cooling coils. Research<br />

indicates that the performance of these beams can also<br />

be significantly compromised if an adequate entry and<br />

discharge path is not maintained.<br />

It is generally recommended that the return and discharge<br />

passage of air through the ceiling perforated tile<br />

be equal to 2 times the width of the coil, normally split<br />

50-50, down the long sides of the beam. Figure 17 illustrates<br />

the recommended entry and discharge area relationships<br />

for recessed passive beams mounted above a<br />

ceiling tile with a 50% free area. The free area of the<br />

perforated ceiling has a direct result on performance of<br />

the beam., as the free are decreases, the output also<br />

decreases. The free area of the tile should not be lower<br />

than 28%, however, no increase in output is gained<br />

beyond 50% free area. When passive beams are<br />

mounted very near a perimeter wall or window, the required<br />

return air passage may be reduced as the warm<br />

air entering the beam has more momentum (contact<br />

<strong>TROX</strong> USA for further application assistance). Exposed<br />

beams must also be located such that the entering air<br />

passage requirements are observed.<br />

When passive beams are mounted adjacent to an<br />

outside window (and the room is thermally stratified),<br />

the momentum of the warm air rising along the<br />

perimeter surface will likely result in entering air<br />

temperatures 4 to 6˚F warmer than the room control<br />

temperature, dependent on the surface temperature of<br />

the façade.<br />

Ceiling or high sidewall outlets can be used (with a lesser<br />

heat transfer efficiency) provided their horizontal<br />

throw to 50 FPM does not extend to within four feet of<br />

the passive beam.<br />

In order to maintain a high level of thermal comfort,<br />

passive beams should be located such that the velocities<br />

of the falling cool air do not cause discomfort. As a<br />

general rule, the velocity at the head level of a stationary<br />

occupant should not exceed 50 FPM. Figure 18<br />

illustrates typical velocities directly below passive<br />

beams as a function of the sensible cooling they<br />

provide.<br />

70<br />

60<br />

50<br />

40<br />

30<br />

Average local velocity<br />

3 feet below passive<br />

beam<br />

Min. 0.33 x B<br />

20<br />

Minimum<br />

20% Free<br />

Area Panel<br />

Separation Skirt<br />

B<br />

10<br />

0<br />

50 100 150 200 250 300 350 400<br />

Passive <strong>Beam</strong> Cooling, BTUH/LF<br />

450<br />

W = 2.0 x B<br />

Figure 18: Velocities Below Passive <strong>Beam</strong>s<br />

Figure 17: Entry Area Requirements for<br />

Passive <strong>Chilled</strong> <strong>Beam</strong>s<br />

Passive chilled beams operate most efficiently in a<br />

stratified or partially stratified room environment. As<br />

such, displacement ventilation or underfloor air<br />

distribution (UFAD) outlets with limited vertical<br />

projection (throw to a terminal velocity of 50 FPM is no<br />

more than 40% of the mounting height of the beams).<br />

For design purposes, the beam entering air temperature<br />

should be assumed 2˚F warmer than that at the control<br />

level of the room under the described installation and<br />

operating conditions.<br />

16


Airside <strong>Design</strong> Considerations<br />

Space temperature control in passive beam systems is<br />

accomplished by varying the amount of sensible heat<br />

removed by the chilled water. The chilled water supply<br />

to several beams within a single zone is generally<br />

controlled by a single chilled water valve. Although the<br />

zone may consist of multiple spaces, a certain degree<br />

of temperature compensation for each space will be<br />

affected by the passive beam itself. As the cooling<br />

requirement of the space is reduced, the temperature of<br />

the air entering the beam will also be reduced. This will<br />

result in less heat transfer to the water circuit and a<br />

lower return water temperature.<br />

Passive chilled beams cannot be used for heating as its<br />

airflow would be reversed. They are typically applied<br />

with some type of separate heating system such as low<br />

level finned tube heaters. Radiant (ceiling or wall<br />

mounted) heating panels can also be used depending<br />

on the façade heat losses expected.<br />

Thermal comfort considerations with active beams<br />

While the primary (conditioned) airflow rate for active<br />

chilled beams can be greatly reduced, their induction<br />

ratios (2 to 6 CFM of room air per CFM primary air)<br />

result in discharge airflow rates that are slightly higher<br />

than those of conventional all-air systems. As such,<br />

attention should be exercised in the beam placement to<br />

avoid drafty conditions and maximize occupant thermal<br />

comfort. Figure 19 predicts maximum occupied zone<br />

velocities for various combinations of primary airflow<br />

rates and active beam spacing. This nomograph<br />

suggests local velocities which will maintain acceptable<br />

levels of occupant comfort per ASHRAE.<br />

Active beams can be for heat in moderate climates. Hot<br />

water can either be delivered to each perimeter area<br />

beam or to a hot water heating coil in the duct supplying<br />

a number of beams within the same thermal control<br />

zone. The use of a zone hot water heating coil feeing<br />

multiple chilled beams is a generally more economic<br />

option than piping each chilled beam for heating as it<br />

may save considerable labor and piping material costs.<br />

If active chilled beams are used for heating, the following<br />

recommendations should be observed:<br />

• <strong>Chilled</strong> beam discharge temperatures should<br />

be maintained within 15˚F of the room<br />

temperature.<br />

• Velocities at the mid-level of outside walls and<br />

windows should be maintained within the<br />

region indicated in figure 19.<br />

Unoccupied periods demanding heating via the chilled<br />

beams or primary air system will require that the AHU<br />

remain operational.<br />

Variable air volume operation using active beams<br />

Although normally operated as constant air volume<br />

delivery devices, active chilled beams can also be used<br />

as variable air volume (VAV) devices. VAV operation<br />

may be advantageous when space occupancy and/or<br />

ventilation demands vary widely. Recommendations for<br />

the control of chilled beams in VAV applications can be<br />

found in the control section of this document.<br />

As the room air distribution provided by active<br />

beams is identical to that provided by ceiling slot<br />

diffusers, their selection for (total) discharge airflow<br />

rates greater than 40 CFM per linear foot of slot is<br />

not recommended when high levels of occupant<br />

thermal comfort are required!<br />

The v L velocities shown in figure 19 are those predicted<br />

within 2 inches of the window or wall surface during<br />

cooling operation. It is recommended that beams which<br />

are configured for both heating and cooling of perimeter<br />

spaces be selected such that v L (selected for cooling<br />

operation) is between 120 and 150 FPM in order to<br />

assure that the warm air is adequately projected down<br />

the perimeter surface. Velocities taken 6 inches away<br />

from the surface can be expected to be about half those<br />

values.<br />

Heating in chilled beam applications<br />

Ceiling or high sidewall mounted passive chilled beams<br />

exert no motive force on their discharge airflow, and<br />

cannot be used for overhead heating. Heating must be<br />

provided by a separate source, either the primary air<br />

supply or a separate heating system (finned tube,<br />

radiant panel, etc.).<br />

17


Local Velocity VH1 , FPM<br />

Airside <strong>Design</strong> Considerations<br />

Cooling<br />

H - H1 (feet)<br />

3 4 5<br />

70 FPM<br />

60 FPM<br />

6<br />

Cooling mode velocity exceeds recommended<br />

level for high occupant comfort levels.<br />

Velocities (V L2 ) within recommended levels for<br />

overhead heating applications.<br />

BEAM<br />

TOTAL<br />

AIRFLOW<br />

RATE (PER<br />

LINEAR<br />

FOOT OF<br />

SLOT)<br />

Cooling<br />

H - H1 (feet)<br />

Heating<br />

6 5 4<br />

6 5 4 3<br />

Type M Nozzle: Q TOTAL = 4.8 x Q PRIMARY<br />

Velocities V H1 V L2 and V L6 are based on a Local<br />

Local<br />

15˚F temperature differential between Velocity V L6 , Velocity V L2 ,<br />

the room and the supply airstream.<br />

FPM<br />

FPM<br />

Type C Nozzle: Q TOTAL = 3.2 x Q PRIMARY<br />

Type B Nozzle: Q TOTAL = 4.2 x Q PRIMARY<br />

Type A Nozzle: Q TOTAL = 5.3 x Q PRIMARY<br />

Type G Nozzle: Q 100 FPM<br />

TOTAL = 3.7 x Q PRIMARY<br />

120 FPM<br />

H/2<br />

55 FPM<br />

40 CFM/LF<br />

90 FPM<br />

110 FPM<br />

100 FPM<br />

50 FPM<br />

35 CFM/LF<br />

80 FPM<br />

90 FPM<br />

45 FPM<br />

40 FPM<br />

30 CFM/LF<br />

70 FPM<br />

80 FPM<br />

70 FPM<br />

35 FPM<br />

25 CFM/LF<br />

60 FPM<br />

30 FPM<br />

20 CFM/LF<br />

50 FPM<br />

60 FPM<br />

50 FPM<br />

4<br />

6 8 10 12 14<br />

Distance A/2 or X (feet)<br />

X<br />

A<br />

0.5 Q SUPPLY 0.5 Q SUPPLY<br />

0.5 Q SUPPLY<br />

H - H1 Cooling<br />

H/2 Heating<br />

2" 2” for VL2<br />

6" 6” for VL6<br />

H - H1<br />

VL2 or V L6<br />

V H1<br />

NOTES:<br />

1. VL2 values in chart are measured 2" from wall in a heating mode. For adequate heating performance, VL2 value at mid-level height of the wall should be at<br />

least 50 FPM.<br />

2. VL6 values in chart are measured 6" from wall in a cooling mode. VL6 values the top of the occupied zone should be limited to about 75 FPM.<br />

3. VH1 values in chart are measured at the top of the occupied zone directly below the point of collision of two opposing air streams (cooling mode). For optimum<br />

thermal comfort, VH1 values should not exceed 50 FPM.<br />

Figure 19: Local Velocity Predictions for <strong>TROX</strong> Active <strong>Chilled</strong> <strong>Beam</strong>s<br />

18


Water Side <strong>Design</strong> Considerations<br />

WATER SIDE DESIGN CONSIDERATIONS<br />

Once the room air conditions have been established,<br />

the water side design objectives and requirements can<br />

be identified. Certain factors must be considered in<br />

arriving at the chilled water system design. The<br />

following sections discuss these.<br />

<strong>Chilled</strong> water supply source<br />

There are several possible sources of adequately<br />

conditioned chilled water for the supply of chilled beam<br />

systems. Among these are several sources discussed<br />

below:<br />

• Return water from AHU chilled water coil<br />

• Dedicated chilled water supply system<br />

• District chilled water supply<br />

• Geothermal wells<br />

When air handling units associated with chilled beam<br />

systems utilize chilled water evaporator coils, their<br />

return water can often be used to remove heat from the<br />

chilled beam circuit. Figure 20 illustrates a chilled water<br />

loop whose heat is extracted through a heat exchanger<br />

to the AHU return water loop. The chilled water supply<br />

is a closed loop which includes a bypass by which<br />

return water can be bypassed around the heat<br />

exchanger to maintain the desired chilled water supply<br />

temperature to the beams. Figure 21 illustrates a chilled<br />

beam system where the beams are supplied by a dedicated<br />

chiller. The chilled water loop allows the chiller to<br />

operate at a higher efficiency due to the higher return<br />

water temperatures associated with the chilled beam<br />

system. The chiller‟s COP can often be increased by 25<br />

to 30% by doing so.<br />

<strong>TROX</strong> USA recommends that the chilled water supply<br />

temperature for passive chilled beams is at least<br />

1˚F above the maximum room dew point that can be<br />

controlled to whilst active beams are kept at or<br />

above the room dew point as an operational safety<br />

margin. In general, most beams installed to date have<br />

a supply temperature 1.5˚F or more above room dew<br />

point.<br />

The return water temperature leaving chilled beams is<br />

at least 3˚F higher than the chilled water supply. As<br />

such, the chilled water return piping does not normally<br />

need to be insulated.<br />

Primary <strong>Chilled</strong><br />

Water Supply<br />

3-way<br />

Moduating<br />

Valve<br />

Secondary<br />

<strong>Chilled</strong> Water<br />

Return<br />

HEAT EXCHANGER<br />

Return Water Bypass<br />

Primary <strong>Chilled</strong><br />

Water Return<br />

Supply Temperature<br />

Controller<br />

<strong>Chilled</strong> Water<br />

Pump<br />

Secondary<br />

(Tempered) <strong>Chilled</strong><br />

Water Supply to<br />

<strong>Beam</strong>s<br />

Figure 20: Shared or Tempered <strong>Chilled</strong><br />

Water Supply Circuit<br />

Dedicated<br />

Chiller<br />

T<br />

In some cases, water from district chilled water supplies<br />

or geothermal wells may replace the return water from<br />

the AHU and serve as the primary loop in the heat<br />

exchanger shown in figure 20.<br />

3-way<br />

Moduating<br />

Valve<br />

Storage<br />

Vessel<br />

Supply Temperature<br />

Controller<br />

T<br />

<strong>Chilled</strong> water supply and return temperatures<br />

The most important decision regarding the chilled water<br />

system involves the specification of a chilled water<br />

supply temperature. In order to prevent condensation<br />

from forming on the beams, the chilled water supply<br />

temperature must be sufficiently maintained. The<br />

REHVA <strong>Chilled</strong> <strong>Beam</strong> Applications <strong>Guide</strong>book 1<br />

suggests that condensation will first occur on the supply<br />

piping entering the beam. As such, it is very important<br />

to insulate the chilled water supply piping to the beams.<br />

Reference 4 suggests that condensation will not likely<br />

form when the active chilled water supply temperature<br />

is maintained no lower than 3˚F below the room air dew<br />

point and at least 1˚F above the space dew point<br />

temperature in the case of passive beams.<br />

Secondary<br />

<strong>Chilled</strong> Water<br />

Return<br />

Return Water Bypass<br />

<strong>Chilled</strong> Water<br />

Pump<br />

Secondary<br />

(Tempered) <strong>Chilled</strong><br />

Water Supply to<br />

<strong>Beam</strong>s<br />

Figure 21: Dedicated <strong>Chilled</strong> Water Circuit<br />

19


Water Side <strong>Design</strong> Considerations<br />

Hot water supply and return temperatures<br />

Active chilled beams can be used for perimeter heating<br />

and cooling in mild climates. It is recommended that the<br />

hot water supply be maintained at a temperature that<br />

will result in a beam discharge temperature no more<br />

than15˚F warmer than the ambient room temperature.<br />

Water flow rates<br />

There are factors that affect the minimum and maximum<br />

water flow rates within the chilled beam system.<br />

Maximum flow rates are limited by the pressure loss<br />

within the beam. Minimum flow rates are based on the<br />

maintenance of turbulent flow to assure proper heat<br />

transfer. The following recommendations apply to the<br />

chilled water system design:<br />

Water head loss through the beams should be<br />

limited to 10 feet H 2 O or less.<br />

Pressures exceeding 10 feet H 2 O at the water control<br />

valve may cause noise when the valve begins<br />

opening.<br />

The 2005 ASHRAE Handbook (Fundamentals) 5<br />

limits water flow rates in pipes that are two (2) inches<br />

in diameter or less to that which results in maximum<br />

velocities of 4 FPS.<br />

<strong>Chilled</strong> beam water flow rates below 0.15 GPM<br />

may result in non-turbulent flow. Selection below<br />

this flow rate should not be made as the coil performance<br />

cannot be assured.<br />

Water treatment recommendations<br />

As most of the elements within the chilled (and hot)<br />

water piping systems are typically copper or brass, it is<br />

important that the water circuit is treated to assure that<br />

there are no corrosive elements in the water. The water<br />

circuits feeding the chilled beams should also be treated<br />

with a sodium nitrite and biocide solutions to prevent<br />

bacterial growth. Glycol should not be added except<br />

where absolutely necessary as it changes the specific<br />

capacity of the chilled water and its effect on the chilled<br />

beam performance must be estimated and accounted<br />

for. Prior to start up and commissioning, all chilled and<br />

hot water piping should be flushed for contaminants.<br />

20


Control Strategies<br />

CHILLED BEAM CONTROL CONSIDERATIONS<br />

This section discusses the control of both the air and<br />

the water supply in chilled beam systems. It also<br />

presents and discusses strategies for condensation<br />

prevention.<br />

Temperature control and zoning with chilled beams<br />

Room temperature control is primarily accomplished by<br />

varying the water flow rate or its supply temperature to<br />

the chilled beam coils in response to a zone thermostat<br />

signal. Modulation of the chilled water flow rate typically<br />

produces a 7 to 8˚F swing in the beam‟s supply air<br />

temperature, which affects a 50 - 60% turndown in the<br />

beam‟s sensible cooling rate. This is usually sufficient<br />

for the control of interior spaces (except conference<br />

areas) where sensible loads do not tend to vary<br />

significantly. If additional reduction of the space cooling<br />

is required, the primary air supply to the beam can be<br />

reduced. In any case, modulation of the chilled water<br />

flow rate or temperature should be the primary means<br />

for controlling room temperature as it has little or no<br />

effect on space ventilation and/or dehumidification. Only<br />

after the chilled water flow has been discontinued<br />

should the primary airflow rate be reduced.<br />

Thermal control zones for chilled beam applications<br />

should be establish in precisely the same manner they<br />

are defined for all air systems. These zones should<br />

consist of adjacent spaces whose sensible cooling<br />

requirements are similar, and several beams should be<br />

controlled from a single space thermostat. For example,<br />

the beams serving several perimeter spaces with the<br />

same solar exposure can be controlled by a single<br />

thermostat to create a zone of similar size to that which<br />

might be served by a single fan terminal in an all air<br />

system. Conference rooms and other areas with widely<br />

varying occupancy should be controlled separately.<br />

Control of the primary airflow rate<br />

Figure 22 illustrates a <strong>TROX</strong> model VFL flow limiter<br />

which can be fitted directly to the inlet side of the active<br />

beam. This limiter is fully self-contained and requires no<br />

power or control connections. It may be field set to<br />

maintain a volume flow rate to the beam. VFL limiters<br />

are recommended for use on beams fed by the same<br />

air handling unit supplying VAV terminals. The VFL<br />

compensates for system pressure changes to maintain<br />

the beam‟s design airflow rate.<br />

VFL flow limiters require a minimum of 0.15 inches H 2 O<br />

differential static pressure to operate. This must be added<br />

to the catalogued pressure loss of the beam to arrive<br />

at an appropriate inlet static pressure requirement. For<br />

acoustical reasons, the inlet static pressure should not<br />

exceed 1.0 inches H 2 O. More information on VFL flow<br />

limiters may be found in <strong>TROX</strong> leaflet 5/9.2/EN/3.<br />

Figure 22: <strong>TROX</strong> VFL Flow Controller<br />

The most economical way to control the output of the<br />

chilled beam is to modulate the water flow rate through<br />

the coil. This may be accomplished in either of two<br />

ways. Figure 23 illustrates a typical piping and hydronic<br />

control schematic for a single thermal zone utilizing<br />

chilled beams. There are isolation valves within each<br />

zone which allow the chilled beam coils within the zone<br />

to be isolated from the chilled water system. This<br />

enables beams to be relocated or removed without<br />

disturbing the water flow in other zones. The coils‟ water<br />

flow rate is throttled by a 2-way chilled water valve<br />

actuated by the zone thermostat. Most chilled beam<br />

systems utilize floating point valve actuators that<br />

provide on-off control of the beam water flow. Throttling<br />

the water flow rate results in variable volume flow<br />

through the main water loop while its supply and return<br />

water temperatures tend to remain relatively constant.<br />

Figure 24 shows a zone within a chilled beam system<br />

that is controlled by a 3-way valve. Such a schematic<br />

will allow modulation of the chilled water flow to the<br />

beams within the zone while maintaining a constant<br />

volume flow rate within the main distribution system.<br />

Such control may be advantageous in cases where a<br />

dedicated chiller is used and significant variations in the<br />

water flow rate can result in danger of freezing within<br />

the chiller itself. Three way valves are also frequently<br />

used when condensation prevention controls are<br />

employed.<br />

The piping illustrated in figure 23 is reverse-return. The<br />

first unit supplied with chilled water is the farthest from<br />

the main chilled water return. Using reverse-return piping<br />

tends to adequately balance the water flow to multiple<br />

beams within a single zone.<br />

<strong>Chilled</strong> (and hot) water flow control strategies<br />

21


Control Strategies<br />

<strong>Chilled</strong><br />

water<br />

supply<br />

<strong>Chilled</strong><br />

water<br />

return<br />

Isolation<br />

valve<br />

Isolation<br />

valve<br />

2 way<br />

on-off<br />

control<br />

valve<br />

T<br />

Zone thermostat<br />

<strong>Chilled</strong> beams within a single thermal zone<br />

Figure 23: <strong>Chilled</strong> <strong>Beam</strong> Zone Control by Means of a Throttling (On/Off) 2 Way Valve<br />

<strong>Chilled</strong><br />

water<br />

supply<br />

<strong>Chilled</strong><br />

water<br />

return<br />

Flow<br />

Measurement<br />

and Balancing<br />

Valves<br />

Isolation<br />

valves (2)<br />

3 way<br />

proportional<br />

control<br />

valve<br />

T<br />

Zone thermostat<br />

<strong>Chilled</strong> beams within a single thermal zone<br />

Figure 24: <strong>Chilled</strong> <strong>Beam</strong> Zone Control by Means of a Diverting 3 Way Valve<br />

