Analogue instruments - Ulrichmatterag.ch
Analogue instruments - Ulrichmatterag.ch
Analogue instruments - Ulrichmatterag.ch
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
<strong>Analogue</strong> <strong>instruments</strong><br />
Induction<br />
Phase-meters<br />
<strong>Analogue</strong> indicator to measure cos<br />
Description<br />
}}<br />
Does not need an auxiliary power supply<br />
}}<br />
DIN box with dimensions 96 and 144.<br />
}}<br />
Class 1.5<br />
}}<br />
Balanced and unbalanced single and<br />
three-phase circuits.<br />
}}<br />
4 quadrants<br />
Features<br />
Voltage circuit<br />
PIC A / PIC B<br />
PIC E<br />
Consumption 5 V·A / 20 mA 15 mA<br />
Frequency<br />
49.5 ... 50.5 Hz<br />
4 T - 5T<br />
59.4 ... 60.6 Hz<br />
54 ... 66 Hz<br />
Overloads<br />
1.2 U n<br />
permanent<br />
2 U n<br />
during 5 s<br />
Application<br />
Current circuit<br />
Nominal current<br />
... 5 A<br />
Measurement of cos in balanced or unbalanced<br />
single and three-phase circuits.<br />
Consumption 4 V·A 2.5 V·A<br />
Frequency<br />
20 ... 100 Hz<br />
1.2 I n<br />
permanent<br />
5 I<br />
Overloads<br />
n<br />
during 30 s<br />
10 I n<br />
during 5 s<br />
40 I n<br />
during 1 s<br />
Accuracy<br />
± 1.5 % FS<br />
Ambient conditions<br />
Operating temperature +10 ... +30 ºC<br />
Limit temperature - 25 ... +40 ºC<br />
Altitude<br />
Dimensions<br />
Weight<br />
Type of box<br />
Degree of protection:<br />
Front panel<br />
Terminals<br />
Insulation voltage<br />
2000 m<br />
See the following table<br />
See the following table<br />
panel<br />
IP 52<br />
IP 00<br />
2 kV, during 1 min, between the me<strong>ch</strong>anism and the box<br />
Standards BS 89, EN 60051, IEC 144, UL 94, DIN 43780, IEC 51, UNE 21318<br />
M1-46