General<br />

With the increasing demand for power systems in<br />

the telecommunication sector, and the need for<br />

more efficient use of operating and maintenance<br />

staff, Benning have produced a range of system<br />

monitoring. The Benning MCU 500, MCU 1000 and<br />

MCU 2000+ offer the user a solution depending<br />

on the customer requirements.<br />

BLT 150 and BLT 400 power systems are fitted<br />

with MCU 500 (Optional MCU 1000) monitoring<br />

system.<br />

By means of local indication (13 off LED´s) and<br />

numerical display, the system status can be<br />

quickly assessed.<br />

The MCU 1000 additionally offers direct communication,<br />

via a RS 485 interface, with the rectifier<br />

modules.<br />

As an optional extra the MCU 1000 may be fitted<br />

with a relay box having 8 volt free contact.<br />

Remote Monitoring System MCU 500, 1000 und 2000+<br />

Float<br />

Boost<br />

Battery test<br />

Battery test negative<br />

Rectifier failure<br />

Mains failure<br />

Fault U < 2,1 V/C<br />

Battery disch. U < 1,9 V/C<br />

LVD tripped<br />

Battery fuse tripped<br />

Load fuse tripped<br />

Battery fault<br />

(reserve)<br />

LED test/reset<br />

MCU 500<br />

DC-Power-Supply<br />

Contacts<br />

(1)<br />

The BLT 2500/5000 has the MCU 2000+ monitoring<br />

fitted as standard.<br />

Both MCU 1000 and MCU 2000+ monitoring<br />

systems have the facility to control and monitor<br />

the power system via the public telephone<br />

network.<br />

As an option, the MCU 1000 and MCU 2000+ signals<br />

can be transmitted via modem to a central<br />

control station.<br />

Float<br />

Boost<br />

Battery test<br />

Battery test negative<br />

Rectifier failure<br />

Mains failure<br />

Fault U < 2,1 V/C<br />

Battery disch. U < 1,9 V/C<br />

LVD tripped<br />

Battery fuse tripped<br />

Load fuse tripped<br />

Battery fault<br />

(reserve)<br />

LED test/reset<br />

DC-Power-Supply<br />

Contacts<br />

(1)<br />

RS 485<br />

(2)<br />

Using a PC and dedicated monitoring software,<br />

information can be sent and received by the<br />

customer based in the control station.<br />

MCU 1000<br />

Rectifier with (2)<br />

or without (1)<br />

interface<br />

The MCU 2000+ provides a large range of supervisory<br />

functions, and enables easy monitoring<br />

and controlling of the power supply system.<br />

Airport München, Benning - Power to Communikation<br />

Communication with the rectifiers is via an RS<br />

485 interface. Options include 8 additional volt<br />

free alarm contacts, 24 external digital inputs and<br />

15 measurement channels.<br />

Float<br />

Boost<br />

Battery test<br />

Battery test negative<br />

Rectifier failure<br />

Mains failure<br />

Fault U < 2,1 V/C<br />

Battery disch. U < 1,9 V/C<br />

LVD tripped<br />

Battery fuse tripped<br />

Load fuse tripped<br />

Battery fault<br />

(reserve)<br />

LED test/reset<br />

DC-Power-Supply<br />

RS 485<br />

(2)<br />

MCU 2000 +