Zone thermostat<br />

T<br />

3 way proportional<br />

control valve<br />

<strong>Chilled</strong><br />

water<br />

supply<br />

<strong>Chilled</strong><br />

water<br />

return<br />

Pump<br />

Isolation<br />

valves (2)<br />

<strong>Chilled</strong> beams within a single thermal zone<br />

Figure 25: <strong>Chilled</strong> <strong>Beam</strong> Zone Control by Water Temperature Modulation<br />

22


Control Strategies<br />

The chilled beam output may also be controlled by<br />

maintaining the water flow rate constant and modulating<br />

its temperature. In these cases, the water flow rate<br />

throughout both the main and zone circuits remains<br />

constant. This is a more expensive alternative which is<br />

generally only used where space humidity levels are<br />

unpredictable yet condensation must be prevented<br />

without compromising the space thermal conditions.<br />

Figure 25 illustrates such a zone using a mixing<br />

strategy where return water is recirculated to raise the<br />

chilled water supply temperature to the beams. A pump<br />

must be supplied within the zone piping circuit to<br />

produce a sufficient head to pump the<br />

supply/recirculated water mixture to the beams.<br />

HEAT<br />

EXCHANGER<br />

Return Water Bypass<br />

<strong>Chilled</strong><br />

Water<br />

Pump<br />

Outdoor Air<br />

Dew Point<br />

Sensor<br />

T<br />

F<br />

Supply Water<br />

Temperature<br />

Controller<br />

Condensation prevention strategies<br />

Secondary <strong>Chilled</strong><br />

Water Return<br />

Secondary (Tempered) <strong>Chilled</strong><br />

Water Supply to <strong>Beam</strong>s<br />

As long as the space dew point temperature can be<br />

maintained within a reasonable (+/- 2˚F) range and the<br />

chilled water supply temperature is at (or above) the<br />

design value, there should be no chance of condensation<br />

on the surfaces of the chilled beams. The beam<br />

surfaces will never be as cold as the entering chilled<br />

water temperature. In the case of active beams, the<br />

constant room airflow across the coil surface will also<br />

provide a drying effect.<br />

Some applications may, however, be subject to periods<br />

where room humidity conditions drift or rise due to<br />

infiltration or other processes that may add significant<br />

unaccounted for moisture to the space. In these cases,<br />

the employment of some type of condensation control<br />

strategy may be warranted. There are several methods<br />

of condensation prevention control that include the<br />

following (and combinations of such):<br />

• Central monitoring and control<br />

• Zonal monitoring with on/off control<br />

• Zonal monitoring with modulating control<br />

<strong>Chilled</strong><br />

water<br />

supply<br />

T<br />

Isolation<br />

valve<br />

2-way <strong>Chilled</strong><br />

Water Valve<br />

(one per zone)<br />

Pressure<br />

Regulator<br />

R<br />

To <strong>Chilled</strong> <strong>Beam</strong><br />

Zones<br />

Figure 26: <strong>Chilled</strong> Water Temperature<br />

Reset Based on Outdoor Dew Point<br />

Zone thermostat<br />

Moisture Sensor<br />

2 way<br />

on-off<br />

control<br />

valve<br />

Isolation<br />

valve<br />

<strong>Chilled</strong><br />

water<br />

return<br />

Central dew point monitoring and control involves the<br />

measurement of the outdoor dew point temperature and<br />

control of the chilled water supply temperature in<br />

relation to that. This is an effective method of control for<br />

relatively mild climate applications where operable<br />

windows and/or other sources contribute to excessive<br />

infiltration of outdoor air. The central supply water<br />

temperature can be modulated to remain at (or some<br />

amount above) the outdoor air dew point. Figure 26<br />

illustrates such a method of condensation control.<br />

An alternative method of condensation prevention is the<br />

use of zonal on/off control signaled by moisture sensors<br />

on the zone chilled water connection (see figure 27).<br />

When moisture forms on the supply water pipe next to<br />

the zone water valve, the zone water flow is shut off<br />

and will not be restored until the moisture has been<br />

<strong>Chilled</strong> beams within a single thermal zone<br />

Figure 27: Throttling <strong>Chilled</strong> Water Control<br />

with Moisture Sensor Override<br />

evaporated. Conditioning of the space will be limited to<br />

that provided by the primary airflow until acceptable<br />

humidity conditions allow the chilled water flow to be<br />

resumed. This is an economic and effective method of<br />

condensation control in spaces where such conditions<br />

are not expected to occur frequently. The sensor may<br />

also be used as a signal to increase the flow of primary<br />

air to further dehumidify the space, reducing the time<br />

that the chilled water flow is shut off.<br />

23


Installation and Commissioning<br />

If the maintenance of local thermal conditions is critical,<br />

a zone humidistat may be used to modulate the zone<br />

chilled water supply temperature as shown in figure 28.<br />

This requires that each zone fitted for such control be<br />

fitted with a pump capable of recirculating return water<br />

into the supply circuit of the chilled beam.<br />

Uni-strut Channels<br />

bolted to structure<br />

above allows<br />

adjustment along<br />

beam width<br />

Temperature<br />

Sensor<br />

Dew Point<br />

Sensor<br />

T<br />

F<br />

Zone Temperature<br />

and Humidity<br />

Controller<br />

3 way<br />

proportional<br />

control valve<br />

Pump<br />

Isolation<br />

valves<br />

(2)<br />

<strong>Chilled</strong><br />

water<br />

supply<br />

<strong>Chilled</strong><br />

water<br />

return<br />

<strong>Beam</strong> suspended<br />

from channels by<br />

threaded rods<br />

Factory furnished<br />

mounting brackets<br />

allow adjustment<br />

along beam length<br />

Figure 29: Installation of an Active <strong>Beam</strong><br />

<strong>Chilled</strong> beams within a single thermal zone<br />

Figure 28: Condensation Protection Using<br />

Temperature/Humidity Sensing to Modulate<br />

the Zone <strong>Chilled</strong> Water Temperature<br />

1"<br />

Integration with<br />

standard 1" wide<br />

(inverted) tee bar grid<br />

INSTALLATION AND COMMISSIONING<br />

Mounting considerations<br />

The weight of chilled beams requires that they be separately<br />

supported, independent of any integrated ceiling<br />

grid or drywall surface. They are usually suspended<br />

from the structure above by means of threaded rods or<br />

other sufficiently strong support means that allow the<br />

beam‟s position to be vertically adjusted. The beams<br />

are usually mounted and connected prior to the installation<br />

of the ceiling grid or drywall. <strong>TROX</strong> chilled beams<br />

are furnished with a minimum of four (4) attachment<br />

angles whose position can be adjusted along the beam<br />

length to allow the beam to be “dropped” into the suspended<br />

ceiling grid with which it is integrated. When<br />

integrated with a ceiling grid system or drywall, it is recommended<br />

that the beams be suspended from linear<br />

channels (such as uni-strut) that run perpendicular to<br />

the beam‟s length, so there is some adjustability in every<br />

direction. Figure 29 illustrates the mounting of active<br />

and passive beams.<br />

<strong>TROX</strong> offers various borders to coordinate DID series<br />

beams with three types of acoustical ceiling grids<br />

(illustrated in figure 30):<br />

5/16"<br />

1"<br />

9/16"<br />

9/16"<br />

Integration with narrow<br />

9/16" wide (inverted)<br />

tee bar grid<br />

Integration with narrow<br />

9/16" wide tubular type<br />

grid<br />

Integration into dry wall<br />

ceiling using plaster<br />

frame<br />

Figure 30: Integration of Active <strong>Beam</strong>s into<br />

Common Ceiling System Applications<br />

24


Installation and Commissioning<br />

When active beams are to be used without an adjacent<br />

ceiling surface, <strong>TROX</strong> recommends that an extended<br />

outer surface be furnished which allows formation of a<br />

Coanda effect that helps direct the discharge air<br />

horizontally and prevent dumping.<br />

Recessed passive chilled beams may also be<br />

integrated with suspension grid systems, but they are<br />

usually mounted above the grid and have no direct<br />

interaction with it. It is recommended that a separation<br />

skirt (see figure 5) be used to separate the two air<br />

streams (warm entering air from cool discharge air) of<br />

the beam. Exposed passive beams are almost always<br />

pendant mounted to the structural slab above and used<br />

without a false ceiling system.<br />

Air and water connections<br />

Connection of the chilled water (and hot water where<br />

applicable) supplies to chilled beams are the<br />

responsibility of the installing contractor. <strong>Chilled</strong> beams<br />

may be furnished with either NPT (threaded) male connections<br />

or with straight pipe ends appropriate for field<br />

soldering. While each coil is factory tested for leakage,<br />

it is important that the beams are at no time subjected<br />

to installation or handling that might result in bending or<br />

otherwise damaging the pipe connections in any way.<br />

All control, balancing and shut–off valves that may be<br />

necessary are also to be provided and installed by others.<br />

Do not over tighten any threaded connections to<br />

the beams.<br />

All chilled water supply piping should be adequately<br />

insulated. Return water piping may be left un-insulated<br />

provided the return water temperature remains above<br />

the dew point of the spaces over which it passes.<br />

Flexible hoses may be used for chilled beam water<br />

connections. These hoses may employ either threaded<br />

or snap lock connectors. <strong>TROX</strong> USA offers such threaded<br />

connectors as an option. These connectors are<br />

100% tested and marked with individual identification<br />

numbers. In the event of a failure, the batch within<br />

which they were manufactured can be readily identified<br />

and preemptive remediation can be performed without<br />

concern that all hoses on the job are subject to failure<br />

soon. The normal life of flexible hoses exceeds fifteen<br />

year but can be affected by (among other things)<br />

swings in their operational temperature and lack of sufficient<br />

water treatment.<br />

connect the beam to the supply air duct and this flexible<br />

duct should not have any excess bends or radius.<br />

Water treatment<br />

It is imperative that there are no corrosive elements in<br />

the secondary water supply to the beams as there are<br />

brass fittings on the coils and/or connection hoses.<br />

Periodic testing of the secondary water circuit on each<br />

floor should be performed to assure that none of these<br />

corrosive elements are present.<br />

Prior to connection to the beams and the chiller plant,<br />

the water pipes should be thoroughly flushed to remove<br />

any impurities that may reside within them. Only after<br />

this purging has occurred should the connections to the<br />

coils and the chiller plant be performed. Additional<br />

information regarding system cleaning may be found in<br />

reference 6.<br />

Once filled by the mechanical contractor, the system<br />

should be dosed with chemicals that prevent bacterial<br />

growth. Typical additives would be a sodium nitrate<br />

inhibitor solution of 1000 parts per million (e.g. Nalcol<br />

90) and a biocide solution of 200 parts per million (e.g.<br />

Nalcol). Reference 6 provides additional information<br />

regarding water treatment.<br />

System Commissioning<br />

A flow measuring device and suitable balancing valve<br />

should be provided for each beam which will enable<br />

adjustment of the chilled water flow rate to each beam<br />

within the thermal zone to its design value. This is<br />

illustrated in figure 24. Where five to six beams are<br />

installed in a reverse-return piping circuit (per figure 23),<br />

there will likely be no need for such measuring devices<br />

and balancing valves.<br />

The primary airflow rate to an active chilled beam can<br />

best be determined by measuring the static pressure<br />

within the pressurized entry plenum and referring to the<br />

calibration chart provided with the beam. <strong>TROX</strong><br />

provides an integral pressure tap (accessible through<br />

the face of the beam) to which a measuring gauge can<br />

be connected. Do not attempt to read the total discharge<br />

airflow rate using a hood or any other device<br />

that adds downstream pressure to the beam as it will<br />

reduce the amount of induction and as such give false<br />

readings.<br />

The connection of the primary air supply duct to active<br />

chilled beams is also the responsibility of the installing<br />

contractor. This connection should include the provision<br />

of at least eight (8) inches of straight sheet metal duct<br />

connected directly to the beam‟s primary air inlet. No<br />

more than five (5) feet of flexible duct should be used to<br />

a<br />

25


Maintenance<br />

SYSTEM OPERATION AND MAINTENANCE<br />

There are certain operational requirements that must<br />

observed when chilled beam systems are employed in<br />

humid climates. In the event the HVAC system is<br />

disabled on nights and/or weekends, the chilled water<br />

supply must remain suspended until the primary air<br />

supply has properly dehumidified the space. It is<br />

recommended that some type of space humidity<br />

sensing be used to assure that a proper space dew<br />

point temperature has been established prior to starting<br />

the delivery of chilled water to the space.<br />

If chilled beams are to be used in traffic or lobby areas,<br />

it is important that the space be maintained at a positive<br />

pressure in order to minimize the infiltration of outdoor<br />

air. In the case of lobby areas, the use of revolving<br />

doors may be warranted. It is also recommended that<br />

the beams not be located near any opening doors or<br />

windows in these areas.<br />

REFERENCES<br />

1. REHVA. 2004. <strong>Chilled</strong> <strong>Beam</strong> Application<br />

<strong>Guide</strong>book.<br />

2. ASHRAE. 2004 Thermal environmental<br />

conditions for human occupancy. AN-<br />

SI/ASHRAE Standard 55-2004.<br />

3. ASHRAE. 2007. ASHRAE Handbook-<br />

Applications.<br />

4. Energie. 2001. Climatic ceilings technical note:<br />

design calculations.<br />

5. ASHRAE. 2005. ASHRAE Handbook-<br />

Fundamentals.<br />

6. BSRIA. 1991. Pre-commission cleaning of<br />

water systems. BSRIA Application <strong>Guide</strong> 8/91.<br />

7. ASHRAE. 2004 Ventilation for acceptable<br />

indoor air quality. ANSI/ASHRAE Standard<br />

62.1-2004.<br />

Maintenance requirements<br />

Due to their simplicity and lack of moving parts, chilled<br />

beams require little maintenance. In fact, the only<br />

scheduled maintenance with chilled beams involves the<br />

periodic vacuuming of their coil surfaces. Passive<br />

beams generally require that this be done every four to<br />

five years. In the case of active beams, such cleaning is<br />

only required when the face of the unit return section<br />

shows visible dirt. At this time, the primary air nozzles<br />

should be visually inspected and any debris or lint<br />

removed. In all cases, it is recommended that good<br />

filtration be maintained within the air handling unit.<br />

26


Passive <strong>Beam</strong> Selection<br />

CHILLED BEAM SELECTION<br />

PASSIVE BEAM SELECTION AND LOCATION<br />

Selection and location of passive chilled beams is primarily<br />

affected by the following parameters:<br />

• Required sensible heat removal<br />

• Allowable chilled water supply temperature<br />

• Horizontal and vertical space restrictions<br />

• Occupant thermal comfort considerations<br />

• Architectural considerations<br />

<strong>Chilled</strong> water supply and return temperatures<br />

Before a passive beam selection can be made, it is<br />

necessary that an appropriate chilled water supply<br />

temperature be identified. <strong>TROX</strong> USA recommends that<br />

the chilled water supply temperature to passive beams<br />

be maintained at least 1˚F above the space dew point<br />

temperature in order to assure that condensation does<br />

not occur.<br />

Return water temperatures will generally be 3 to 6˚F<br />

higher than the supply water temperature.<br />

Water flow rate and pressure loss considerations<br />

Water flow velocities in excess of 4 feet per second<br />

should be avoided in order to prevent unwanted noise.<br />

<strong>Design</strong> water flow rates below 0.25 gallons per minute<br />

are not recommended as laminar flow begins to occur<br />

below this flow rate and coil performance may be<br />

reduced. Passive chilled beams should also be selected<br />

such that their water side head loss does not exceed 10<br />

feet of water.<br />

Passive chilled beam performance data<br />

The amount of sensible cooling that can be provided by<br />

an active chilled beam is dependent on all of the factors<br />

listed above. Tables 2 and 3 illustrate the performance<br />

of <strong>TROX</strong> TCB-1 and TCB-2 series passive chilled<br />

beams. The available beam widths are listed in the<br />

table. The water side pressure loss is illustrated for 4, 6,<br />

8 and 10 foot versions of each beam. The sensible<br />

cooling capacity of each beam is expressed in BTUH<br />

per linear foot of length for various temperature<br />

differentials between entering air and the entering<br />

chilled water supply. This capacity is based on a 6 foot<br />

beam length, a discharge free area of 50% and an<br />

equal inlet free area. It also assumes that the distance<br />

between the beam and any obstacle above it is at least<br />

40% the width of the beam. Table 4 presents correction<br />

factors for other beam lengths and inlet/discharge<br />

conditions.<br />

Passive beam selection procedures<br />

Selection of passive chilled beams should be performed<br />

as follows:<br />

1. Estimate the beam entering air temperature<br />

• If a fully mixed room air distribution<br />

system is being used, the entering air<br />

temperature will equal the room control<br />

temperature.<br />

• If a stratified system is being used, the<br />

entering air temperature may be assumed<br />

to be 2˚F warmer than the room control<br />

temperature.<br />

• When mounted directly above a perimeter<br />

window, the entering air temperature can<br />

be assumed to be 6˚F warmer than the<br />

room temperature.<br />

2. Specify the chilled water supply temperature.<br />

3. Using the temperature difference between the<br />

entering air and chilled water, select a beam<br />

whose width and length will remove the<br />

required amount of sensible heat.<br />

4. Identify the required water flow rate and<br />

pressure loss for the selected beam.<br />

Passive chilled beam selection examples<br />

EXAMPLE 1:<br />

TCB-1 series passive (recessed type) chilled beams are<br />

being used to condition an interior office space that is<br />

120 feet long by 60 feet wide with a sensible heat gain<br />

12 BTUH per square foot. The space is controlled by a<br />

thermostat (at the mid-level of the room) for a dry bulb<br />

temperature of 76˚F and space RH of 50%. A thermal<br />

displacement ventilation system supplies 0.2 CFM per<br />

square foot of pretreated ventilation air at 65˚F.<br />

SOLUTION:<br />

The total sensible heat gain of the space is 8,640<br />

BTUH. The room dew point temperature is 57˚F<br />

therefore a chilled water supply temperature of 58˚F will<br />

be used.<br />

As the displacement ventilation system being used in<br />

conjunction with the beams will crate a stratified room<br />

environment, the beam entering air temperature (and<br />

the return air temperature leaving the space) may be<br />

assumed to be 2˚F warmer than the room control<br />

temperature, or in this case 78˚F.<br />

The sensible heat removal of the ventilation air can then<br />

be calculated as follows:<br />

q VENT = 1.09 x CFM VENT x (T RETURN – T SUPPLY )<br />

= 1.09 x (0.2 x 720) x (78 – 65)<br />

= 2,040 BTUH<br />

a<br />

27


Passive <strong>Beam</strong> Performance<br />

<strong>Beam</strong> Width (B)<br />

(inches)<br />

24<br />

20<br />

16<br />

12<br />

Water Flow Rate<br />

(GPM)<br />

ΔP WATER , ft. H 2 O<br />

<strong>Chilled</strong> <strong>Beam</strong> Length, Ft.<br />

Sensible Cooling Capacity, (BTUH/LF)<br />

T ROOM - T CWS<br />

4 5 6 8 10 15 16 17 18 19 20 21 22<br />

0.75 0.6 0.6 0.7 0.9 1.1 216 236 257 278 299 319 340 361<br />

1.00 1.0 1.1 1.3 1.6 1.9 243 264 285 305 326 347 367 388<br />

1.25 1.6 1.8 2.0 2.5 2.9 259 280 301 321 342 363 383 404<br />

1.50 2.3 2.5 2.9 3.6 4.2 270 291 301 332 353 374 394 415<br />

1.75 0.4 0.4 0.5 0.6 0.7 278 299 319 340 361 381 402 423<br />

2.00 0.5 0.6 0.6 0.8 1.0 284 304 325 346 366 387 408 428<br />

2.25 0.6 0.7 0.8 1.0 1.2 288 309 329 350 371 391 412 433<br />

2.50 0.8 0.9 1.0 1.2 1.5 292 312 333 354 374 395 416 437<br />

2.75 0.9 1.1 1.2 1.5 1.8 295 315 336 357 377 398 419 439<br />

3.00 1.1 1.3 1.4 1.8 2.1 297 318 338 359 380 400 421 442<br />

0.75 0.4 0.5 0.6 0.7 0.9 211 229 247 264 278 296 315 334<br />

1.00 0.8 0.9 1.0 1.3 1.6 232 249 267 284 299 318 337 355<br />

1.25 1.2 1.4 1.6 2.0 2.4 244 262 279 297 312 331 350 368<br />

1.50 1.7 2.1 2.3 2.8 3.5 252 270 287 305 321 346 359 377<br />

1.75 0.3 0.4 0.4 0.5 0.6 270 276 293 311 327 216 365 383<br />

2.00 0.4 0.5 0.5 0.7 0.8 262 280 298 315 332 351 369 388<br />

2.25 0.5 0.6 0.7 0.8 1.0 266 284 301 319 336 354 373 392<br />

2.50 0.7 0.7 0.8 1.0 1.2 269 286 304 321 339 357 376 395<br />

2.75 0.8 0.9 1.0 1.2 1.5 271 288 306 324 341 360 378 397<br />

3.00 0.9 1.1 1.2 1.5 1.8 273 290 308 325 343 362 380 399<br />

0.75 0.5 0.5 0.6 0.7 0.9 183 197 212 227 241 256 270 285<br />

1.00 0.8 1.0 1.1 1.3 1.6 197 211 226 240 255 270 284 299<br />

1.25 1.3 1.5 1.7 2.1 2.5 205 220 234 249 263 278 293 307<br />

1.50 1.9 2.2 2.4 3.0 3.6 210 225 240 254 269 283 298 313<br />

1.75 0.3 0.3 0.3 0.4 0.5 214 229 244 258 273 287 302 317<br />

2.00 0.3 0.4 0.4 0.5 0.6 217 232 247 261 276 290 305 320<br />

2.25 0.4 0.5 0.5 0.7 0.8 220 234 249 264 278 293 307 322<br />

2.50 0.5 0.6 0.7 0.8 1.0 222 236 251 265 280 295 309 324<br />

2.75 0.6 0.7 0.8 1.0 1.2 223 238 252 267 281 296 311 325<br />

3.00 0.8 0.9 1.0 1.2 1.4 224 239 254 268 283 297 312 327<br />

0.75 0.3 0.3 0.4 0.4 0.5 164 174 185 195 206 217 227 238<br />

1.00 0.5 0.6 0.6 0.8 0.9 172 182 193 204 214 225 235 246<br />

1.25 0.8 0.9 1.0 1.2 1.5 177 187 198 208 219 230 240 251<br />

1.50 1.1 1.3 1.4 1.8 2.1 180 191 201 212 222 233 244 254<br />

1.75 0.2 0.2 0.2 0.3 0.4 182 193 203 214 225 235 246 256<br />

2.00 0.3 0.3 0.3 0.4 0.5 184 195 205 216 226 237 248 258<br />

2.25 0.3 0.4 0.4 0.5 0.6 185 196 207 217 228 238 249 260<br />

2.50 0.4 0.4 0.5 0.6 0.7 186 197 208 218 229 239 250 261<br />

2.75 0.5 0.5 0.6 0.8 0.9 187 198 209 219 230 240 251 262<br />

3.00 0.6 0.6 0.7 0.9 1.1 188 199 209 220 230 241 252 262<br />

NOTES REGARDING PERFORMANCE DATA:<br />

1. Sensible cooling data is based on a six (6) foot long uncapped beam with a 12" stack height (H), a ceiling free area of 50%<br />

and an air passage width (W) twice the beam width (B) per figure 17. 13.<br />

2. For other beam lengths, ceiling free areas and/or air passage widths see table 3 for correction factors.<br />

Table 1: TCB-1 Passive <strong>Beam</strong> (One Row Coil) Cooling Performance Data<br />

