Technical data TEBEVERT<br />
Static by-pass EUE<br />
Input DC voltage V see type table<br />
Permissible deviation % + 20, -15<br />
Ripple of the input voltage % max. 5 rms<br />
Reverse smoothing mV 2<br />
Nominal power VA see type table<br />
Output voltage V 230<br />
Static deviation % ± 5<br />
Frequency Hz 50<br />
Frequency stability % ± 0,1 (crystal controlled)<br />
Mains control of frequency % ± 3<br />
Power factor range<br />
0,7 ind. to 0,8 cap.<br />
Voltage form<br />
sine-wave<br />
Distortion factor % < 3 (at linear load)<br />
Overload capacity<br />
2xI nom for 1 sec.,<br />
cut-off after 40 sec.<br />
Crest factor load 2,5 : 1<br />
Radio interference EN 55022<br />
Efficiency % 80–85<br />
Ambient temperature °C +5 to +40<br />
Installation height m up to 1000 above sea level<br />
Moisture class<br />
F<br />
Cooling<br />
temperature-controlled<br />
forced ventilation<br />
Protection class 1 - EN 60950<br />
Protection<br />
IP 20 (without terminals)<br />
Painting (front panel) RAL 7032<br />
Indications<br />
Output current<br />
Output voltage present<br />
Fault<br />
Overload<br />
Mains synchronization<br />
Parallel operation<br />
Pot.-free contact<br />
bargraph<br />
LED<br />
LED<br />
LED<br />
LED<br />
LED<br />
fault (delay approx. 10 sec.)<br />
Loads of systems with EUE are<br />
permanently supplied via the inverter.<br />
The voltage gap, arising in the event of<br />
failure in the inverter or overload, is<br />
< 1,5 ms, so even sensitive electronic<br />
loads can be supplied without any<br />
problems. The overload behaviour is<br />
approx. 5 x I rated for 100 ms, therefore<br />
loads with high inrush currents can<br />
also be connected.<br />
Dimensions EUE (Static By-Pass)<br />
246,5<br />
483<br />
466<br />
3 U = 133,4<br />
Connections<br />
AC side<br />
DC side<br />
Alarm<br />
Remote control<br />
Earthing bolt<br />
EUE/parallel operation<br />
Options<br />
Dimensions<br />
plugs / terminals<br />
plugs / terminals<br />
plugs<br />
M6<br />
connector<br />
SUE operation<br />
EUE operation<br />
parallel operation<br />
see type table<br />
444<br />
Type table Tebevert<br />
Type<br />
Input<br />
voltage<br />
Input current at<br />
cos ϕ 0,8 a. Nominal<br />
input voltage<br />
Output<br />
power<br />
Dimensions<br />
H x W x D [mm]<br />
G 24 E 230/ 6,5/2rfg-PWE 24 V 57A 1500VA 177,0 x 483 x 390 18,5<br />
G 48 E 230/ 4,4/2rfg-PWE 48 V 20A 1000VA 133,4 x 483 x 256 10,5<br />
G 48 E 230/10,9/2rfg-PWE 48 V 50A 2500VA 177,0 x 483 x 390 18,5<br />
G 48 E 230/21,7/2rfg-PWE 48 V 92A 5000VA 177,0 x 483 x 450 28,0<br />
G 60 E 230/ 4,4/2rfg-PWE 60 V 16A 1000VA 133,4 x 483 x 256 10,5<br />
G 60 E 230/10,9/2rfg-PWE 60 V 40A 2500VA 177,0 x 483 x 390 18,5<br />
G 60 E 230/21,7/2rfg-PWE 60 V 74A 5000VA 177,0 x 483 x 450 28,0<br />
Weight [kg]<br />
Type table EUE<br />
Type<br />
Nominal power<br />
[VA]<br />
Dimensions<br />
H x W x D [mm]<br />
EUE E 230/ 32,60/2 - 24E 7500 133,4 x 483 x 300<br />
EUE E 230/ 21,74/2 - 48E (60E) 5000 133,4 x 483 x 300<br />
EUE E 230/ 54,35/2 - 48E (60E) 12500 133,4 x 483 x 300<br />
EUE E 230/ 108,7/2 - 48E (60E) 25000 133,4 x 483 x 300