Technical data, Plug-in Rectifiers<br />

Type<br />

max. quantity per 19“ level<br />

output power [W]<br />

PDT<br />

6<br />

400<br />

PDT<br />

6<br />

650<br />

PDT<br />

4<br />

800<br />

PDT<br />

4<br />

1800<br />

PDD<br />

3<br />

3000<br />

PDE<br />

1<br />

7200<br />

PDE<br />

1<br />

15000<br />

Input voltage range<br />

Input current<br />

Frequency<br />

Power factor<br />

Output current<br />

at 24 V<br />

at 48 V<br />

at 60 V<br />

Output voltages<br />

Boost voltage<br />

Float voltage<br />

Direct supply<br />

Battery check<br />

[V]<br />

[A]<br />

[Hz]<br />

[A]<br />

[A]<br />

[A]<br />

[V/c]<br />

[V/c]<br />

[V/c]<br />

[V/c]<br />

singlephase 196–264 I threephase 340–460<br />

2,1 I 3,4 I 4,2 I 8,5 I 14 I 13,7 I 22<br />

47–63<br />

0,98 I 0,93<br />

– I – I 15 I 50 I 75 I 200 I –<br />

7,5 I 12 I 15 I 33 I 50 I 125 I 225<br />

– I 10 I 12 I 27 I 40 I 100 I 200<br />

externally adjustable<br />

2,4<br />

2,23<br />

2,05<br />

1,8<br />

Stability U output<br />

Static [%]<br />

Dynamic load 10-100-10 [%]<br />

(di/dt>200µs)<br />

Response time<br />

[ms]<br />

Efficiency<br />

Characteristic<br />

Noise voltage<br />

[mV]<br />

Radio interference<br />

Protection class<br />

Safety<br />

Protection<br />

Cooling<br />

Ambient temperature<br />

[°C]<br />

Installation height<br />

[m]<br />

Moisture class<br />

Current measurement<br />

Voltage measurement<br />

Indications:/front panel<br />

Mains<br />

DC voltage high<br />

Operation<br />

Alarm<br />

Fan failure<br />

Common alarm/change-over contact<br />

Connections:<br />

Main input<br />

Output<br />

Alarms<br />

Dimensions<br />

Height (front panel)<br />

[mm]<br />

Width<br />

[mm]<br />

Depth<br />

[mm]<br />

Weight<br />

[kg]<br />

±1<br />

±5<br />

< 5<br />

90 I 91 I 94<br />

IU<br />

1 for 24 V units, 2 for 48/60 V units<br />

EN 55022 class B<br />

1-EN 60950<br />

EN 60950<br />

IP 20<br />

convection<br />

I fan behind the front panel, temperature controlled<br />

0 – 40<br />

up to 2000 m above sea level<br />

F DIN 40040<br />

– I test sockets*<br />

– I – I test sockets*<br />

yellow LED<br />

red LED<br />

green LED<br />

red LED<br />

I<br />

red LED<br />

fault<br />

plug I terminals 4 mm 2<br />

plug I M8 I M12<br />

plug I plugterminal<br />

267 I 267 I 267 I 267 I 267 I 177 I 267<br />

71 I 71 I 107 I 107 I 146 I 485 I 485<br />

250 I 250 I 250 I 350 I 440 I 400 I 400<br />

3,0 I 3,6 I 5,5 I 9,5 I 12,5 I 26,5 I 40,0<br />

* digital display: standard in PDE 7200 and PDE 15000<br />

in PDT 800, PDT 1800 and PDD 3000 only in version with MCU interface