28


Passive <strong>Beam</strong> Performance<br />

<strong>Beam</strong> Width (B)<br />

(inches)<br />

24<br />

20<br />

16<br />

14<br />

Water Flow Rate<br />

(GPM)<br />

ΔP WATER , ft. H 2 O<br />

<strong>Chilled</strong> <strong>Beam</strong> Length, Ft.<br />

Sensible Cooling Capacity, (BTUH/LF)<br />

T ROOM - T CWS<br />

4 5 6 8 10 15 16 17 18 19 20 21 22<br />

0.75 1.8 1.3 1.5 1.7 2.1 153 194 236 277 318 360 401 442<br />

1.00 3.2 2.3 2.6 3.1 3.7 242 283 324 366 407 448 490 531<br />

1.25 5.0 3.6 4.1 4.8 5.8 295 336 377 418 460 501 542 584<br />

1.50 7.2 5.2 5.9 6.9 8.3 330 371 412 454 495 536 577 619<br />

1.75 0.8 0.9 1.0 1.2 1.4 354 396 437 478 520 561 602 643<br />

2.00 1.0 1.1 1.3 1.6 1.9 373 415 456 497 539 580 621 662<br />

2.25 1.3 1.4 1.6 2.0 2.4 387 429 470 511 553 594 635 677<br />

2.50 1.6 1.8 2.0 2.5 2.9 399 440 482 523 564 606 647 688<br />

2.75 1.9 2.2 2.4 3.0 3.5 409 450 491 533 574 615 656 698<br />

3.00 2.3 2.6 2.9 3.6 4.2 417 458 499 541 582 623 665 706<br />

0.75 0.9 1.1 1.2 1.5 1.7 169 204 239 273 308 343 378 413<br />

1.00 1.7 1.9 2.2 2.7 3.1 232 266 301 336 371 406 440 475<br />

1.25 2.6 3.0 3.4 4.2 4.8 267 302 337 372 407 441 476 511<br />

1.50 3.8 4.3 4.9 6.0 6.9 292 326 361 396 431 466 500 535<br />

1.75 0.6 0.7 0.8 1.0 1.1 309 343 378 413 448 483 517 552<br />

2.00 0.8 1.0 1.1 1.3 1.4 322 356 391 426 461 496 530 565<br />

2.25 1.0 1.2 1.4 1.7 1.8 332 366 401 436 471 506 540 575<br />

2.50 1.3 1.5 1.7 2.0 2.2 340 375 409 444 479 514 549 583<br />

2.75 1.6 1.8 2.0 2.5 2.7 346 381 416 451 486 520 555 590<br />

3.00 1.9 2.2 2.4 2.9 3.2 352 387 422 456 491 526 561 596<br />

0.75 0.8 0.9 1.0 1.2 1.4 168 195 221 247 274 300 326 352<br />

1.00 1.4 1.5 1.7 2.2 2.5 202 228 254 281 307 333 360 386<br />

1.25 2.1 2.4 2.7 3.4 3.9 222 249 275 301 327 354 380 406<br />

1.50 3.0 3.4 3.9 4.9 5.7 235 262 288 314 341 367 393 419<br />

1.75 0.5 0.6 0.6 0.8 1.0 245 272 298 324 350 377 403 429<br />

2.00 0.7 0.8 0.8 1.1 1.2 252 279 305 331 358 384 410 437<br />

2.25 0.8 1.0 1.1 1.3 1.6 258 284 311 337 363 389 416 442<br />

2.50 1.0 1.2 1.3 1.6 2.0 262 289 315 341 368 394 420 447<br />

2.75 1.2 1.4 1.6 2.0 2.4 266 292 319 345 371 398 424 450<br />

3.00 1.5 1.7 1.9 2.4 2.8 269 296 322 348 375 401 427 453<br />

0.75 0.6 0.7 0.8 1.1 1.3 153 176 198 221 244 266 289 311<br />

1.00 1.1 1.3 1.5 1.9 2.2 177 199 222 245 267 290 312 335<br />

1.25 1.8 2.0 2.3 3.0 3.5 191 214 237 259 282 304 327 350<br />

1.50 2.5 2.9 3.3 4.3 5.0 201 224 246 269 291 314 337 359<br />

1.75 0.4 0.5 0.6 0.7 0.8 208 231 253 276 298 321 344 366<br />

2.00 0.6 0.7 0.7 0.9 1.1 213 236 258 281 303 326 349 371<br />

2.25 0.7 0.8 0.9 1.2 1.3 217 240 262 285 308 330 353 375<br />

2.50 0.9 1.0 1.2 1.4 1.7 220 243 265 288 311 333 356 378<br />

2.75 1.1 1.2 1.4 1.7 2.0 223 245 268 291 313 336 358 381<br />

3.00 1.3 1.5 1.7 2.1 2.4 225 248 270 293 315 338 361 383<br />

NOTES REGARDING PERFORMANCE DATA:<br />

1. Sensible cooling data is based on a six (6) foot long uncapped beam with a 12" stack height (H), a ceiling free area of 50%<br />

and an air passage width (W) twice the beam width (B) per figure 17. 13.<br />

2. For other beam lengths, ceiling free areas and/or air passage widths see table 3 for correction factors.<br />

Table 2: TCB-2 Passive <strong>Beam</strong> (Two Row Coil) Cooling Performance Data<br />

29


Passive <strong>Beam</strong> Performance<br />

<strong>Beam</strong> Length<br />

(linear ft.)<br />

4<br />

6<br />

8<br />

10<br />

Stack Height<br />

(inches)<br />

8<br />

10<br />

12<br />

8<br />

10<br />

12<br />

8<br />

10<br />

12<br />

8<br />

10<br />

12<br />

Ceiling Panel Free Area<br />

(%)<br />

Cooling Performance Factor (F C )<br />

<strong>Beam</strong> Width (Inches)<br />

12 * 14 * 16 20 24<br />

W = 2.0 x B W = 2.0 x B W = 2.0 x B W = 2.0 x B W = 2.0 x B<br />

30.0% 0.81 0.81 0.81 0.81 0.81<br />

40.0% 0.91 0.91 0.91 0.91 0.91<br />

50% or more 0.95 0.95 0.95 0.95 0.95<br />

30.0% 0.86 0.86 0.86 0.86 0.86<br />

40.0% 0.96 0.96 0.96 0.96 0.96<br />

50% or more 1.01 1.01 1.01 1.01 1.01<br />

30.0% 0.90 0.90 0.90 0.90 0.90<br />

40.0% 1.01 1.01 1.01 1.01 1.01<br />

50% or more 1.06 1.06 1.06 1.06 1.06<br />

30.0% 0.77 0.77 0.77 0.77 0.77<br />

40.0% 0.86 0.86 0.86 0.86 0.86<br />

50% or more 0.90 0.90 0.90 0.90 0.90<br />

30.0% 0.81 0.81 0.81 0.81 0.81<br />

40.0% 0.90 0.90 0.90 0.90 0.90<br />

50% or more 0.95 0.95 0.95 0.95 0.95<br />

30.0% 0.85 0.85 0.85 0.85 0.85<br />

40.0% 0.95 0.95 0.95 0.95 0.95<br />

50% or more 1.00 1.00 1.00 1.00 1.00<br />

30.0% 0.73 0.73 0.73 0.73 0.73<br />

40.0% 0.82 0.82 0.82 0.82 0.82<br />

50.0% 0.86 0.86 0.86 0.86 0.86<br />

30.0% 0.78 0.78 0.78 0.78 0.78<br />

40.0% 0.87 0.87 0.87 0.87 0.87<br />

50% or more 0.91 0.91 0.91 0.91 0.91<br />

30.0% 0.82 0.82 0.82 0.82 0.82<br />

40.0% 0.91 0.91 0.91 0.91 0.91<br />

50.0% 0.96 0.96 0.96 0.96 0.96<br />

30.0% 0.71 0.71 0.71 0.71 0.71<br />

40.0% 0.80 0.80 0.80 0.80 0.80<br />

50% or more 0.84 0.84 0.84 0.84 0.84<br />

30.0% 0.75 0.75 0.75 0.75 0.75<br />

40.0% 0.84 0.84 0.84 0.84 0.84<br />

50% or more 0.88 0.88 0.88 0.88 0.88<br />

30.0% 0.79 0.79 0.79 0.79 0.79<br />

40.0% 0.88 0.88 0.88 0.88 0.88<br />

50% or more 0.93 0.93 0.93 0.93 0.93<br />

* TCB-1 (1 row) beams are available in 12 inch width, but not 14 inches. TCB-2 (2 row) beams are available in 14 inch width, but not 12".<br />

NOTES:<br />

1. Cooling performance in tables 1 and 2 are based on 6 foot long beams with a 12" stack height (and W = 2.0 x B).<br />

They also assume a 50% (or more free area for both the intake and discharge section (see figure table 13). 17).<br />

2. To determine the performance of a beam with a different length, stack height or facial (free) area, multiply the<br />

appropriate cooling factor (F C ) from the table of above by the sensible cooling value from table 1 or 2.<br />

3. To determine the performance of a beam with a different length, stack height or facial (free) area, multiply the<br />

appropriate cooling factor (F C ) from the table of above by the sensible cooling value from table 1 or 2.<br />

Table 3: Correction Factors for Other <strong>Beam</strong> Configurations<br />

30


Passive <strong>Beam</strong> Selection<br />

The required sensible heat removal of the beams is the<br />

total sensible heat gain of the space (8,640 BTUH) less<br />

that removed by the air supply (2,040 BTUH) or 6,600<br />

BTUH.<br />

Blind Box<br />

In order to contain the beam and its required inlet area<br />

within a single 2 foot wide ceiling module, it is desired<br />

that 12” wide beams be used. Table 1 indicates four 8<br />

foot long beams with chilled water flow rates of 0.75<br />

GPM (and a 20˚F temperature differential between the<br />

entering air and chilled water) could remove the required<br />

sensible heat. These would be located uniformly<br />

within the space.<br />

H<br />

0.3 x B<br />

B<br />

0.5 x B<br />

Passive <strong>Beam</strong>s in Perimeter Applications<br />

When passive beams are used for perimeter applications,<br />

it is not necessary that the inlet area to the beam<br />

be as wide as with interior applications. The momentum<br />

of the warm air moving up the façade assists in the delivery<br />

to the beam. Figure 31 illustrates such an application<br />

and suggests that the width of the gap between the<br />

beam and the façade can be as little as 33 percent of<br />

the beam width, but must be maintained throughout the<br />

entire entry passage. For such cases, the performance<br />

data shown in tables 1 and 2 may be used. In addition,<br />

the beam entering air temperature can be assumed to<br />

be 6 to 8°F warmer during design operation.<br />

EXAMPLE 2:<br />

A TCB-2 (recessed type) passive beam is to be used for<br />

conditioning a 120 square foot perimeter space served<br />

by a UFAD system. The space design conditions are<br />

74˚F/55% RH. The space sensible heat gain is 45<br />

BTUH per square foot, 10 BTUH per square foot of<br />

which will be removed by the pretreated air in the UFAD<br />

system. The perimeter exposure is 10 feet long.<br />

SOLUTION:<br />

The beam entering air temperature can be assumed to<br />

be 81˚F. A chilled water supply temperature of 59˚F<br />

(1˚F above the space dew point) has been chosen,<br />

therefore the temperature difference between the entering<br />

air and entering water is 22˚F. The passive beam<br />

selected must be capable of removing 4,200 BTUH (35<br />

BTUH per square foot) of sensible heat. If an 8 foot long<br />

beam is to be used, it must remove 525 BTUH per linear<br />

foot. According to table 2, a 20 inch wide beam at 1.5<br />

GPM could be used.<br />

ACTIVE BEAM SELECTION AND LOCATION<br />

In addition to sensible heat removal and water side<br />

pressure loss effects, active chilled beam selection and<br />

location should also consider acoustical and air side<br />

pressure effects as well as room air distribution performance<br />

and its effect on occupant thermal comfort.<br />

Figure 31: Passive <strong>Beam</strong>s for Perimeter<br />

Cooling Applications<br />

<strong>TROX</strong> DID active chilled beams offer a range of air nozzles<br />

that afford the designer to tailor the beam selection<br />

to the space cooling and air distribution requirements.<br />

DID300 and DID600U series beams offer three different<br />

nozzle sizes (A, B or C) . Type A nozzles are the smallest<br />

in diameter, create the highest induction ratios and<br />

thus provide the greatest sensible cooling per CFM of<br />

primary air. Their small diameter however also results in<br />

higher air side pressure losses which limit the primary<br />

airflow rates through the beam. These beams are commonly<br />

used for interior spaces where ventilation rates<br />

are very low compared to the sensible load.<br />

Type C nozzles are the largest in diameter and allow<br />

considerably higher primary airflow rates. Use of type C<br />

nozzles will allow the most sensible cooling per linear<br />

foot of beam of all the nozzles. These beams are most<br />

often used when reasonably high primary airflow rates<br />

are necessary.<br />

Type B nozzles are considerably larger than type A but<br />

still smaller than type C nozzles. Their performance is<br />

thus a compromise between the other two nozzle types.<br />

DID620 series beams offer four nozzle sizes (G, M, Z<br />

and K), but the most predominantly used are the G and<br />

M types. The type G nozzle produces induction ratios<br />

similar to the type C nozzles previously discussed but<br />

with slightly higher pressure drops and noise levels.<br />

Type M nozzles produce induction ratios that are some<br />

15% higher, but at an additional pressure drop and<br />

noise level.<br />

For information on nozzle types Z and K contact <strong>TROX</strong><br />

USA. Table 4 on page 32 presents a brief performance<br />

comparison of the various nozzle types.<br />

31


Active <strong>Beam</strong> Selection and Location<br />

<strong>Chilled</strong> water supply and return temperatures<br />

Before an active chilled beam selection can be made, it<br />

is necessary that an appropriate chilled water supply<br />

temperature be identified. <strong>TROX</strong> USA recommends that<br />

the chilled water supply temperature to active beams be<br />

selected and maintained at or above the space dew<br />

point temperature in order to assure that condensation<br />

does not occur. Return water temperatures will generally<br />

be 3 to 6˚F higher than the supply water temperature.<br />

Active <strong>Beam</strong><br />

Series<br />

DID-302-US<br />

DID-602-US<br />

DID-602-HC<br />

DID-622-US<br />

DID-622-HC<br />

Nozzle<br />

Type<br />

C<br />

A<br />

C<br />

Induction<br />

Ratio 1<br />

A 5.3<br />

B<br />

4.2<br />

3.2<br />

A 5.3<br />

B 4.2<br />

C 3.2<br />

5.3<br />

B 4.2<br />

3.3<br />

M 4.8<br />

G 3.7<br />

M 4.8<br />

G 3.7<br />

Primary Airflow<br />

CFM/LF<br />

ΔP AIR<br />

inches H 2 O<br />

Maximum <strong>Chilled</strong><br />

Water Flow Rate<br />

(GPM)<br />

NC<br />

Secondary Cooling 2 Total Cooling 3<br />

BTUH/LF BTUH/CFM BTUH/LF BTUH/CFM<br />

5.0 0.19


Active <strong>Beam</strong> Selection and Location<br />

Water flow rate and pressure loss considerations<br />

Water flow velocities in excess of 4 feet per second<br />

should be avoided in order to prevent unwanted noise.<br />

<strong>Design</strong> water flow rates below 0.25 gallons per minute<br />

are not recommended as laminar flow begins to occur<br />

below this flow rate and coil performance may be reduced.<br />

<strong>Chilled</strong> beams should also be selected such that their<br />

water side head loss does not exceed 10 feet of water.<br />

Air side design considerations<br />

Although active chilled beams remove large amounts<br />

sensible heat from the room air that is circulated<br />

through them, it is very important that the designer does<br />

not treat them as purely an air conditioning device. They<br />

are also an air distribution device and their proper selection<br />

and placement is paramount to the maintenance<br />

of thermal comfort within the space. The design of active<br />

chilled beam systems must not only consider the<br />

sensible cooling (and or heating) capacities of the<br />

beams but also their resultant room air distribution.<br />

Figure 19 can be used to predict local velocities for active<br />

chilled beams. In order to prevent excessive velocities<br />

in the occupied zone, it is recommended that the<br />

beam discharge airflow rate (primary plus induced room<br />

air) not be greater than 40 CFM per linear foot of slot,<br />

therefore 2 slot beams should not be sized for primary<br />

airflow rates in excess of 80 CFM per linear foot of<br />

beam.<br />

The primary airflow rate to active chilled beams must be<br />

sufficient to maintain proper ventilation of the space.<br />

The preconditioning of the primary air delivery must also<br />

enable the primary air supply to provide adequate<br />

space dehumidification without assistance from the<br />

cooling coil within the beam. When active beams are<br />

applied in humid climates, designing for a space relative<br />

humidity level near 55% will often result in a more effective<br />

application of the chilled beam system. This is particularly<br />

true when the dew point temperature of the<br />

primary air cannot be suppressed below about 53˚F<br />

(see further discussion see page 15).<br />

Oftentimes, the cooling, ventilation and/or demands for<br />

areas fed by the same air handling unit vary. In such<br />

cases, the designer should attempt to match the inlet<br />

pressure requirements of those beams as closely as<br />

possible in order to reduce the noise that can be generated<br />

by pressure regulating dampers in the ductwork.<br />

This can often be accomplished by selecting nozzle<br />

types that will match the pressure drop to the beam<br />

primary airflow rate.<br />

Active beams used for both heating and cooling<br />

Active chilled beams can be used for heating as well as<br />

cooling. This is commonly done in climates where overhead<br />

heating with all air systems is popular.<br />

Heating can be accomplished in either of two ways:<br />

<strong>Beam</strong>s can be fitted to a four pipe system (using the<br />

four pipe performance data) that enables the beam to<br />

access either chilled or hot water according to the<br />

space demand.<br />

A zone heating coil can be provided in the primary air<br />

duct that will add the required zone heating to the primary<br />

air prior to its entry into the beam. A two pipe system<br />

(delivering chilled water only) will then be sufficient<br />

as the zone chilled water valve will remain closed during<br />

periods demanding space heating.<br />

The latter practice is often employed as it results in far<br />

less piping. With either approach, the discharge air temperature<br />

should not be more than 15°F above that of<br />

the room (per ASHRAE recommendations) if adequate<br />

overhead heating performance is to be achieved. This<br />

same recommendation is valid for all air heating as well.<br />

Selecting active beams to do both heating and cooling<br />

of perimeter areas requires a close examination of the<br />

resultant room air velocities. Figure 36 introduces two<br />

velocities (VL 2 and VL 6 ) that aid the designer in selecting<br />

beams for this application.<br />

VL 2 represents the velocity measured two (2) inches<br />

from the outside window at the mid-level of the space.<br />

For good heating performance this value should be at<br />

least 50 FPM during the heating mode.<br />

VL 6 represents the velocity six (6) inches form the surface,<br />

and is used to assess the draft risk during cooling<br />

operation. For minimal draft risk, the VL 6 value should<br />

not exceed about 75 FPM.<br />

A good beam selection will conform to both of the recommendations<br />

cited.<br />

Active beams operated in a VAV mode<br />

Although they primarily deliver constant air volume (at a<br />

variable temperature) active beams may be operated in<br />

a VAV mode when space cooling requirements vary<br />

greatly (conference rooms, etc.). In such cases there is<br />

little concern over “dumping” at low discharge velocities<br />

as the cooling coil is off and the discharge air temperature<br />

is only a few degrees below that of the room being<br />

served.<br />

33


Active <strong>Beam</strong> Performance Data<br />

Active beam performance data<br />

Performance data for DID600 series, DID620 series,<br />

and DID300 series active chilled beams are presented<br />

in figures 37 through 62. Table 5 may be used as a<br />

reference to that data. Note that this performance data<br />

pertains only to those beams manufactured by <strong>TROX</strong><br />

USA and is intended for the sole purpose of selecting<br />

those products. These data may not be applicable to<br />

versions offered by other <strong>TROX</strong> companies.<br />

<strong>TROX</strong> USA also offers electronic selection programs<br />

for all of these chilled beams. Contact <strong>TROX</strong><br />

USA or your local representative for details.<br />

The cooling capacity nomographs are based on beams<br />

of six (6) foot length supplied by primary air whose dry<br />

bulb temperature is 20˚F cooler than the room being<br />

supplies. The chilled water is supplied at a temperature<br />

which is 18°F above the room air being induced into the<br />

beam. Cooling performance for each nozzle type is<br />

presented. The primary airflow range for each nozzle is<br />

limited to that which results in primary air side pressure<br />

losses below one (1) inch of water and NC levels below<br />

40 (based on 10dB per octave band room attenuation.<br />

The minimum cooling capacities shown are with no<br />

chilled water contribution and represent the sensible<br />

cooling provided by the preconditioned primary air supply.<br />

Use of these nomographs will facilitate the selection of<br />

a nozzle type as well as identify the cooling capacities<br />

of the beam for various differentials between the room<br />

and entering chilled water temperatures.<br />

Similar nomographs are provided for heating applications<br />

which assume a primary air delivery temperature<br />

that is 20˚F below that of the room and a hot water supply<br />

that is 50°F warmer than the induced room air.<br />

Again the primary air ranges for the various nozzles are<br />

limited by the air side pressure loss (less than 1” H 2 O.)<br />

and space NC (40) level. In the case of the heating<br />

nomographs, shaded areas are labeled “Primary Air<br />

Cooling” represents the cooling effect of the primary air.<br />

The net sensible heating values shown reflect this primary<br />

air cooling effect.<br />

Both the cooling and heating nomographs include correction<br />

factors for other beam lengths. Corrections<br />

should also be made if the room to primary air temperature<br />

differential varies from that assumed by the nomographs.<br />

Finally, figure 19 is used to estimate local velocities<br />

associated with the chilled beam selection and placement.<br />

The use of these tables is illustrated in the selection<br />

examples that follow.<br />

Performance Parameter<br />

DID601<br />

(1 Slot)<br />

Active <strong>Beam</strong> Type and Discharge Configuration<br />

DID602<br />

(2 Slot)<br />

DID621<br />

(1 Slot)<br />

DID622<br />

(2 Slot)<br />

DID301<br />

(1 Slot)<br />

DID302<br />

(2 Slot)<br />

Cooling Performance (2 Pipe Variants)<br />

- Sensible cooling capacities<br />

- <strong>Chilled</strong> water flow rates<br />

- Airside pressure loss data<br />

- Acoustical (NC) data<br />

Figure 45<br />

Figure 46<br />

Figure 51<br />

Figure 52<br />

Figure 57<br />

Figure 58<br />

Cooling Performance (4 Pipe Variants)<br />

- Sensible cooling capacities<br />

- <strong>Chilled</strong> water flow rates<br />

- Airside pressure loss data<br />

- Acoustical (NC) data<br />

Figure 47<br />

Figure 48<br />

Figure 53<br />

Figure 54<br />

Figure 59<br />

Figure 60<br />

Heating Performance (2 Pipe Variants)<br />

- Sensible heating capacities<br />

- Hot water flow rates<br />

- Airside pressure loss data<br />

- Acoustical (NC) data<br />

Figure 49<br />

Figure 50<br />

Figure 55<br />

Figure 56<br />

Figure 61<br />

Figure 62<br />

<strong>Chilled</strong> Water Pressure Loss (2 Pipe Coils)<br />

Figures 37<br />

and 39<br />

Figures 37<br />

and 39<br />

Figures 37<br />

and 39<br />

Figures 37<br />

and 39<br />

Figure 42<br />

Figure 42<br />

<strong>Chilled</strong> Water Pressure Loss (4 Pipe Coils)<br />

Figures 38<br />

and 40<br />

Figures 38<br />

and 40<br />

Figures 38<br />

and 40<br />

Figures 38<br />

and 40<br />

Figure 43<br />

Figure 43<br />

Hot Water Pressure Loss (4 Pipe Coils)<br />

Figure 41<br />

Figure 41<br />

Figure 41<br />

Figure 41<br />

Figure 44<br />

Figure 44<br />

Table 5: Reference to Active <strong>Beam</strong> Performance Data<br />

34


Active <strong>Beam</strong> Selection Examples<br />

Active beam selection examples<br />

The following examples detail the selection of active<br />

chilled beams for a call center, brokerage trading area<br />

(high sensible load) and a laboratory (high primary air<br />

change rates).<br />

EXAMPLE 3:<br />

Select and locate DID302 series active chilled beams to<br />

condition a large open office area in a call center. The<br />

area considered is 60 feet by 30 feet and houses 22<br />

occupants. The space sensible load (14 BTUH/ft² or a<br />

total of 25,200 BTUH) is comprised as follows:<br />

Occupants:<br />

Lighting:<br />

Equipment:<br />

4.0 BTUH/ ft²<br />

1.5 W/ft² (5 BTUH/ ft²)<br />

1.5 W/ft² (5 BTUH/ft²)<br />

The space should be designed for a 75˚F dry bulb temperature<br />

and a maximum relative humidity of 53%<br />

(corresponding to a dew point temperature of 56.8˚Fand<br />

a humidity ratio (W ROOM ) of 0.0098 Lbs H 2 O per Lb DA).<br />

The primary air will be conditioned to a dew point temperature<br />

of 51˚F (corresponding to a humidity ratio W PRI-<br />

MARY of 0.0079 Lbs H 2 O per Lb DA) and delivered at<br />

55˚F. The ceilings are ten (10) feet high. The space NC<br />

shall not exceed 35.<br />

SOLUTION:<br />

As there are 22 occupants, the chilled beams must not<br />

only remove the space sensible gain, but must also<br />

treat the space latent gain (200 BTUH per person or a<br />

total of 5,000 BTUH) and provide proper space ventilation.<br />

If a ventilation rate of 15 CFM per person is to be<br />

maintained this amounts to a space ventilation rate of<br />

330 CFM.<br />

In order to satisfy the space latent gain, the required<br />

primary airflow rate would be calculated as:<br />

CFM LATENT = q LATENT / 4840 x (W ROOM – W PRIMARY )<br />

= 4,400 / 4840 x (0.0098 – 0.0079)<br />

= 478 CFM<br />

The ratio of the sensible heat gain to the primary airflow<br />

rate is therefore 52.7 (25,200 BTUH/478 CFM). The<br />

chilled water supply temperature will be specified at<br />

57˚F (18˚F below room temperature) in order to maintain<br />

it above the space dew point temperature. Referring<br />

to table 4, it would appear that a DID302-US beam<br />

with type B nozzles delivering primary air at 13 CFM per<br />

linear foot of beam would be appropriate. Table 4 also<br />

predicts that this selection would provide 702 BTUH of<br />

sensible cooling per linear foot of beam, so the application<br />

would require 36 linear feet of beam, or six (4) six<br />

(8) foot long beams.<br />

Figure 32 illustrates the desired mounting layout for the<br />

beams. Figure 19 indicates that beams with an opposing<br />

blow will provide very low VH 1 velocities when a<br />

spacing of 30 feet is maintained. The air side pressure<br />

loss will be 0.47 inches of H 2 O and an NC value of 28<br />

are indicated by table 4. Figure 42 predicts a water side<br />

pressure loss of 8.25 feet for a chilled water flow rate of<br />

1.5 GPM.<br />

EXAMPLE 4:<br />

Select and locate DID622 series active chilled beams to<br />

condition a brokerage trading area. The area considered<br />

is 40 feet by 40 feet and houses 16 traders. The<br />

space sensible load (44 BTUH/ft² or a total of 81,600<br />

BTUH) is comprised as follows:<br />

Occupants:<br />

Lighting:<br />

Equipment:<br />

5.0 BTUH/ ft²<br />

1.5 W/ft² (5 BTUH/ ft²)<br />

12 W/ft² (41 BTUH/ft²)<br />

DID302-US Active <strong>Chilled</strong><br />

<strong>Beam</strong>s, 6 foot Nominal<br />

Length (typical of 6)<br />

10 feet<br />

The space should be designed for a 75˚F dry bulb temperature<br />

and a maximum relative humidity of 53%<br />

(corresponding to a dew point temperature of 56.8˚F<br />

and a humidity ratio (W ROOM ) of 0.0098 Lbs H 2 O per Lb<br />

DA). The primary air will be conditioned to a dew point<br />

temperature of 51˚F (corresponding to a humidity ratio<br />

W PRIMARY of 0.0079 Lbs H 2 O per Lb DA) and delivered<br />

at 55˚F. The ceilings are ten (10) feet high. The space<br />

NC shall not exceed 40.<br />

30 feet<br />

Figure 32: <strong>Beam</strong> Layout for Example 3<br />

35


Active <strong>Beam</strong> Selection Examples<br />

SOLUTION:<br />

The beams must be selected to remove 70,400 BTUH<br />

(44 BTUH/FT²) of sensible heat from the space.<br />

The beams‟ primary airflow rate must also be sufficient<br />

to handle the latent gain from the 16 occupants (200<br />

BTUH per person or a total of 3,200 BTUH) and provide<br />

proper ventilation (176 CFM per ASHRAE Standard<br />

62.1-2004) to the space occupants. In order to satisfy<br />

the space latent gain, the required primary airflow rate<br />

would be calculated as:<br />

CFM LATENT = q LATENT / 4840 x (W ROOM – W PRIMARY )<br />

= 3,200 / 4840 x (0.0098 – 0.0079)<br />

= 348 CFM<br />

The ideal ratio of the sensible heat gain to the primary<br />

airflow rate would be 202 BTUH/CFM of primary air, but<br />

this is not achievable for any of the beam/nozzle arrangements<br />

listed in table 4. The sensible cooling requirement<br />

will therefore determine the primary airflow<br />

rate.<br />

The chilled water supply temperature will be specified at<br />

57˚F (18˚F below room temperature) in order to maintain<br />

it above the space dew point temperature. In order<br />

to minimize the number of beams, DID622-HC beams<br />

(and two pipe –HC coils) will be considered. Figure 52<br />

summarizes the performance of a six (6) foot beam of<br />

this type. If “G” nozzles are to be used, an airflow rate<br />

of 23 BTUH/LF can be employed within the acoustical<br />

constraints defined. This will result in a beam sensible<br />

cooling capacity of about 1,275 BTUH/LF (with its maximum<br />

chilled water flow rate of 2.25 GPM). In this case,<br />

we would require 64 linear feet of beams. If twelve (12)<br />

six foot units were provided, the necessary cooling<br />

(1,133 BTUH/LF) could be accomplished with a primary<br />

airflow rate of 20 CFM/LF and a chilled water flow rate<br />

of 2.25 GPM. This results in a space primary airflow<br />

requirement of 1,440 CFM.<br />

Alternatively, type “M” nozzles could be employed. Figure<br />

52 indicates that these nozzles (in a six foot beam)<br />

can provide up to 900 BTUH/LF of sensible cooling with<br />

a chilled water flow rate of 2.25 GPM and a primary<br />

airflow rate of 12 CFM/LF and. If these nozzles are chosen,<br />

we need 78 linear feet of beams. If twelve (12)<br />

eight foot units (at their maximum chilled water flow rate<br />

of 2.0 GPM) are employed, the cooling requirement<br />

could be satisfied at a primary airflow rate of 11.5 CFM /<br />

LF, or a total primary airflow rate of 1,104 CFM.<br />

In either case the NC level would be within specified<br />

levels, while the air side pressure drop would be approximately<br />

1.0 inches H 2 O.<br />

If, in order to minimize the primary airflow requirement,<br />

the latter selection were preferred, the beam layout<br />

might be as shown in figure 33.<br />

Referring to figure 19, the total discharge airflow rate<br />

(CFM/LF of beam) of the selection using “M” nozzles is:<br />

CFM SUPPLY = CFM PRIMARY x Induction Ratio<br />

= 11.5 CFM/LF x 4.8 = 55 CFM/LF<br />

As the beam has 2 slots, this equates to 27.5 CFM per<br />

linear foot of slot. The beam spacing (A) is twelve feet<br />

so A/2 is six feet. Figure 19 indicates that, the velocities<br />

VH 1 and VL 6 six feet below the ceiling velocity will be<br />

approximately 30 and 58 FPM, respectively. These are<br />

well within the values recommended.<br />

The airside pressure loss is about 0.93 inches H 2 O and<br />

the NC level (27) is well within the range specified.<br />

EXAMPLE 5:<br />

12 feet 12 feet<br />

40 feet<br />

Figure 33: <strong>Chilled</strong> <strong>Beam</strong> Layout for<br />

Selection Example 4<br />

DID602 series beams are to be used for a biological<br />

laboratory module. The laboratory module is 30 by 20<br />

feet (600 ft²) with ten (10) foot ceilings. The space sensible<br />

cooling load is 70 BTUH/ft² while the total space<br />

latent load is 2,000 BTUH. A minimum air change rate<br />

of 8 ACH-1 will be required. The velocity at the six foot<br />

level of the occupied space should not exceed 60 FPM<br />

while that along the wall cannot exceed 100 FPM. The<br />

design conditions within the laboratory are 75˚F/50%<br />

RH (W = 0.0092 LBM H 2 O per pound dry air, dew point<br />

temperature of 55.2˚F). The NC shall not exceed 40<br />

nor shall the primary air pressure drop exceed 1.0 inches<br />

H 2 O.<br />

36


Active <strong>Beam</strong> Selection Examples<br />

The primary air supply is to be delivered at 55˚F with a<br />

dew point temperature of 52˚F (W = 0.0082 LBM H 2 O<br />

per pound dry air). The beams are to be located directly<br />

above the work benches in order to capture the most<br />

sensible heat. Figure 34 illustrates the bench layout for<br />

the lab.<br />

SOLUTION:<br />

As the space dew point temperature is 55.2˚F, a 56˚F<br />

chilled water supply temperature will be used. As the<br />

beams are to be located directly above the benches<br />

where most of the space heat sources reside, the induced<br />

air entering the beams will be assumed to be 2°F<br />

warmer than the room air resulting in a 21˚F temperature<br />

differential between the room air and the entering<br />

chilled water.<br />

The minimum primary air delivery to the space for ventilation<br />

purposes is 8 ACH-1, or 800 CFM. The amount of<br />

primary air required to satisfy the space latent load may<br />

be calculated as:<br />

Figure 35 illustrates the proposed beam placement.<br />

Referring to figure 19, the total air supply from each<br />

beam will be 666 CFM or 40 CFM per linear foot of slot.<br />

As A/2 is 8 feet and X is 7 feet, the value of VH 1 and<br />

VL 6 at the six foot (H - H1 = 4 feet) level will be 56 and<br />

86 FPM, respectively.<br />

The water side pressure drop for DID602-US and<br />

DID602-HC can be found in figures 37 and 39, respectively.<br />

Lab<br />

Benches<br />

8 feet<br />

(typical)<br />

CFM LATENT = q LATENT / 4840 x (W ROOM – W PRIMARY )<br />

= 2,000 / 4840 x (0.0092 – 0.0082)<br />

= 413 CFM<br />

As this is less than the ventilation requirement, the minimum<br />

primary airflow delivery will be 800 CFM.<br />

The total space sensible load is 42,000 BTUH. Ideally,<br />

the beam selected should provide 52.5 (42,000 / 800)<br />

BTUH of sensible cooling per CFM of primary air. Table<br />

4 indicates that DID602 beams with “C” nozzles can<br />

provide such a ratio.<br />

The layout of the laboratory would favor the placement<br />

of one or two beams over each bench, so we will consider<br />

the use of four (8) eight foot beams. Applying the<br />

correction factors from figure 46 we see that an eight<br />

foot beam can provide 25 CFM/LF of primary air while<br />

keeping the air side pressure drop of inches H 2 O. The<br />

NC level (39) would also be acceptable. In order to supply<br />

the required air changes (800 CFM), we would need<br />

32 feet of these beams or four (4) eight foot lengths.<br />

As figure 46 is based on an 18°F temperature difference<br />

between the air and chilled water entering the beam, we<br />

must correct the water side sensible cooling according<br />

to the correction factor (1.16) shown in table 6 (page<br />

38) while the primary air contribution (567 BTUH/LF or<br />

17,400 BTUH total) remains the same. The sensible<br />

cooling provided the chilled water coil must thus be<br />

24,600 BTUH or 769 BTUH/LF. Applying the correction<br />

factor (1.16) from table 6, we enter figure 46 to determine<br />

the chilled water flow rate that will provide 663<br />

(769/1.16) BTUH/LF of water side sensible cooling or<br />

1,230 (663 + 567) BTUH/LF of total sensible cooling.<br />

This relates to a chilled water flow rate of 1.0 GPM.<br />

Figure 34: Lab Bench Arrangement<br />

for Example 5<br />

16 feet<br />

(typical)<br />

DID602-US Active<br />

<strong>Chilled</strong> <strong>Beam</strong><br />

(8 ft. Long, "C" Nozzles)<br />

(typical of 4)<br />

Figure 35: <strong>Chilled</strong> <strong>Beam</strong> Arrangement<br />

for Example 5<br />

37


Nomenclature and Performance Notes<br />

L (X + H1)<br />

<strong>Beam</strong> Spacing (A)<br />

X<br />

A/2<br />

ΔT Z<br />

TSUPPLY<br />

H - H1<br />

V L<br />

ΔT L<br />

V H1<br />

ΔT H1<br />

H<br />

6" for Cooling<br />

2" for Heating<br />

3.3 ft.<br />

Occupied Zone Height (H1)<br />

OCCUPIED ZONE<br />

(as defined by ASHRAE Std. 55-2004)<br />

1 ft.<br />

Figure 36: Room Air Velocity and Temperature Parameters Used in this <strong>Design</strong><br />

Nomenclature<br />

V H1 : Local velocity at the top of the occupied zone directly below the point of collision of opposing air streams<br />

T H1 : Local temperature at the top of the occupied zone directly below the point of collision of opposing air streams<br />

V L2 : Local velocity at the top of the occupied zone measured two (2) inches from an outside wall<br />

T L2 : Local temperature at the top of the occupied zone measured two (2) inches from an outside wall<br />

V L6 : Local velocity at the top of the occupied zone measured six (6) inches from an outside wall<br />

T L6 : Local temperature at the top of the occupied zone measured six (6) inches from an outside wall<br />

A: Centerline distance between two active beams with opposing blows<br />

X: Distance between active beam centerline and an adjacent wall<br />

H: Mounting height of active chilled beam<br />

H1: Height of occupied zone (usually considered 42” for seated occupants, 66 inches for standing occupants)<br />

T INDUCED AIR : Dry bulb temperature of room air entering the chilled beam cooling coil<br />

T CWS : Temperature of the chilled water entering the chilled beam transfer coil (cooling mode)<br />

T HWS : Temperature of the hot water entering the chilled beam heat transfer coil (heating mode)<br />

Induction ratio: Ratio of discharge airflow rate (to the room) to primary (ducted) airflow rate<br />

Net sensible heating: <strong>Beam</strong> water side heating less the cooling effect of the (cooler) primary air<br />

t INDUCED AIR - t CWS<br />

12°F<br />

14°F<br />

16°F<br />

18°F<br />

20°F<br />

22°F<br />

t IHWS - t INDUCED AIR<br />

20°F<br />

30°F<br />

40°F<br />

50°F<br />

60°F<br />

70°F<br />

Water Side Sensible<br />

Cooling Correction<br />

Factor<br />

0.67<br />

0.78<br />

0.89<br />

1.0<br />

1.11<br />

1.22<br />

Water Side Heating<br />

Correction Factor<br />

0.4<br />

0.6<br />

0.8<br />

1.0<br />

1.2<br />

1.4<br />

Table 6: Water Side Correction Factors for<br />

Various Entering Air to Entering <strong>Chilled</strong> Water<br />

Temperature Differentials<br />

Table 7: Water Side Correction Factors for<br />

Various Entering Air to Entering Hot Water<br />

Temperature Differentials<br />

38


<strong>Chilled</strong> Water Pressure Drop (FT H2O)<br />

Selection for <strong>Design</strong> Water Flow Rates Less than<br />

0.25 GPM is Not Recommended<br />

<strong>Chilled</strong> Water Pressure Drop (FT H2O)<br />

Selection for <strong>Design</strong> Water Flow Rates Less than<br />

0.25 GPM is Not Recommended<br />

Water Side Pressure Loss<br />

9.0<br />

10 Foot Nominal Length<br />

Max. GPM = 0.90<br />

8.0<br />

7.0<br />

8 Foot Nominal Length<br />

Max. GPM = 1.0<br />

6.0<br />

5.0<br />

4.0<br />

6 Foot Nominal Length<br />

Max. GPM = 1.15<br />

3.0<br />

4 Foot Nominal Length<br />

Max. GPM = 1.35<br />

2.0<br />

1.0<br />

0.25 0.50 0.75 1.00 1.25 1.50<br />

Water Flow Rate (GPM)<br />

Figure 32: 37: 2 Pipe Standard Capacity Coil <strong>Chilled</strong> Water Pressure Loss<br />

Models DID601-US-2, DID602-US-2, DID621-US-2 and DID622-US-2<br />

9.0<br />

8.0<br />

10 Foot Nominal Length<br />

Max. GPM = 1.1<br />

7.0<br />

8 Foot Nominal Length<br />

Max. GPM = 1.2<br />

6.0<br />

5.0<br />

4.0<br />

6 Foot Nominal Length<br />

Max. GPM = 1.35<br />

3.0<br />

4 Foot Nominal Length<br />

Max. GPM = 1.5<br />

2.0<br />

1.0<br />

0.25 0.50 0.75 1.00 1.25 1.50<br />

Water Flow Rate (GPM)<br />

Figure 33: 38: 4 Pipe Standard Capacity Coil <strong>Chilled</strong> Water Pressure Loss<br />

Models DID601-US-4, DID602-US-4, DID621-US-4 and DID622-US-4<br />

39


<strong>Chilled</strong> Water Pressure Drop (FT H2O)<br />

Selection for <strong>Design</strong> Water Flow Rates Less than<br />

0.5 GPM is Not Recommended<br />

<strong>Chilled</strong> Water Pressure Drop (FT H2O)<br />

Selection for <strong>Design</strong> Water Flow Rates Less than<br />

0.5 GPM is Not Recommended<br />

Water Side Pressure Loss<br />

10.0<br />

9.0<br />

10 Foot Nominal Length<br />

Max. GPM = 1.85<br />

8.0<br />

7.0<br />

8 Foot Nominal Length<br />

Max. GPM = 2.05<br />

6.0<br />

5.0<br />

4.0<br />

6 Foot Nominal Length<br />

Max. GPM = 2.35<br />

3.0<br />

4 Foot Nominal Length<br />

Max. GPM = 2.75<br />

2.0<br />

1.0<br />

0.50 0.75 1.00 1.25 1.50 1.75 2.00 2.25 2.50 2.75 3.00<br />

Water Flow Rate (GPM)<br />

Figure 39: 34: 2 Pipe High Capacity Coil <strong>Chilled</strong> Water Pressure Loss<br />

Models DID601-HC-2, DID602-HC-2, DID621-HC-2 and DID622-HC-2<br />

9.0<br />

8.0<br />

10 Foot Nominal Length<br />

Max. GPM = 2.1<br />

7.0<br />

8 Foot Nominal Length<br />

Max. GPM = 2.3<br />

6.0<br />

5.0<br />

4.0<br />

6 Foot Nominal Length<br />

Max. GPM = 2.7<br />

3.0<br />

4 Foot Nominal Length<br />

Max. GPM = 3.0<br />

2.0<br />

1.0<br />

0.50 0.75 1.00 1.25 1.50 1.75 2.00 2.25 2.50 2.75 3.00<br />

Water Flow Rate (GPM)<br />

Figure 40: 35: 4 Pipe High Capacity Coil <strong>Chilled</strong> Water Pressure Loss<br />

Models DID601-HC-4, DID602-HC-4, DID621-HC-4 and DID622-HC-4<br />

40


Hot Water Pressure Drop (FT H2O)<br />

Selection for <strong>Design</strong> Water Flow Rates Less than<br />

0.25 GPM is Not Recommended<br />

Water Side Pressure Loss<br />

6.0<br />

5.5<br />

5.0<br />

4.5<br />

4.0<br />

3.5<br />

10 Foot Nominal Length<br />

3.0<br />

2.5<br />

8 Foot Nominal Length<br />

2.0<br />

1.5<br />

6 Foot Nominal Length<br />

1.0<br />

0.5<br />

4 Foot Nominal Length<br />

0.25 0.50 0.75 1.00 1.25 1.50<br />

Water Flow Rate (GPM)<br />

Figure 36: 41: 4 Pipe (Std. or High Capacity) Hot Water Coils Pressure Loss<br />

Models DID601-US-4, DID602-US-4, DID621-US-4 and DID622-US-4,<br />

DID601-HC-4, DID602-HC-4, DID621-HC-4 and DID622-HC-4<br />

41


<strong>Chilled</strong> Water Pressure Drop (FT H2O)<br />

Selection for <strong>Design</strong> Water Flow Rates Less than<br />

0.25 GPM is Not Recommended<br />

<strong>Chilled</strong> Water Pressure Drop (FT H2O)<br />

Selection for <strong>Design</strong> Water Flow Rates Less than<br />

0.25 GPM is Not Recommended<br />

Water Side Pressure Loss<br />

9.0<br />

8.0<br />

10 Foot Nominal Length<br />

Max. GPM = 1.3<br />

7.0<br />

6.0<br />

8 Foot Nominal Length<br />

Max. GPM = 1.45<br />

5.0<br />

4.0<br />

3.0<br />

2.0<br />

1.0<br />

6 Foot Nominal Length<br />

Max. GPM = 1.5<br />

4 Foot Nominal Length<br />

Max. GPM = 1.5<br />

0.25 0.50 0.75 1.00 1.25 1.50<br />

Water Flow Rate (GPM)<br />

Figure 37: 42: 2 Pipe Standard Capacity Coil <strong>Chilled</strong> Water Pressure Loss<br />

Models DID301-US-2 and DID302-US-2<br />

9.0<br />

8.0<br />

10 Foot Nominal Length<br />

Max. GPM = 1.5<br />

7.0<br />

8 Foot Nominal Length<br />

Max. GPM = 1.5<br />

6.0<br />

5.0<br />

4.0<br />

3.0<br />

2.0<br />

6 Foot Nominal Length<br />

Max. GPM = 1.35<br />

1.0<br />

4 Foot Nominal Length<br />

Max. GPM = 1.5<br />

0.25 0.50 0.75 1.00 1.25 1.50<br />

Water Flow Rate (GPM)<br />

Figure 38: 43: 4 Pipe Standard Capacity Coil <strong>Chilled</strong> Water Pressure Loss<br />

Models DID301-US-4 and DID302-US-4<br />

42


Hot Water Pressure Drop (FT H2O)<br />

Selection for <strong>Design</strong> Water Flow Rates Less than<br />

0.25 GPM is Not Recommended<br />

Water Side Pressure Loss<br />

6.0<br />

5.5<br />

5.0<br />

4.5<br />

4.0<br />

3.5<br />

3.0<br />

2.5<br />

2.0<br />

10 Foot Nominal Length<br />

8 Foot Nominal Length<br />

1.5<br />

1.0<br />

4 Foot Nominal Length<br />

0.5<br />

6 Foot Nominal Length<br />

0.25 0.50 0.75 1.00 1.25<br />

1.50<br />

Water Flow Rate (GPM)<br />

Figure 39: 44: 4 Pipe Hot Water Coil Pressure Loss<br />

Models DID301-US-4 and DID3022-US-4<br />

43


Sensible Cooling Capacity, BTUH/LF<br />

PRIMARY AIR COOLING SECONDARY (WATER) COOLING<br />

TOTAL SENSIBLE COOLING<br />

Cooling Performance (2-Pipe) DID601<br />

1200<br />

1120<br />

1040<br />

960<br />

Chart is based on 6 ft. DID601-HC-2 (2<br />

pipe) cooling with a 20˚F temperature<br />

differential between room and primary air<br />

and an 18˚F temperature differential<br />

between room and entering chilled water.<br />

For other beam lengths, see the<br />

correction factors table below.<br />

Performance at water flow rates > 1.5<br />

GPM is only achievable with DID601-HC<br />

models.<br />

GPM CWS<br />

880<br />

3.0<br />

2.5<br />

800<br />

GPM CWS<br />

GPM CWS<br />

2.0<br />

1.5<br />

720<br />

3.0<br />

2.5<br />

1.0<br />

0.8<br />

640<br />

560<br />

3.0<br />

2.5<br />

2.0<br />

1.5<br />

2.0<br />

1.5<br />

1.0<br />

0.8<br />

0.6<br />

0.6<br />

0.4<br />

0.3<br />

480<br />

1.0<br />

0.8<br />

0.4<br />

0.2<br />

400<br />

320<br />

0.6<br />

0.4<br />

0.3<br />

0.3<br />

0.2<br />

0.2<br />

240<br />

160<br />

NC 22<br />

"C" NOZZLES<br />

25 30 35 39<br />

80<br />

0<br />

NC 20 25<br />

0.3" 0.4" 0.5" 0.6"<br />

NC 15 20 25<br />

"A" NOZZLES<br />

0.3" 0.4" 0.6" 0.8" 1.0"<br />

0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9" 1.0"<br />

30 34<br />

"B" NOZZLES<br />

0.7" 0.8" 0.9"1.0"<br />

2.0<br />

3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0 14.0<br />

Primary Airflow Rate, CFM/LF<br />

15.0<br />

Corrections for Other DID601-US-2 or DID601-HC-2 Lengths & T INDUCED AIR - T ENTERING WATER<br />

Performance Parameter<br />

Sensible Cooling (BTUH/LF)<br />

Max. Recommended GPM (DID601-US-2 models)<br />

Max. Recommended GPM (DID601-HC-2 models)<br />

Noise Level (NC)<br />

Primary Air Pressure Drop<br />

<strong>Chilled</strong> Water Pressure Loss<br />

T INDUCED AIR - T ENTERING CHILLED WATER<br />

<strong>Beam</strong> Length (Nominal Length in Feet)<br />

4 Feet 6 Feet 8 Feet<br />

10 Feet<br />

Multiply by 1.03 No Correction Multiply by 0.91 Multiply by 0.90<br />

1.35 1.15 1.0<br />

0.9<br />

2.65 2.25 2.0<br />

1.8<br />

-5 No Correction +3<br />

+4<br />

Multiply by 0.85 No Correction Multiply by 1.03 Multiply by 1.15<br />

See Figure 37 32 (DID601-US-2) or Figure 39 34 (DID601-HC-2)<br />

See Table 6 (page 38)<br />

Figure 45: 40: Cooling (2 Pipe) Performance, DID601-US-2 and DID601-HC-2<br />

44


Sensible Cooling Capacity, BTUH/LF<br />

PRIMARY AIR COOLING SECONDARY (WATER) COOLING<br />

TOTAL SENSIBLE COOLING<br />

Cooling Performance (2-Pipe) DID602<br />

1600<br />

1500<br />

1400<br />

Chart is based on 6 ft. DID602-HC-2 (2<br />

pipe) cooling with a 20˚F temperature<br />

differential between room and primary air<br />

and an 18˚F temperature differential<br />

between room and entering chilled water.<br />

For other beam lengths, see the<br />

correction factors table below.<br />

GPM CWS<br />

1300<br />

Performance at water flow rates > 1.5<br />

GPM is only achievable with DID602-HC<br />

models.<br />

3.0<br />

2.5<br />

2.0<br />

1200<br />

1.5<br />

GPM CWS<br />

1.0<br />

1100<br />

1000<br />

900<br />

800<br />

700<br />

GPM CWS<br />

3.0<br />

3.0<br />

2.5<br />

2.0<br />

1.5<br />

1.0<br />

2.5<br />

2.0<br />

1.5<br />

1.0<br />

0.8<br />

0.6<br />

0.4<br />

0.8<br />

0.6<br />

0.4<br />

0.3<br />

0.2<br />

0.8<br />

0.3<br />

600<br />

0.6<br />

0.4<br />

0.2<br />

500<br />

0.3<br />

400<br />

0.2<br />

300<br />

NC22<br />

"C" NOZZLES<br />

25 30 35 39<br />

200<br />

0.3" 0.4" 0.5"<br />

0.6" 0.7" 0.8" 0.9" 1.0"<br />

100<br />

0<br />

4.0<br />

NC 20 25<br />

0.3" 0.4" 0.5" 0.6"<br />

30 34<br />

"B" NOZZLES<br />

0.7" 0.8" 0.9"1.0"<br />

NC 15 20 25<br />

"A" NOZZLES<br />

0.3" 0.4" 0.6" 0.8" 1.0"<br />

6.0 8.0 10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0 26.0 28.0<br />

30.0<br />

Primary Airflow Rate, CFM/LF<br />

Corrections for Other DID602-US-2 or DID602-HC-2 Lengths & T INDUCED AIR - T ENTERING WATER<br />

Performance Parameter<br />

Sensible Cooling (BTUH/LF)<br />

Max. Recommended GPM (DID602-US-2 models)<br />

Max. Recommended GPM (DID602-HC-2 models)<br />

Noise Level (NC)<br />

Primary Air Pressure Drop<br />

<strong>Chilled</strong> Water Pressure Loss<br />

T INDUCED AIR - T ENTERING CHILLED WATER<br />

<strong>Beam</strong> Length (Nominal Length in Feet)<br />

4 Feet 6 Feet 8 Feet<br />

10 Feet<br />

Multiply by 1.03 No Correction Multiply by 0.91 Multiply by 0.90<br />

1.35 1.15 1.0<br />

0.9<br />

2.65 2.25 2.0<br />

1.8<br />

-5 No Correction +3<br />

+4<br />

Multiply by 0.85 No Correction Multiply by 1.03 Multiply by 1.15<br />

See Figure 37 (DID602-US-2) or Figure 39 (DID602-HC-2)<br />

See Table 6 (page 38)<br />

Figure 46: Cooling (2 Pipe) Performance, DID602-US-2 and DID602-HC-2<br />

45


Sensible Cooling Capacity, BTUH/LF<br />

PRIMARY AIR COOLING SECONDARY (WATER) COOLING<br />

TOTAL SENSIBLE COOLING<br />

Cooling Performance (4-Pipe) DID601<br />

1200<br />

1120<br />

1040<br />

960<br />

Chart is based on 6 ft. DID601-HC-4 (4<br />

pipe) cooling with a 20˚F temperature<br />

differential between room and primary air<br />

and an 18˚F temperature differential<br />

between room and entering chilled water.<br />

For other beam lengths, see the<br />

correction factors table below.<br />

Performance at water flow rates > 1.5<br />

GPM is only achievable with DID601-HC<br />

models.<br />

GPMCWS<br />

880<br />

800<br />

GPMCWS<br />

3.0<br />

2.5<br />

2.0<br />

720<br />

640<br />

GPMCWS<br />

3.0<br />

3.0<br />

2.5<br />

2.0<br />

1.5<br />

1.0<br />

1.5<br />

1.0<br />

0.8<br />

0.6<br />

560<br />

480<br />

400<br />

2.5<br />

2.0<br />

1.5<br />

1.0<br />

0.8<br />

0.6<br />

0.8<br />

0.6<br />

0.4<br />

0.3<br />

0.4<br />

0.3<br />

0.2<br />

320<br />

0.4<br />

0.3<br />

0.2<br />

240<br />

0.2<br />

160<br />

NC 22<br />

"C" NOZZLES<br />

25 30 35 39<br />

80<br />

0<br />

NC 20 25<br />

0.3" 0.4" 0.5" 0.6"<br />

NC 15 20 25<br />

"A" NOZZLES<br />

0.3" 0.4" 0.6" 0.8" 1.0"<br />

0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9" 1.0"<br />

30 34<br />

"B" NOZZLES<br />

0.7" 0.8" 0.9"1.0"<br />

2.0<br />

3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0 14.0<br />

Primary Airflow Rate, CFM/LF<br />

15.0<br />

Corrections for Other DID601-US-4 or DID601-HC-4 Lengths & T INDUCED AIR - T ENTERING WATER<br />

Performance Parameter<br />

Sensible Cooling (BTUH/LF)<br />

Max. Recommended GPM (DID601-US-4 models)<br />

Max. Recommended GPM (DID601-HC-4 models)<br />

Noise Level (NC)<br />

Primary Air Pressure Drop<br />

<strong>Chilled</strong> Water Pressure Loss<br />

TINDUCED AIR - TENTERING CHILLED WATER<br />

<strong>Beam</strong> Length (Nominal Length in Feet)<br />

4 Feet 6 Feet 8 Feet<br />

10 Feet<br />

Multiply by 1.03 No Correction Multiply by 0.91 Multiply by 0.90<br />

1.5 1.35 1.2<br />

1.1<br />

3.0 2.65 2.35<br />

2.1<br />

-5 No Correction +3<br />

+4<br />

Multiply by 0.85 No Correction Multiply by 1.03 Multiply by 1.15<br />

See Figure 38 33 (DID601-US-4) or Figure 40 35 (DID601-HC-4)<br />

See Table 6 (page 38)<br />

Figure 47: 42: Cooling (4 Pipe) Performance, DID601-US-4 and DID601-HC-4<br />

46


Sensible Cooling Capacity, BTUH/LF<br />

PRIMARY AIR COOLING SECONDARY (WATER) COOLING<br />

TOTAL SENSIBLE COOLING<br />

Cooling Performance (4-Pipe) DID602<br />

1600<br />

1500<br />

1400<br />

Chart is based on 6 ft. DID602-HC-4 (4<br />

pipe) cooling with a 20˚F temperature<br />

differential between room and primary air<br />

and an 18˚F temperature differential<br />

between room and entering chilled water.<br />

For other beam lengths, see the<br />

correction factors table below.<br />

GPMCWS<br />

1300<br />

Performance at water flow rates > 1.5<br />

GPM is only achievable with DID602-HC<br />

models.<br />

3.0<br />

2.5<br />

1200<br />

GPMCWS<br />

2.0<br />

1.5<br />

1100<br />

1000<br />

GPMCWS<br />

3.0<br />

2.5<br />

2.0<br />

1.0<br />

0.8<br />

0.6<br />

900<br />

800<br />

3.0<br />

2.5<br />

2.0<br />

1.5<br />

1.5<br />

1.0<br />

0.8<br />

0.6<br />

0.4<br />

0.3<br />

0.2<br />

700<br />

600<br />

500<br />

1.0<br />

0.8<br />

0.6<br />

0.4<br />

0.3<br />

0.4<br />

0.3<br />

0.2<br />

400<br />

0.2<br />

300<br />

NC 22<br />

"C" NOZZLES<br />

25 30 35 39<br />

200<br />

0.3" 0.4" 0.5"<br />

0.6" 0.7" 0.8" 0.9" 1.0"<br />

100<br />

0<br />

NC 20 25<br />

0.3" 0.4" 0.5" 0.6"<br />

NC 15 20 25<br />

"A" NOZZLES<br />

0.3" 0.4" 0.6" 0.8" 1.0"<br />

30 34<br />

0.7" 0.8" 0.9"1.0"<br />

"B" NOZZLES<br />

4.0<br />

6.0 8.0 10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0 26.0 28.0<br />

30.0<br />

Primary Airflow Rate, CFM/LF<br />

Corrections for Other DID602-US-4 or DID602-HC-4 Lengths & T INDUCED AIR - T ENTERING WATER<br />

Performance Parameter<br />

Sensible Cooling (BTUH/LF)<br />

Max. Recommended GPM (DID602-US-4 models)<br />

Max. Recommended GPM (DID602-HC-4 models)<br />

Noise Level (NC)<br />

Primary Air Pressure Drop<br />

<strong>Chilled</strong> Water Pressure Loss<br />

TINDUCED AIR - TENTERING CHILLED WATER<br />

<strong>Beam</strong> Length (Nominal Length in Feet)<br />

4 Feet 6 Feet 8 Feet<br />

10 Feet<br />

Multiply by 1.03 No Correction Multiply by 0.91 Multiply by 0.90<br />

1.5 1.35 1.2<br />

1.1<br />

3.0 2.65 2.35<br />

2.1<br />

-5 No Correction +3<br />

+4<br />

Multiply by 0.85 No Correction Multiply by 1.03 Multiply by 1.15<br />

See Figure 33 38 (DID602-US-4) or Figure 40 35 (DID602-HC-4)<br />

See Table 6 (page 38)<br />

Figure 48: 43: Cooling (4 Pipe) Performance, DID602-US-4 and DID602-HC-4<br />

47


PRIMARY AIR COOLING<br />

Net Sensible Heating Capacity, BTUH/LF<br />

WATER SIDE HEATING<br />

NET SENSIBLE HEATING<br />

Heating Performance (4-Pipe) DID601<br />

1200<br />

1100<br />

Chart is based on 6 ft. DID601-HC-4 (4 pipe) heating<br />

with a 20˚F temperature differential between room and<br />

primary air and a 50˚F temperature differential<br />

between room and entering hot water. For other beam<br />

lengths, see the correction factors table below.<br />

1000<br />

900<br />

GPMHWS<br />

GPMHWS<br />

800<br />

700<br />

GPMHWS<br />

1.5<br />

1.0<br />

1.5<br />

1.0<br />

0.8<br />

1.5<br />

1.0<br />

0.8<br />

600<br />

0.8<br />

0.6<br />

0.6<br />

0.6<br />

500<br />

400<br />

0.4<br />

0.4<br />

0.3<br />

0.3<br />

0.2 0.2<br />

0.4<br />

0.3<br />

300<br />

0.2<br />

200<br />

100<br />

0<br />

-100<br />

-200<br />

-300<br />

-400<br />

"A" NOZZLES<br />

NC 15 20 25<br />

0.3" 0.4" 0.6" 0.8" 1.0"<br />

NC 20<br />

"B" NOZZLES<br />

0.3" 0.4"<br />

25<br />

30 34<br />

0.5" 0.6" 0.7" 0.8" 0.9"1.0"<br />

-500<br />

"C" NOZZLES<br />

NC 22 25 30 35 39<br />

0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9" 1.0"<br />

2.0<br />

3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0 14.0<br />

Primary Airflow Rate, CFM/LF<br />

15.0<br />

Corrections for Other DID601-US-4 or DID601-HC-4 Lengths & T ENTERING WATER - T INDUCED AIR<br />

Performance Parameter<br />

Water Side Heating (BTUH/LF)<br />

Max. Recommended GPM (DID601-US-4 models)<br />

Max. Recommended GPM (DID601-HC-4 models)<br />

Noise Level (NC)<br />

<strong>Beam</strong> Length (Nominal Length in Feet)<br />

4 Feet 6 Feet 8 Feet<br />

10 Feet<br />

Multiply by 1.04 No Correction Multiply by 0.88 Multiply by 0.85<br />

1.5 1.5 1.5<br />

1.5<br />

1.5 1.5 1.5<br />

1.5<br />

-5 No Correction +3<br />

+4<br />

Primary Air Pressure Drop<br />

Multiply by 0.85 No Correction Multiply by 1.03 Multiply by 1.15<br />

Hot Water Pressure Loss See Figure 36 41<br />

TENTERING HOT WATER - TINDUCED AIR<br />

See Table 7 (page 38)<br />

Figure 49: 52: 44: Heating (4 Pipe) Performance, DID601-US-4 and DID601-HC-4<br />

48


PRIMARY AIR COOLING<br />

Net Sensible Heating Capacity, BTUH/LF<br />

WATER SIDE HEATING<br />

NET SENSIBLE HEATING<br />

Heating Performance (4-Pipe) DID602<br />

1000<br />

900<br />

800<br />

Chart is based on 6 ft. DID602-HC-4 (4<br />

pipe) heating with a 20˚F temperature<br />

differential between room and primary air<br />

and a 50˚F temperature differential<br />

between room and entering hot water.<br />

For other beam lengths, see the<br />

correction factors table below.<br />

GPMHWS<br />

GPMHWS<br />

700<br />

600<br />

500<br />

1.5<br />

1.0<br />

0.8<br />

0.6<br />

1.5<br />

1.0<br />

0.8<br />

0.6<br />

GPMHWS<br />

1.5<br />

1.0<br />

0.8<br />

400<br />

0.4<br />

0.3<br />

0.4<br />

0.6<br />

300<br />

0.2<br />

0.3<br />

0.4<br />

200<br />

0.2<br />

0.3<br />

100<br />

0.2<br />

0<br />

-100<br />

-200<br />

-300<br />

-400<br />

"A" NOZZLES<br />

NC 15 20 25<br />

0.3" 0.4" 0.6" 0.8" 1.0"<br />

-500<br />

-600<br />

"B" NOZZLES<br />

NC 20<br />

0.3" 0.4"<br />

25<br />

30 34<br />

0.5" 0.6" 0.7" 0.8" 0.9"1.0"<br />

-700<br />

"C" NOZZLES<br />

NC 22 25 30 35 39<br />

0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9" 1.0"<br />

4.0<br />

6.0 8.0 10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0 26.0 28.0<br />

Primary Airflow Rate, CFM/LF<br />

30.0<br />

Corrections for Other DID602-US-4 or DID602-HC-4 Lengths & T ENTERING WATER - T INDUCED AIR<br />

Performance Parameter<br />

Water Side Heating (BTUH/LF)<br />

Max. Recommended GPM (DID602-US-4 models)<br />

Max. Recommended GPM (DID602-HC-4 models)<br />

Noise Level (NC)<br />

<strong>Beam</strong> Length (Nominal Length in Feet)<br />

4 Feet 6 Feet 8 Feet<br />

10 Feet<br />

Multiply by 1.04 No Correction Multiply by 0.88 Multiply by 0.85<br />

1.5 1.5 1.5<br />

1.5<br />

1.5 1.5 1.5<br />

1.5<br />

-5 No Correction +3<br />

+4<br />

Primary Air Pressure Drop<br />

Multiply by 0.85 No Correction Multiply by 1.03 Multiply by 1.15<br />

Hot Water Pressure Loss See Figure 36 41<br />

TENTERING HOT WATER - TINDUCED AIR<br />

See Table 7 (page 38)<br />

Figure 50: 45: Heating (4 Pipe) Performance, DID602-US-4 and DID602-HC-4<br />

49


PRIMARY AIR COOLING<br />

Sensible Cooling Capacity, BTUH/LF<br />

TOTAL SENSIBLE COOLING<br />

SECONDARY (WATER) COOLING<br />

Cooling Performance (2-Pipe) DID621<br />

1120<br />

1040<br />

960<br />

880<br />

Chart is based on 6 ft. DID621-HC-2 (2<br />

pipe) cooling with a 20˚F temperature<br />

differential between room and primary air<br />

and an 18˚F temperature differential<br />

between room and entering chilled water.<br />

For other beam lengths, see the<br />

correction factors table below.<br />

Performance at water flow rates > 1.5<br />

GPM is only achievable with DID621-HC<br />

models.<br />

GPM CWS<br />

800<br />

720<br />

640<br />

3.0<br />

2.5<br />

2.0<br />

GPM CWS<br />

1.5<br />

1.0<br />

560<br />

3.0<br />

0.6<br />

480<br />

400<br />

2.0<br />

1.5<br />

1.0<br />

0.6<br />

0.4<br />

0.4<br />

0.3<br />

0.2<br />

320<br />

0.3<br />

0.2<br />

240<br />

160<br />

"G" NOZZLES<br />

80<br />

NC<br />

15<br />

20<br />

25 30 35 37<br />

0<br />

NC<br />

0.2" 0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9"<br />

15 20 25 27<br />

0.2" 0.3" 0.4" 0.6" 0.8" 1.0"<br />

"M" NOZZLES<br />

1.0"<br />

1.0<br />

2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0<br />

Primary Airflow Rate, CFM/LF<br />

Corrections for Other DID621-US-2 or DID621-HC-2 Lengths & T INDUCED AIR - T ENTERING WATER<br />

Performance Parameter<br />

Sensible Cooling (BTUH/LF)<br />

Max. Recommended GPM (DID621-US-2 models)<br />

Max. Recommended GPM (DID621-HC-2 models)<br />

Noise Level (NC)<br />

Primary Air Pressure Drop<br />

<strong>Chilled</strong> Water Pressure Loss<br />

T INDUCED AIR - T ENTERING WATER<br />

<strong>Beam</strong> Length (Nominal Length in Feet)<br />

4 feet 6 feet 8 feet<br />

10 feet<br />

Multiply by 1.02 No Correction Multiply by 0.98 Multiply by 0.90<br />

1.35 1.15 1.0<br />

0.9<br />

2.65 2.25 2.0<br />

1.8<br />

-5 No Correction +3<br />

+6<br />

Multiply by 1.03 No Correction Multiply by .98 Multiply by .97<br />

See Figure 32 37 (DID621-US-2) or 39 34 (DID621-HC-2)<br />

See Table 6 (page38)<br />

Figure 51: 46: Cooling (2 Pipe) Performance, DID621-US-2 and DID621-HC-2<br />

50


PRIMARY AIR COOLING<br />

Sensible Cooling Capacity, BTUH/LF<br />

TOTAL SENSIBLE COOLING<br />

SECONDARY (WATER) COOLING<br />

Cooling Performance (2-Pipe) DID622<br />

1500<br />

1400<br />

1300<br />

1200<br />

Chart is based on 6 ft. DID622-HC-2 (2<br />

pipe) cooling with a 20˚F temperature<br />

differential between room and primary air<br />

and an 18˚F temperature differential<br />

between room and entering chilled water.<br />

For other beam lengths, see the<br />

correction factors table below.<br />

Performance at water flow rates > 1.5<br />

GPM is only achievable with DID622-HC<br />

models.<br />

GPMCWS<br />

1100<br />

1000<br />

900<br />

3.0<br />

2.5<br />

2.0<br />

1.5<br />

1.0<br />

800<br />

GPMCWS<br />

0.6<br />

0.4<br />

700<br />

600<br />

500<br />

400<br />

3.0<br />

2.0<br />

1.5<br />

1.0<br />

0.6<br />

0.4<br />

0.3<br />

0.2<br />

0.3<br />

0.2<br />

300<br />

"G" NOZZLES<br />

200<br />

NC<br />

15<br />

20<br />

25 30 35 37<br />

100<br />

NC<br />

0.2" 0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9"<br />

15 20 25 27<br />

0.2" 0.3" 0.4" 0.6" 0.8" 1.0"<br />

"M" NOZZLES<br />

1.0"<br />

2.0<br />

4.0 6.0 8.0 10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0 26.0<br />

Primary Airflow Rate, CFM/LF<br />

Corrections for Other DID622-US-2 or DID622-HC-2 Lengths & T INDUCED AIR - T ENTERING<br />

WATER<br />

Performance Parameter<br />

<strong>Beam</strong> Length (Nominal Length in Feet)<br />

4 feet 6 feet 8 feet<br />

10 feet<br />

Sensible Cooling (BTUH/LF)<br />

Max. Recommended GPM (DID622-US-2 models)<br />

Max. Recommended GPM (DID622-HC-2models)<br />

Noise Level (NC)<br />

Primary Air Pressure Drop<br />

<strong>Chilled</strong> Water Pressure Loss<br />

TINDUCED AIR - TENTERING CHILLED WATER<br />

Multiply by 1.02 No Correction Multiply by 0.98 Multiply by 0.90<br />

1.35 1.15 1.0<br />

0.9<br />

2.65 2.25 2.0<br />

1.8<br />

-5 No Correction +3<br />

+6<br />

Multiply by 1.02 No Correction Multiply by .98 Multiply by .97<br />

See Figure 37 32 (DID622-US-2) or Figure 39 34 (DID622-HC-2)<br />

See table 6 (page38)<br />

Figure 47: 52: Cooling (2 Pipe) Performance, DID622-US-2 and DID622-HC-2<br />

51


PRIMARY AIR COOLING<br />

Sensible Cooling Capacity, BTUH/LF<br />

TOTAL SENSIBLE COOLING<br />

SECONDARY (WATER) COOLING<br />

Cooling Performance (4-Pipe) DID621<br />

1120<br />

1040<br />

960<br />

880<br />

Chart is based on 6 ft. DID621-HC-4 (4<br />

pipe) cooling with a 20˚F temperature<br />

differential between room and primary air<br />

and an 18˚F temperature differential<br />

between room and entering chilled water.<br />

For other beam lengths, see the<br />

correction factors table below.<br />

Performance at water flow rates > 1.5<br />

GPM is only achievable with DID621-HC<br />

models.<br />

GPMCWS<br />

800<br />

720<br />

640<br />

3.0<br />

2.5<br />

2.0<br />

GPMCWS<br />

1.5<br />

560<br />

1.0<br />

0.6<br />

480<br />

400<br />

3.0<br />

2.0<br />

1.5<br />

1.0<br />

0.6<br />

0.4<br />

0.3<br />

0.2<br />

320<br />

0.4<br />

0.3<br />

240<br />

0.2<br />

160<br />

"G" NOZZLES<br />

80<br />

NC<br />

15<br />

20<br />

25 30 35 37<br />

0<br />

NC<br />

0.2" 0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9"<br />

15 20 25 27<br />

0.2" 0.3" 0.4" 0.6" 0.8" 1.0"<br />

"M" NOZZLES<br />

1.0"<br />

1.0<br />

2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0<br />

Primary Airflow Rate, CFM/LF<br />

Corrections for Other DID621-US-4 or DID621-HC-4 Lengths & T INDUCED AIR - T ENTERING<br />

WATER<br />

Performance Parameter<br />

<strong>Beam</strong> Length (Nominal Length in Feet)<br />

4 feet 6 feet 8 feet<br />

10 feet<br />

Sensible Cooling (BTUH/LF)<br />

Max. Recommended GPM (DID621-US-4 models)<br />

Max. Recommended GPM (DID621-HC-4 models)<br />

Noise Level (NC)<br />

Primary Air Pressure Drop<br />

<strong>Chilled</strong> Water Pressure Loss<br />

Multiply by 1.02 No Correction Multiply by 0.98 Multiply by 0.90<br />

1.5 1.35 1.2<br />

1.1<br />

3.0 2.65 2.35<br />

2.1<br />

-5 No Correction +3<br />

+6<br />

Multiply by 1.03 No Correction Multiply by .98 Multiply by .97<br />

See Figure 38 33 (DID621-US-4) or Figure 40 35 (DID621-HC-4)<br />

TINDUCED AIR - TENTERING CHILLED WATER See Table 6 (page 38)<br />

Figure 48: 53: Cooling (4 Pipe) Performance, DID621-US-4 and DID621-HC-4<br />

52


PRIMARY AIR COOLING<br />

Sensible Cooling Capacity, BTUH/LF<br />

TOTAL SENSIBLE COOLING<br />

SECONDARY (WATER) COOLING<br />

Cooling Performance (4-Pipe) DID622<br />

1500<br />

1400<br />

1300<br />

1200<br />

Chart is based on 6 ft. DID622-HC-4 (4<br />

pipe) cooling with a 20˚F temperature<br />

differential between room and primary air<br />

and an 18˚F temperature differential<br />

between room and entering chilled water.<br />

For other beam lengths, see the<br />

correction factors table below.<br />

Performance at water flow rates > 1.5<br />

GPM is only achievable with DID622-HC<br />

models.<br />

GPMCWS<br />

1100<br />

1000<br />

3.0<br />

2.5<br />

2.0<br />

900<br />

GPMCWS<br />

1.5<br />

1.0<br />

800<br />

0.6<br />

700<br />

600<br />

3.0<br />

2.5<br />

1.5<br />

1.0<br />

0.4<br />

0.3<br />

0.2<br />

500<br />

0.6<br />

400<br />

300<br />

0.4<br />

0.2<br />

"G" NOZZLES<br />

200<br />

NC<br />

15<br />

20<br />

25 30 35 37<br />

100<br />

NC<br />

0.2" 0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9"<br />

15 20 25 27<br />

0.2" 0.3" 0.4" 0.6" 0.8" 1.0"<br />

"M" NOZZLES<br />

1.0"<br />

2.0<br />

4.0 6.0 8.0 10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0 26.0<br />

Primary Airflow Rate, CFM/LF<br />

Corrections for Other DID622-US-4 or DID622-HC-4 Lengths & T INDUCED AIR - T ENTERING WATER<br />

Performance Parameter<br />

Sensible Cooling (BTUH/LF)<br />

Max. Recommended GPM (DID622-US-4 models)<br />

Max. Recommended GPM (DID622-HC-4 models)<br />

Noise Level (NC)<br />

Primary Air Pressure Drop<br />

<strong>Chilled</strong> Water Pressure Loss<br />

<strong>Beam</strong> Length (Nominal Length in Feet)<br />

4 feet 6 feet 8 feet<br />

10 feet<br />

Multiply by 1.02 No Correction Multiply by 0.98 Multiply by 0.90<br />

1.5 1.35 1.2<br />

1.05<br />

3.0 2.65 2.3<br />

2.1<br />

-5 No Correction +3<br />

+6<br />

Multiply by 1.03 No Correction Multiply by .98 Multiply by .97<br />

See Figure 38 33 (DID622-US-4) or Figure 40 35 (DID622-HC-4)<br />

TINDUCED AIR - TENTERING HOT WATER See Table 7 (page 38)<br />

Figure 54: 49: Cooling (4 Pipe) Performance, DID622-US-4 and DID622-HC-4<br />

53


PRIMARY AIR<br />

COOLING<br />

Net Sensible Heating Capacity, BTUH/LF<br />

NET SENSIBLE HEATING<br />

WATERSIDE HEATING<br />

Heating Performance (4-Pipe) DID621<br />

1050<br />

950<br />

850<br />

Chart is based on 6 ft. DID621-US-4 or<br />

DID621-HC-4 (4 pipe) heating with a 20˚F<br />

temperature differential between room<br />

and primary air and an 50˚F temperature<br />

differential between room and entering<br />

hot water. For other beam lengths, see<br />

the correction factors table below.<br />

GPM HWS<br />

750<br />

650<br />

GPM HWS<br />

1.5<br />

550<br />

450<br />

1.5<br />

1.0<br />

0.6<br />

1.0<br />

0.6<br />

0.4<br />

350<br />

0.4<br />

0.3<br />

250<br />

150<br />

0.3<br />

0.2<br />

0.2<br />

50<br />

0<br />

-50<br />

-150<br />

NC<br />

15 20 25 27<br />

-250<br />

0.2" 0.3" 0.4" 0.6" 0.8" 1.0"<br />

"M" NOZZLES<br />

"G" NOZZLES<br />

NC<br />

15<br />

20<br />

25 30 35 37<br />

0.2"<br />

0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9"<br />

1.0"<br />

1.0<br />

2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0<br />

Primary Airflow Rate, CFM/LF<br />

Corrections for Other DID621-US-4 or DID621-HC-4 Lengths & T ENTERING WATER - T INDUCED AIR<br />

Performance Parameter<br />

Water Side Heating (BTUH/LF)<br />

Max. Recommended GPM (DID621-US-4 models)<br />

Max. Recommended GPM (DID621-HC-4 models)<br />

Noise Level (NC)<br />

Primary Air Pressure Drop<br />

<strong>Beam</strong> Length (Nominal Length in Feet)<br />

4 Feet 6 Feet 8 Feet<br />

10 Feet<br />

Multiply by 1.03 No Correction Multiply by 0.96 Multiply by 0.92<br />

1.5 1.5 1.5<br />

1.5<br />

1.5 1.5 1.5<br />

1.5<br />

-5 No Correction +3<br />

+6<br />

Multiply by 1.03 No Correction Multiply by 0.98 Multiply by 0.97<br />

Hot Water Pressure Loss See Figure 36 41<br />

T ENTERING HOT WATER - T INDUCED AIR<br />

See table 7 (page 38)<br />

Figure 55: 50: Heating (4 Pipe) Performance, DID621-US-4 and DID621-HC-4<br />

54


PRIMARY AIR COOLING<br />

Net Sensible Heating Capacity, BTUH/LF<br />

WATER SIDE HEATING<br />

NET SENSIBLE HEATING<br />

Heating Performance (4-Pipe) DID622<br />

1000<br />

900<br />

800<br />

Chart is based on 6 ft. DID622-US-4 or<br />

DID622-HC-4 (4 pipe) heating with a 20˚F<br />

temperature differential between room<br />

and primary air and an 50˚F temperature<br />

differential between room and entering<br />

hot water. For other beam lengths, see<br />

the correction factors table below.<br />

GPMHWS<br />

700<br />

GPMHWS<br />

1.5<br />

1.0<br />

600<br />

1.5<br />

0.8<br />

500<br />

400<br />

1.0<br />

0.8<br />

0.6<br />

0.6<br />

0.4<br />

300<br />

0.4<br />

0.3<br />

0.3<br />

200<br />

0.2<br />

100<br />

0.2<br />

0<br />

-100<br />

-200<br />

-300<br />

NC<br />

15 20 25 27<br />

-400<br />

0.2" 0.3" 0.4" 0.6" 0.8" 1.0"<br />

"M" NOZZLES<br />

-500<br />

"G" NOZZLES<br />

NC<br />

15<br />

20<br />

25 30 35 37<br />

0.2"<br />

0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9"<br />

1.0"<br />

2.0<br />

4.0 6.0 8.0 10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0 26.0<br />

Primary Airflow Rate, CFM/LF<br />

Corrections for Other DID622-US-4 or DID622-HC-4 Lengths & T ENTERING WATER - T INDUCED AIR<br />

Performance Parameter<br />

Water Side Heating (BTUH/LF)<br />

Max. Recommended GPM (DID622-US-4 models)<br />

Max. Recommended GPM (DID622-HC-4 models)<br />

Noise Level (NC)<br />

Primary Air Pressure Drop<br />

<strong>Beam</strong> Length (Nominal Length in Feet)<br />

4 Feet 6 Feet 8 Feet<br />

10 Feet<br />

Multiply by 1.03 No Correction Multiply by 0.96 Multiply by 0.92<br />

1.5 1.5 1.5<br />

1.5<br />

1.5 1.5 1.5<br />

1.5<br />

-5 No Correction +3<br />

+6<br />

Multiply by 1.02 No Correction Multiply by 0.98 Multiply by 0.97<br />

Hot Water Pressure Loss See Figure 41 36<br />

TENTERING HOT WATER - TINDUCED AIR<br />

See Table 7 (page 38)<br />

Figure 56: 51: Heating (4 Pipe) Performance, DID622-US-4 and DID622-HC-4<br />

55


Sensible Cooling Capacity, BTUH/LF<br />

PRIMARY AIR COOLING SECONDARY (WATER) COOLING<br />

TOTAL SENSIBLE COOLING<br />

Cooling Performance (2-Pipe) DID301<br />

750<br />

700<br />

650<br />

Chart is based on 6 ft. DID301-US-2 (2<br />

pipe) cooling with a 20˚F temperature<br />

differential between room and primary air<br />

and an 18˚F temperature differential<br />

between room and entering chilled water.<br />

For other beam lengths, see the<br />

correction factors table below.<br />

600<br />

GPMCWS<br />

550<br />

500<br />

GPMCWS<br />

1.5<br />

1.0<br />

450<br />

0.8<br />

400<br />

350<br />

GPMCWS<br />

1.5<br />

1.0<br />

0.8<br />

0.6<br />

0.4<br />

0.3<br />

0.2<br />

300<br />

250<br />

1.5<br />

1.0<br />

0.8<br />

0.6<br />

0.6<br />

0.4<br />

0.3<br />

0.2<br />

200<br />

150<br />

0.4<br />

0.3<br />

0.2<br />

"C" NOZZLES<br />

100<br />

NC<br />

0.2"<br />

20<br />

25 30 35 39<br />

0.3" 0.4" 0.5"<br />

0.6" 0.7" 0.8" 0.9" 1.0"<br />

50<br />

NC 15<br />

0.2"<br />

20<br />

0.3"<br />

25<br />

0.4"<br />

30<br />

0.5" 0.6"<br />

35<br />

37<br />

0.8" 1.0"<br />

"B" NOZZLES<br />

0<br />

NC 15 20 25 30 33<br />

0.3" 0.3" 0.4" 0.6" 0.8" 1.0"<br />

"A" NOZZLES<br />

2.0<br />

3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0 14.0<br />

Primary Airflow Rate, CFM/LF<br />

150.0<br />

Corrections for Other DID301-US-2 Lengths & T INDUCED AIR - T ENTERING WATER<br />

Performance Parameter<br />

Sensible Cooling (BTUH/LF)<br />

Max. Recommended GPM (DID301-US-2 models)<br />

Noise Level (NC)<br />

Primary Air Pressure Drop<br />

<strong>Beam</strong> Length (Nominal Length in Feet)<br />

4 Feet 6 Feet 8 Feet<br />

10 Feet<br />

Multiply by 1.02 No Correction Multiply by 0.97 Multiply by 0.95<br />

1.5 1.5 1.45<br />

1.35<br />

-1 No Correction +1<br />

+2<br />

Multiply by 0.74 No Correction Multiply by 1.03 Multiply by 1.07<br />

<strong>Chilled</strong> Water Pressure Loss See Figure 37 42<br />

TINDUCED AIR - TENTERING CHILLED WATER<br />

See Table 6 (page 38)<br />

Figure 57: 52: Cooling (2 Pipe) Performance, DID301-US-2<br />

56


Sensible Cooling Capacity, BTUH/LF<br />

PRIMARY AIR COOLING SECONDARY (WATER) COOLING<br />

TOTAL SENSIBLE COOLING<br />

Cooling Performance (2-Pipe) DID302<br />

1500<br />

1400<br />

1300<br />

Chart is based on 6 ft. DID302-US-2 (2<br />

pipe) cooling with a 20˚F temperature<br />

differential between room and primary air<br />

and an 18˚F temperature differential<br />

between room and entering chilled water.<br />

For other beam lengths, see the<br />

correction factors table below.<br />

GPMCWS<br />

1200<br />

1100<br />

1.5<br />

1.0<br />

1000<br />

900<br />

GPMCWS<br />

0.8<br />

0.6<br />

0.4<br />

800<br />

1.5<br />

1.0<br />

0.3<br />

0.2<br />

GPMCWS<br />

700<br />

0.8<br />

0.6<br />

600<br />

1.5<br />

1.0<br />

0.4<br />

0.3<br />

500<br />

0.8<br />

0.6<br />

0.2<br />

0.4<br />

400<br />

0.3<br />

0.2<br />

300<br />

"C" NOZZLES<br />

200<br />

NC<br />

0.2"<br />

20<br />

25 30 35 39<br />

0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9" 1.0"<br />

100<br />

NC 15<br />

0.2"<br />

20<br />

0.3"<br />

25<br />

0.4"<br />

30<br />

0.5" 0.6"<br />

35<br />

37<br />

0.8" 1.0"<br />

"B" NOZZLES<br />

0<br />

NC 15 20 25 30 33<br />

0.3" 0.3" 0.4" 0.6" 0.8" 1.0"<br />

"A" NOZZLES<br />

4.0<br />

6.0 8.0 10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0 26.0 28.0<br />

Primary Airflow Rate, CFM/LF<br />

30.0<br />

Corrections for Other DID302-US-2 Lengths & T INDUCED AIR - T ENTERING WATER<br />

Performance Parameter<br />

Sensible Cooling (BTUH/LF)<br />

Max. Recommended GPM (DID302-US-2 models)<br />

Noise Level (NC)<br />

Primary Air Pressure Drop<br />

<strong>Beam</strong> Length (Nominal Length in Feet)<br />

4 Feet 6 Feet 8 Feet<br />

10 Feet<br />

Multiply by 1.02 No Correction Multiply by 0.97 Multiply by 0.95<br />

1.35 1.15 1.0<br />

0.9<br />

-1 No Correction +1<br />

+2<br />

Multiply by 0.74 No Correction Multiply by 1.03 Multiply by 1.07<br />

<strong>Chilled</strong> Water Pressure Loss See Figure 37 42<br />

TINDUCED AIR - TENTERING CHILLED WATER<br />

See table 6 (page 38)<br />

Figure 58: 53: Cooling (2 Pipe) Performance, DID302-US-2<br />

57


Sensible Cooling Capacity, BTUH/LF<br />

PRIMARY AIR COOLING SECONDARY (WATER) COOLING<br />

TOTAL SENSIBLE COOLING<br />

Cooling Performance (4-Pipe) DID301<br />

750<br />

700<br />

650<br />

Chart is based on 6 ft. DID301-US-4 (4<br />

pipe) cooling with a 20˚F temperature<br />

differential between room and primary air<br />

and an 18˚F temperature differential<br />

between room and entering chilled water.<br />

For other beam lengths, see the<br />

correction factors table below.<br />

600<br />

550<br />

500<br />

GPMCWS<br />

450<br />

400<br />

350<br />

GPMCWS<br />

1.5<br />

1.5<br />

1.0<br />

0.5<br />

0.3<br />

GPMCWS<br />

300<br />

1.0<br />

250<br />

1.5<br />

0.5<br />

0.3<br />

200<br />

1.0<br />

0.5<br />

150<br />

0.3<br />

"C" NOZZLES<br />

100<br />

NC<br />

0.2"<br />

20<br />

25 30 35 39<br />

0.3" 0.4" 0.5"<br />

0.6" 0.7" 0.8" 0.9" 1.0"<br />

50<br />

NC 15<br />

0.2"<br />

20<br />

0.3"<br />

25<br />

0.4"<br />

30<br />

0.5" 0.6"<br />

35<br />

37<br />

0.8" 1.0"<br />

"B" NOZZLES<br />

0<br />

NC 15 20 25 30 33<br />

0.3" 0.3" 0.4" 0.6" 0.8" 1.0"<br />

"A" NOZZLES<br />

2.0<br />

3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0 14.0<br />

Primary Airflow Rate, CFM/LF<br />

15.0<br />

Corrections for Other DID301-US-4 Lengths & T INDUCED AIR - T ENTERING WATER<br />

Performance Parameter<br />

Sensible Cooling (BTUH/LF)<br />

Max. Recommended GPM (DID301-US-4 models)<br />

Noise Level (NC)<br />

Primary Air Pressure Drop<br />

<strong>Beam</strong> Length (Nominal Length in Feet)<br />

4 Feet 6 Feet 8 Feet<br />

10 Feet<br />

Multiply by 1.02 No Correction Multiply by 0.97 Multiply by 0.95<br />

1.5 1.5 1.5<br />

1.5<br />

-1 No Correction +1<br />

+2<br />

Multiply by 0.74 No Correction Multiply by 1.03 Multiply by 1.07<br />

<strong>Chilled</strong> Water Pressure Loss See Figure 38 43<br />

TINDUCED AIR - TENTERING CHILLED WATER<br />

See Table 6 (page 38)<br />

Figure 54: 59: Cooling (4 Pipe) Performance, DID301-US-4<br />

58


Sensible Cooling Capacity, BTUH/LF<br />

PRIMARY AIR COOLING SECONDARY (WATER) COOLING<br />

TOTAL SENSIBLE COOLING<br />

Cooling Performance (4-Pipe) DID302<br />

1500<br />

1400<br />

1300<br />

Chart is based on 6 ft. DID302-US-4 (4<br />

pipe) cooling with a 20˚F temperature<br />

differential between room and primary air<br />

and an 18˚F temperature differential<br />

between room and entering chilled water.<br />

For other beam lengths, see the<br />

correction factors table below.<br />

1200<br />

1100<br />

GPMCWS<br />

1000<br />

1.5<br />

900<br />

800<br />

GPMCWS<br />

1.5<br />

1.0<br />

0.8<br />

0.6<br />

0.4<br />

1.0<br />

0.3<br />

700<br />

GPMCWS<br />

0.8<br />

0.2<br />

600<br />

500<br />

1.5<br />

1.0<br />

0.8<br />

0.6<br />

0.4<br />

0.3<br />

0.2<br />

400<br />

0.6<br />

0.4<br />

300<br />

0.2<br />

"C" NOZZLES<br />

200<br />

NC<br />

0.2"<br />

20<br />

25 30 35 39<br />

0.3" 0.4" 0.5"<br />

0.6" 0.7" 0.8" 0.9" 1.0"<br />

100<br />

NC 15<br />

0.2"<br />

20<br />

0.3"<br />

25<br />

0.4"<br />

30<br />

0.5" 0.6"<br />

35<br />

37<br />

0.8" 1.0"<br />

"B" NOZZLES<br />

0<br />

NC 15 20 25 30 33<br />

0.3" 0.3" 0.4" 0.6" 0.8" 1.0"<br />

"A" NOZZLES<br />

4.0<br />

6.0 8.0 10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0 26.0 28.0<br />

Primary Airflow Rate, CFM/LF<br />

30.0<br />

Corrections for Other DID302-US-2 Lengths & T INDUCED AIR - T ENTERING WATER<br />

Performance Parameter<br />

Sensible Cooling (BTUH/LF)<br />

Max. Recommended GPM (DID302-US-2 models)<br />

Noise Level (NC)<br />

Primary Air Pressure Drop<br />

<strong>Beam</strong> Length (Nominal Length in Feet)<br />

4 Feet 6 Feet 8 Feet<br />

10 Feet<br />

Multiply by 1.02 No Correction Multiply by 0.97 Multiply by 0.95<br />

1.5 1.5 1.45<br />

1.3<br />

-1 No Correction +1<br />

+2<br />

Multiply by 0.74 No Correction Multiply by 1.03 Multiply by 1.07<br />

<strong>Chilled</strong> Water Pressure Loss See Figure 38 43<br />

TINDUCED AIR - TENTERING CHILLED WATER<br />

See Table 6 (page 38)<br />

Figure 60: 55: Cooling (4 Pipe) Performance, DID302-US-4<br />

59


Net Sensible Heating Capacity, BTUH/LF<br />

PRIMARY AIR COOLING NET SENSIBLE HEATING<br />

WATERSIDE HEATING<br />

Heating Performance (4-Pipe) DID301<br />

450 Chart is based on 6 ft. DID301-US-4 (4<br />

pipe) heating with a 20˚F temperature<br />

differential between room and primary air<br />

and an 50˚F temperature differential<br />

400 between room and entering hot water.<br />

For other beam lengths, see the<br />

correction factors table below.<br />

350<br />

GPM HWS<br />

300<br />

250<br />

200<br />

150<br />

GPM HWS<br />

0.3<br />

1.5<br />

1.0<br />

GPM HWS<br />

1.5<br />

1.0<br />

0.8<br />

0.5<br />

0.8<br />

0.5<br />

0.3<br />

1.5<br />

1.0<br />

0.8<br />

0.5<br />

100<br />

0.3<br />

50<br />

0<br />

-50<br />

-150<br />

-200<br />

NC 15 20 25 30 33<br />

0.3" 0.3" 0.4" 0.6" 0.8" 1.0"<br />

"A" NOZZLES<br />

-250<br />

NC 15<br />

0.2"<br />

20<br />

0.3"<br />

25<br />

0.4"<br />

30<br />

0.5" 0.6"<br />

35<br />

37<br />

0.8" 1.0"<br />

"B" NOZZLES<br />

"C" NOZZLES<br />

NC<br />

25 30 35 39<br />

0.3" 0.4" 0.5"<br />

0.6" 0.7" 0.8" 0.9" 1.0"<br />

2.0<br />

3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0 14.0<br />

Primary Airflow Rate, CFM/LF<br />

Corrections for Other DID301-US-4 Lengths & T ENTERING WATER - T INDUCED AIR<br />

Performance Parameter<br />

Water Side Heating (BTUH/LF)<br />

Max. Recommended GPM (DID301-US-4 models)<br />

Noise Level (NC)<br />

Primary Air Pressure Drop<br />

<strong>Beam</strong> Length (Nominal Length in Feet)<br />

4 Feet 6 Feet 8 Feet<br />

10 Feet<br />

Multiply by 1.03 No Correction Multiply by 0.96 Multiply by 0.92<br />

1.5 1.5 1.5<br />

1.5<br />

-1 No Correction +1<br />

+2<br />

Multiply by 1.02 No Correction Multiply by 0.98 Multiply by 0.97<br />

Hot Water Pressure Loss See Figure 39 44<br />

T ENTERING HOT WATER - T INDUCED AIR<br />

See table 7 (page 38)<br />

Figure 61: 56: Heating (4 Pipe) Performance, DID301-US-4<br />

60


Net Sensible Heating Capacity, BTUH/LF<br />

PRIMARY AIR COOLING NET SENSIBLE HEATING<br />

WATERSIDE HEATING<br />

Heating Performance (4-Pipe) DID302<br />

700 Chart is based on 6 ft. DID302-US-4 (4 pipe) heating with<br />

a 20˚F temperature differential between room and primary<br />

air and an 50˚F temperature differential between room and<br />

entering hot water. For other beam lengths, see the<br />

600 correction factors table below.<br />

500<br />

GPM HWS<br />

GPM HWS<br />

GPM HWS<br />

400<br />

300<br />

1.5<br />

1.0<br />

0.8<br />

0.6<br />

0.4<br />

1.5<br />

1.0<br />

0.8<br />

0.6<br />

0.4<br />

1.5<br />

1.0<br />

0.8<br />

200<br />

0.6<br />

100<br />

0.4<br />

0<br />

-100<br />

-200<br />

-300<br />

-400<br />

-500<br />

NC 15 20 25 30 33<br />

0.3" 0.3" 0.4" 0.6" 0.8" 1.0"<br />

"A" NOZZLES<br />

-600<br />

NC 15<br />

0.2"<br />

20<br />

0.3"<br />

25<br />

0.4"<br />

30<br />

0.5" 0.6"<br />

35<br />

37<br />

0.8" 1.0"<br />

"B" NOZZLES<br />

"C" NOZZLES<br />

NC<br />

25 30 35 39<br />

0.3" 0.4" 0.5"<br />

0.6" 0.7" 0.8" 0.9" 1.0"<br />

4.0<br />

6.0 8.0 10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0 26.0 28.0<br />

Primary Airflow Rate, CFM/LF<br />

Corrections for Other DID302-US-4 Lengths & T ENTERING WATER - T INDUCED AIR<br />

Performance Parameter<br />

Water Side Heating (BTUH/LF)<br />

Max. Recommended GPM (DID302-US-4 models)<br />

Noise Level (NC)<br />

Primary Air Pressure Drop<br />

<strong>Beam</strong> Length (Nominal Length in Feet)<br />

4 Feet 6 Feet 8 Feet<br />

10 Feet<br />

Multiply by 1.03 No Correction Multiply by 0.96 Multiply by 0.92<br />

1.5 1.5 1.5<br />

1.5<br />

-1 No Correction +1<br />

+2<br />

Multiply by 1.02 No Correction Multiply by 0.98 Multiply by 0.97<br />

Hot Water Pressure Loss See Figure 44<br />

T ENTERING HOT WATER - T INDUCED AIR<br />

See Table 7 (page 38)<br />

Figure 62: Heating (4 Pipe) Performance, DID302-US-4<br />

61


Specification DID600<br />

DID600 Series Active <strong>Chilled</strong> <strong>Beam</strong>s<br />

PART 1- GENERAL<br />

1.01 Summary<br />

This section describes the active chilled<br />

beams.<br />

1.02 Submittals<br />

Submit product data for all items complete with the<br />

following information:<br />

1. Operating weights and dimensions of all unit<br />

assemblies.<br />

2. Performance data, including sensible and latent<br />

cooling capacities, nozzle types, primary and total<br />

supply (primary plus induced) airflow rates,<br />

chilled (and where applicable hot) water flow<br />

rates, noise levels in octave bands, air and water<br />

side pressure losses and maximum discharge air<br />

throw values.<br />

3. Construction details including manufacturers<br />

recommendations for installation, mounting and<br />

connection.<br />

PART 2- PRODUCTS<br />

2.01 General<br />

Materials and products required for the work of this<br />

section shall not contain asbestos, polychlorinated<br />

biphenyls (PCB) or other hazardous materials<br />

identified by the engineer or owner.<br />

Approved Manufacturers:<br />

These specifications set forth the minimum<br />

requirements for the active chilled beams to be<br />

accepted for this project. Products provided by the<br />

following manufacturers will be deemed acceptable<br />

provided they meet all of the construction and<br />

performance requirements of this specification:<br />

1. <strong>TROX</strong><br />

2.02 <strong>Design</strong><br />

1. Furnish and install <strong>TROX</strong> DID601 and/or DID602<br />

series active chilled beams of sizes and<br />

capacities as indicated on the drawings and<br />

within the mechanical equipment schedules. The<br />

quantity and length of the beams shall be as<br />

shown on the drawings, without EXCEPTION.<br />

The beams shall be constructed and delivered to<br />

the job site as single units.<br />

2. The face of the beam shall consist of a room air<br />

induction section of 50% free area perforated<br />

steel flanked by two linear supply slots. The<br />

entire visible face section shall be finished in<br />

white powder coat paint or as specified by the<br />

architect. All visible internal surfaces shall be flat<br />

black. The face of the beam shall be hinged for<br />

easy access to internal components.<br />

3. <strong>Beam</strong>s shall be provided with side and end<br />

details which will allow its integration into the<br />

applicable (nominal 24 inch wide) acoustical<br />

ceiling grid as specified by the architect. <strong>Beam</strong>s<br />

used for exposed mounting applications shall<br />

include factory mounted Coanda plates to assure<br />

a horizontal discharge of the supply air.<br />

4. The beams shall consist of a minimum 20 gauge<br />

galvanized steel housing encasing the integral<br />

sensible cooling coil and a plenum feeding a<br />

series of induction nozzles. A side or end<br />

mounted connection spigot shall afford the<br />

connection of a primary air supply duct (4”<br />

nominal diameter for all one way beams and 2<br />

way beams through six feet in length, 5” nominal<br />

diameter for 2 way beams longer than six feet)<br />

The overall height of the beams shall not exceed<br />

9¾ inches.<br />

5. <strong>Beam</strong>s shall incorporate provisions for<br />

measurement of their primary airflow rate. The<br />

measurement location must be accessible from<br />

the face of the beam and require a single<br />

pressure differential measurement. Airflow<br />

calibration charts that relate the measurement to<br />

the primary airflow rate shall be furnished with the<br />

beams.<br />

6. (OPTIONAL) Each beam shall be furnished with<br />

a separate volume flow limiter for mounting in the<br />

primary air duct by the installing contractor. This<br />

device shall allow field adjustment of a maximum<br />

primary air flow rate that is maintained<br />

independent of any static pressure changes in<br />

the inlet ductwork. The volume flow limiter shall<br />

add no more than 0.20 inches H 2 O pressure drop<br />

to the primary air delivery system and shall not<br />

require any control or power connections.<br />

7. <strong>Beam</strong>s shall be provided with connections for<br />

either 2 or 4 pipe operation as indicated on plans<br />

and schedules. Four pipe configurations shall<br />

require separate supply and return connections<br />

for chilled and hot water. The coils shall be<br />

mounted horizontally and shall be manufactured<br />

with seamless copper tubing (½” outside<br />

diameter) with minimum .025 inch wall thickness<br />

mechanically fixed to aluminum fins. The<br />

aluminum fins shall be limited to no more than ten<br />

(10) fins per inch. The beam shall have a working<br />

pressure of at least 300 PSI, be factory tested for<br />

leakage at a minimum pressure of 360 PSI. Each<br />

chilled beam shall be provided with factory<br />

integrated drain fittings. Each chilled beam shall<br />

be provided with factory integrated<br />

62


Specification DID600<br />

drain fittings. Unless otherwise specified, coil<br />

connections shall be bare copper for field<br />

sweating to the water supply circuit. Connections<br />

shall face upwards, be located near the left end<br />

of the beam (when viewing into the primary air<br />

connection<br />

8. (OPTIONAL) The chilled water coil shall be<br />

provided with NPT male threaded fittings where<br />

specified. These fittings must be suitable for field<br />

connection to a similar NPT female flexible hose<br />

spigot and shall be at least 1½” long to facilitate<br />

field connection (by others).<br />

9. <strong>Beam</strong>s shall be delivered clean, flushed and<br />

capped to prevent ingress of dirt.<br />

2.03 Performance<br />

1. All performance shall be in compliance with that<br />

shown on the equipment schedule. Acoustical<br />

testing shall have been performed in accordance<br />

with ISO 3741.<br />

2. Coils shall be rated in accordance with ARI<br />

Standard 410, but their cooling and heating<br />

capacities shall be established in accordance to<br />

European Standard EN15116 for the specific<br />

application on the inlet side of the submitted<br />

chilled beam. Evidence of this testing must be<br />

included in the submittal.<br />

3. Primary airflow rates shall not result in supply<br />

(primary plus induced) airflow rates in excess of<br />

80 CFM per linear foot of (two slot) beam.<br />

4. <strong>Chilled</strong> water flow rates to the beams shall be<br />

limited to that which results in a maximum ten<br />

(10) foot head loss. Water flow velocities through<br />

the beam shall not exceed 4 FPS.<br />

lowered into the grid module by adjusting the nuts<br />

connecting the threaded rods to the beam.<br />

3. Before connecting the supply water system(s) to<br />

the beams, contractor shall flush the piping<br />

system(s) to assure that all debris and other<br />

matter have been removed.<br />

4. Contractor shall perform connection of beams to<br />

the chilled water circuit by method specified (hard<br />

connection using sweated connection or<br />

connection using flexible hoses.<br />

5. Flexible connector hoses shall be furnished by<br />

others (optionally by the manufacturer). Hoses<br />

shall be twenty four (24) inches in length and<br />

suitable for operation with a bend radius as small<br />

as five (5) inches. Such hoses shall be 100%<br />

tested and certified for no leakage at 500 PSI.<br />

Connector hoses shall consist of a PFTE lined<br />

hose with a wire braided jacket. The hoses shall<br />

be suitable for operation in an environment<br />

between -40 and 200˚F, rated for a least 300 PSI<br />

and tested for leakage at a minimum pressure of<br />

360 PSI. Contractor shall assure that the chilled<br />

water supplying the beams has been properly<br />

treated in accordance to BSRIA publication AG<br />

2/93.<br />

6. No power or direct control connections shall be<br />

required for the operation of the chilled beam.<br />

3.03 Cleaning and Protection<br />

1. Protect units before, during and after installation.<br />

Damaged material due to improper site protection<br />

shall be cause for rejection.<br />

2. Clean equipment, repair damaged finishes as<br />

required to restore beams to as-new appearance.<br />

PART 3- EXECUTION<br />

3.02 Installation<br />

1. Coordinate the size, tagging and capacity of the<br />

beams to their proper location.<br />

2. (RECOMMENDED INSTALLATION<br />

PROCEDURE) <strong>Chilled</strong> beams up to six feet in<br />

length shall be independently suspended from<br />

the structure above by a four (4) threaded rods of<br />

⅜” diameter (provided by the installing<br />

contractor). For beams beyond six feet in length,<br />

six (6) threaded rods of ⅜” diameter. The upper<br />

end of the rods shall be suspended from strut<br />

channels that are a) mounted perpendicular to<br />

the beam length and b) at least four inches wider<br />

than the beam to facilitate relocation of the<br />

threaded rods along their length. The rods shall<br />

be fixed to factory mounting brackets on the<br />

beam that allow repositioning (at least four<br />

inches) along its length. The beam shall then be<br />

positioned above the acoustical ceiling grid and<br />

63


Specification DID620<br />

DID620 Series Active <strong>Chilled</strong> <strong>Beam</strong>s<br />

PART 1- GENERAL<br />

1.01 Summary<br />

This section describes the active chilled<br />

beams.<br />

1.02 Submittals<br />

Submit product data for all items complete with the<br />

following information:<br />

1. Operating weights and dimensions of all unit<br />

assemblies.<br />

2. Performance data, including sensible and latent<br />

cooling capacities, nozzle types, primary and total<br />

supply (primary plus induced) airflow rates,<br />

chilled (and where applicable hot) water flow<br />

rates, noise levels in octave bands, air and water<br />

side pressure losses and maximum discharge air<br />

throw values.<br />

3. Construction details including manufacturers<br />

recommendations for installation, mounting and<br />

connection.<br />

PART 2- PRODUCTS<br />

2.01 General<br />

Materials and products required for the work of this<br />

section shall not contain asbestos, polychlorinated<br />

biphenyls (PCB) or other hazardous materials<br />

identified by the engineer or owner.<br />

Approved Manufacturers:<br />

These specifications set forth the minimum<br />

requirements for the active chilled beams to be<br />

accepted for this project. Products provided by the<br />

following manufacturers will be deemed acceptable<br />

provided they meet all of the construction and<br />

performance requirements of this specification:<br />

1. <strong>TROX</strong><br />

2.02 <strong>Design</strong><br />

1. Furnish and install <strong>TROX</strong> DID621 (1 slot) and/or<br />

DID622 (2 slot) series single slot active chilled<br />

beams of sizes and capacities as indicated on the<br />

drawings and within the mechanical equipment<br />

schedules. The quantity and length of the beams<br />

shall be as shown on the drawings, without<br />

EXCEPTION. The beams shall be constructed<br />

and delivered to the job site as single units.<br />

2. The face of the beam shall consist of a room air<br />

induction section of 50% free area perforated<br />

steel flanked by two linear supply slots. The<br />

entire visible face section shall be finished in<br />

white powder coat paint or as specified by the<br />

architect. All visible internal surfaces shall be flat<br />

black.<br />

3. <strong>Beam</strong>s shall be provided with side and end<br />

details which will allow its integration into the<br />

applicable (nominal 24 inch wide) acoustical<br />

ceiling grid as specified by the architect. <strong>Beam</strong>s<br />

used for exposed mounting applications shall<br />

include factory mounted Coanda plates to assure<br />

a horizontal discharge of the supply air.<br />

4. The beams shall consist of a minimum 20 gauge<br />

galvanized steel housing encasing the integral<br />

sensible cooling coil and a plenum feeing a series<br />

of induction nozzles. A side (model 622-US-H) or<br />

top (model 622-US-V) mounted connection spigot<br />

shall afford the connection of a six (6) inch<br />

diameter supply air. The overall height of beams<br />

shall not exceed 8⅞ inches.<br />

5. Each beam shall be provided with a pressure tap<br />

that may be used to measure the pressure<br />

differential between the primary air plenum and<br />

the room. Airflow calibration charts that relate this<br />

pressure differential reading with the primary and<br />

beam supply airflow rates shall be furnished with<br />

the beams.<br />

6. (OPTIONAL) Each beam shall be furnished with<br />

a separate volume flow limiter for mounting in the<br />

primary air duct by the installing contractor. This<br />

device shall allow field adjustment of a maximum<br />

primary air flow rate that is maintained<br />

independent of any static pressure changes in<br />

the inlet ductwork. The volume flow limiter shall<br />

add no more than 0.20 inches H2O pressure drop<br />

to the primary air delivery system and shall not<br />

require any control or power connections.<br />

7. <strong>Beam</strong>s shall be provided with connections for<br />

either 2 or 4 pipe operation as indicated on plans<br />

and schedules. Four pipe configurations shall<br />

require separate supply and return connections<br />

for chilled and hot water. The coils shall be<br />

mounted horizontally and shall be manufactured<br />

with seamless copper tubing (½” outside<br />

diameter) with minimum .025 inch wall thickness<br />

mechanically fixed to aluminum fins. The<br />

aluminum fins shall be limited to no more than ten<br />

(10) fins per inch. The beam shall have a working<br />

pressure of at least 300 PSI, be factory tested for<br />

leakage at a minimum pressure of 360 PSI. Each<br />

chilled beam shall be provided with factory<br />

integrated drain fittings. Unless otherwise<br />

specified, coil connections shall be bare copper<br />

for field sweating to the water supply circuit.<br />

Connections shall face upwards, be located near<br />

the left end of the beam (when viewing into the<br />

primary air connection<br />

64


Specification DID620<br />

8. (OPTIONAL) The chilled water coil shall be<br />

provided with NPT male threaded fittings where<br />

specified. These fittings must be suitable for field<br />

connection to a similar NPT female flexible hose<br />

spigot and shall be at least 1½” long to facilitate<br />

field connection (by others).<br />

9. <strong>Beam</strong>s shall be delivered clean, flushed and<br />

capped to prevent ingress of dirt<br />

2.03 Performance<br />

1. All performance shall be in compliance with that<br />

shown on the equipment schedule. Acoustical<br />

testing shall have been performed in accordance<br />

with ISO 3741.<br />

2. Coils shall be rated in accordance with ARI<br />

Standard 410, but their cooling and heating<br />

capacities shall be established in accordance to<br />

European Standard EN15116 for the specific<br />

application on the inlet side of the submitted<br />

chilled beam. Evidence of this testing must be<br />

included in the submittal.<br />

3.<br />

4. Primary airflow rates shall not result in supply<br />

(primary plus induced) airflow rates in excess of<br />

80 CFM per linear foot of beam.<br />

5. <strong>Chilled</strong> water flow rates to the beams shall be<br />

limited to that which results in a maximum ten<br />

(10) foot head loss. Water flow velocities through<br />

the beam shall not exceed 4 FPS.<br />

4. Contractor shall perform connection of beams to<br />

the chilled water circuit by method specified (hard<br />

connection using sweated connection or<br />

connection using flexible hoses.<br />

5. Flexible connector hoses shall be furnished by<br />

others (optionally by the manufacturer). Hoses<br />

shall be twenty four (24) inches in length and<br />

suitable for operation with a bend radius as small<br />

as five (5) inches. Such hoses shall be 100%<br />

tested and certified for no leakage at 500 PSI.<br />

Connector hoses shall consist of a PFTE lined<br />

hose with a wire braided jacket. The hoses shall<br />

be suitable for operation in an environment<br />

between -40 and 200˚F, rated for a least 300 PSI<br />

and tested for leakage at a minimum pressure of<br />

360 PSI. Contractor shall assure that the chilled<br />

water supplying the beams has been properly<br />

treated in accordance to BSRIA publication AG<br />

2/93.<br />

6. No power or direct control connections shall be<br />

required for the operation of the chilled beam.<br />

3.03 Cleaning and Protection<br />

1. Protect units before, during and after installation.<br />

Damaged material due to improper site protection<br />

shall be cause for rejection.<br />

2. Clean equipment, repair damaged finishes as<br />

required to restore beams to as-new appearance.<br />

PART 3- EXECUTION<br />

3.02 Installation<br />

1. Coordinate the size, tagging and capacity of the<br />

beams to their proper location.<br />

2. (RECOMMENDED INSTALLATION<br />

PROCEDURE) <strong>Chilled</strong> beams up to six feet in<br />

length shall be independently suspended from<br />

the structure above by a four (4) threaded rods of<br />

⅜” diameter (provided by the installing<br />

contractor). For beams beyond six feet in length,<br />

six (6) threaded rods of ⅜” diameter. The upper<br />

end of the rods shall be suspended from strut<br />

channels that are a) mounted perpendicular to<br />

the beam length and b) at least four inches wider<br />

than the beam to facilitate relocation of the<br />

threaded rods along their length. The rods shall<br />

be fixed to factory mounting slots on the beam<br />

that allow repositioning (at least four inches)<br />

along its length. The beam shall then be<br />

positioned above the acoustical ceiling grid and<br />

lowered into the grid module by adjusting the nuts<br />

connecting the threaded rods to the beam.<br />

3. Before connecting the supply water system(s) to<br />

the beams, contractor shall flush the piping<br />

system(s) to assure that all debris and other<br />

matter have been removed.<br />

65


Specification DID300<br />

DID300 Series Active <strong>Chilled</strong> <strong>Beam</strong>s<br />

PART 1- GENERAL<br />

1.01 Summary<br />

This section describes the active chilled beams.<br />

1.02 Submittals<br />

Submit product data for all items complete with the<br />

following information:<br />

1. Operating weights and dimensions of all unit<br />

assemblies.<br />

2. Performance data, including sensible and latent<br />

cooling capacities, nozzle types, primary and total<br />

supply (primary plus induced) airflow rates,<br />

chilled (and where applicable hot) water flow<br />

rates, noise levels in octave bands, air and water<br />

side pressure losses and maximum discharge air<br />

throw values.<br />

3. Construction details including manufacturers<br />

recommendations for installation, mounting and<br />

connection.<br />

PART 2- PRODUCTS<br />

2.01 General<br />

Materials and products required for the work of this<br />

section shall not contain asbestos, polychlorinated<br />

biphenyls (PCB) or other hazardous materials<br />

identified by the engineer or owner.<br />

Approved Manufacturers:<br />

These specifications set forth the minimum<br />

requirements for the active chilled beams to be<br />

accepted for this project. Products provided by the<br />

following manufacturers will be deemed acceptable<br />

provided they meet all of the construction and<br />

performance requirements of this specification:<br />

1. <strong>TROX</strong><br />

2.02 <strong>Design</strong><br />

1. Furnish and install <strong>TROX</strong> DID301 (single slot)<br />

and/or DID302 (two slot) series active chilled<br />

beams of sizes and capacities as indicated on the<br />

drawings and within the mechanical equipment<br />

schedules. The quantity and length of the beams<br />

shall be as shown on the drawings, without<br />

EXCEPTION. The beams shall be constructed<br />

and delivered to the job site as single units.<br />

2. The face of the beam shall consist of a room air<br />

induction section of 50% free area perforated<br />

steel flanked by two linear supply slots (or an<br />

OPTIONAL linear bar grille with a 70% free area<br />

face). The entire visible face section shall be<br />

finished in white powder coat paint or as specified<br />

by the architect. All visible internal surfaces shall<br />

be flat black.<br />

3. <strong>Beam</strong>s shall be provided with side and end<br />

details which will allow its integration into the<br />

applicable (nominal 12 inch wide) acoustical<br />

ceiling grid as specified by the architect. <strong>Beam</strong>s<br />

used for exposed mounting applications shall<br />

include factory mounted “Coanda” plates to<br />

assure a horizontal discharge of the supply air.<br />

4. The beams shall consist of a minimum 20 gauge<br />

galvanized steel housing encasing the integral<br />

sensible cooling coil and a plenum feeing a series<br />

of induction nozzles. A side entry primary air duct<br />

connection shall be provided with a nominal five<br />

(5) or six (6) inch round spigot. The overall height<br />

of the beams shall not exceed 9½”<br />

5. <strong>Beam</strong>s shall incorporate provisions for<br />

measurement of their primary airflow rate. The<br />

measurement location must be accessible from<br />

the face of the beam and require a single<br />

pressure differential measurement. Airflow<br />

calibration charts that relate the measurement to<br />

the primary airflow rate shall be furnished with the<br />

beams.<br />

6. (OPTIONAL) Each beam shall be furnished with<br />

a separate volume flow limiter for mounting in the<br />

primary air duct by the installing contractor. This<br />

device shall allow field adjustment of a maximum<br />

primary air flow rate that is maintained<br />

independent of any static pressure changes in<br />

the inlet ductwork. The volume flow limiter shall<br />

add no more than 0.20 inches H 2 O pressure drop<br />

to the primary air delivery system and shall not<br />

require any control or power connections.<br />

7. When furnished in a 2 pipe configuration, the<br />

assembly shall contain two (2) separate chilled<br />

water coils with single supply and return<br />

connections. Four pipe connections shall require<br />

separate connections for their chilled and hot<br />

water supply. The coils shall be mounted<br />

vertically and (non-piped) condensate trays shall<br />

be furnished directly beneath them. The coils<br />

shall be manufactured with seamless copper<br />

tubing (½” outside diameter) with minimum .025<br />

inch wall thickness mechanically fixed to<br />

aluminum fins. The aluminum fins shall be limited<br />

to no more than ten (10) fins per inch. The beam<br />

shall have a working pressure of at least 300 PSI,<br />

be factory tested for leakage at a minimum<br />

pressure of 360 PSI. Each chilled beam shall be<br />

provided with factory integrated drain fittings.<br />

Unless otherwise specified, coil connections shall<br />

be ½” O.D. bare<br />

66


Specification DID300<br />

copper for field sweating to the water supply circuit.<br />

Connections to 2 pipe coils shall extend from left end<br />

of the beam (when viewing into the primary air connection<br />

spigot) and shall be at least 1½” long to facilitate<br />

field connection (by others).<br />

8. (OPTIONAL) The chilled water coil shall be provided<br />

with NPT male threaded fittings where<br />

specified. These fittings must be suitable for field<br />

connection to a similar NPT female flexible hose.<br />

9. <strong>Beam</strong>s shall be delivered clean, flushed and<br />

capped to prevent ingress of dirt.<br />

2.03 Performance<br />

All performance shall be in compliance with that<br />

shown on the equipment schedule. Acoustical testing<br />

shall have been performed in accordance with ISO<br />

3741.<br />

Coils shall be rated in accordance with ARI Standard<br />

410, but their cooling and heating capacities shall be<br />

established in accordance to European Standard<br />

EN15116 for the specific application on the inlet side<br />

of the submitted chilled beam. Evidence of this testing<br />

must be included in the submittal.<br />

Primary airflow rates shall not result in supply (primary<br />

plus induced) airflow rates in excess of 40 CFM per<br />

linear foot of beam.<br />

<strong>Chilled</strong> water flow rates to the beams shall be limited<br />

to that which results in a maximum ten (10) foot head<br />

loss. Water flow velocities through the beam shall not<br />

exceed 4 FPS.<br />

3. Before connecting the supply water system(s) to<br />

the beams, contractor shall flush the piping system(s)<br />

to assure that all debris and other matter<br />

have been removed.<br />

4. Contractor shall perform connection of beams to<br />

the chilled water circuit by method specified (hard<br />

connection using sweated connection or connection<br />

using flexible hoses.<br />

5. Flexible connector hoses shall be furnished by<br />

others (optionally by the manufacturer). Hoses<br />

shall be twenty four (24) inches in length and<br />

suitable for operation with a bend radius as small<br />

as five (5) inches. Such hoses shall be 100%<br />

tested and certified for no leakage at 500 PSI.<br />

Connector hoses shall consist of a PFTE lined<br />

hose with a wire braided jacket. The hoses shall<br />

be suitable for operation in an environment between<br />

-40 and 200˚F, rated for a least 300 PSI<br />

and tested for leakage at a minimum pressure of<br />

360 PSI. Contractor shall assure that the chilled<br />

water supplying the beams has been properly<br />

treated in accordance to BSRIA publication AG<br />

2/93.<br />

6. No power or direct control connections shall be<br />

required for the operation of the chilled beam.<br />

3.03 Cleaning and Protection<br />

Protect units before, during and after installation.<br />

Damaged material due to improper site protection<br />

shall be cause for rejection.<br />

Clean equipment, repair damaged finishes as required<br />

to restore beams to as-new appearance.<br />

PART 3- EXECUTION<br />

3.02 Installation<br />

1. Coordinate the size, tagging and capacity of the<br />

beams to their proper location.<br />

2. (RECOMMENDED INSTALLATION PROCE-<br />

DURE) <strong>Chilled</strong> beams up to six feet in length<br />

shall be independently suspended from the structure<br />

above by a four (4) threaded rods of ⅜” diameter<br />

(provided by the installing contractor). For<br />

beams beyond six feet in length, six (6) threaded<br />

rods of ⅜” diameter. The upper end of the rods<br />

shall be suspended from strut channels that are<br />

a) mounted perpendicular to the beam length and<br />

b) at least four inches wider than the beam to<br />

facilitate relocation of the threaded rods along<br />

their length. The rods shall be fixed to factory<br />

mounting brackets on the beam that allow repositioning<br />

(at least four inches) along its length. The<br />

beam shall then be positioned above the acoustical<br />

ceiling grid and lowered into the grid module<br />

by adjusting the nuts connecting the threaded<br />

rods to the beam.<br />

67


In North America<br />

Trox USA, Inc.<br />

4305 Settingdown Circle<br />

Cumming<br />

Georgia<br />

USA 30028<br />

Telephone: (770) 569-1433<br />

Telefax: (770) 569-1435<br />

e-mail: trox@troxusa.com<br />

www.troxusa.com<br />

Head Office & Research Centers<br />

Gebrüder Trox GmbH<br />

Postfach 10 12 63<br />

D-47504 Neukirchen-Vluyn<br />

Telephone 49 28 45/2 02-0<br />

Telefax 49 28 45/2 02-2 65<br />

www.troxtechnik.com<br />

E-mail: trox@troxtechnik.de<br />

Australia<br />

Trox (Australia) Pty Ltd.<br />

Austria<br />

Trox Austria GmbH<br />

Belgium<br />

S.A. Trox Belgium N.V.<br />

Brazil<br />

Trox do Brasil Ltda.<br />

China<br />

Trox Air Conditioning<br />

Components (Suzhou)<br />

Co., Ltd.<br />

Croatia<br />

Trox Austria GmbH<br />

Czech Republic<br />

Trox Austria GmbH<br />

Denmark<br />

Trox Danmark A/S<br />

Dubai<br />

Trox (U.K.) Ltd.<br />

France<br />

Trox France Sarl<br />

Germany<br />

Hesco Deutschland GmbH<br />

FSL FassadenSystemLüftung<br />

GmbH & Co. KG<br />

Great Britain<br />

Trox (U.K.) Ltd.<br />

Hong Kong<br />

Trox Hong Kong Ltd.<br />

Hungary<br />

Trox Austria GmbH<br />

Italy<br />

Trox Italiana S.p.A.<br />

Malaysia<br />

Trox (Malaysia) Sdn. Bhd.<br />

Norway<br />

Auranor Group AS<br />

Poland<br />

Trox Austria GmbH<br />

South Africa<br />

Trox (South Africa)<br />

(Pty) Ltd.<br />

Spain<br />

Trox Española, S.A.<br />

Switzerland<br />

Trox Hesco<br />

(Schweiz) AG<br />

Yugoslavia<br />

Trox Austria GmbH<br />

68<br />

<strong>Design</strong> changes reserved · All rights reserved © Gebrüder Trox GmbH (01/2009)

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!