Cooling Capacity Data - RTL 60 - Nominal Airflow 11500 m 3 /h<br />
INDOOR COIL ENTERING AIR TEMPERATURE (°C)<br />
OUTDOOR AIR TEMPERATURE (°C)<br />
20 25 30 35 40 45<br />
Wet bulb temperature = 15 °C<br />
Total cooling capacity (kW) 59.6 57.3 55.1 52.9 50.6 48.4<br />
Total power input (kW) 15.3 16.2 17.1 17.9 18.8 19.7<br />
21 °C<br />
39.9 40.7 41.6 42.4 43.3 44.1<br />
23 °C 44.9 45.8 46.8 47.7 48.7 48.4<br />
Dry bulb temperature<br />
25 °C Sensible cooling<br />
49.8 57.1 55.1 52.9 50.6 48.4<br />
27 °C capacity (kW)<br />
59.6 57.3 55.1 52.9 50.6 48.4<br />
29 °C 59.6 57.3 55.1 52.9 50.6 48.4<br />
31 °C 59.6 57.3 55.1 52.9 50.6 48.4<br />
Wet bulb temperature = 17 °C<br />
Total cooling capacity (kW) 63.3 61.0 58.6 56.3 54.0 51.6<br />
Total power input (kW) 15.4 16.3 17.2 18.1 19.0 19.9<br />
21 °C<br />
38.4 39.3 40.1 40.9 41.7 42.5<br />
23 °C 43.7 44.7 45.6 46.5 47.5 48.4<br />
Dry bulb temperature<br />
25 °C Sensible cooling<br />
49.0 50.1 51.1 52.2 53.2 51.1<br />
27 °C capacity (kW)<br />
60.2 59.6 58.6 56.3 54.0 51.6<br />
29 °C 62.7 61.0 58.6 56.3 54.0 51.6<br />
31 °C 63.3 61.0 58.6 56.3 54.0 51.6<br />
Wet bulb temperature = 19 °C<br />
Total cooling capacity (kW) 67.1 64.6 62.2 59.8 57.4 55.0<br />
Total power input (kW) 15.6 16.6 17.5 18.4 19.3 20.2<br />
21 °C<br />
30.9 31.6 32.2 32.9 33.5 34.2<br />
23 °C 36.5 37.3 38.1 38.9 39.6 40.4<br />
Dry bulb temperature<br />
25 °C Sensible cooling<br />
42.2 43.1 44.0 44.9 45.7 46.6<br />
27 °C capacity (kW)<br />
47.8 48.8 49.8 50.8 51.8 52.9<br />
29 °C 53.4 54.5 55.7 56.8 57.4 55.0<br />
31 °C 65.2 64.6 62.2 59.8 57.4 55.0<br />
Wet bulb temperature = 21 °C<br />
Total cooling capacity (kW) 71.0 68.5 66.0 63.4 60.9 58.3<br />
Total power input (kW) 16.3 17.3 18.2 19.2 20.1 21.1<br />
23 °C<br />
28.2 28.8 29.4 30.0 30.6 31.2<br />
25 °C 34.2 34.9 35.6 36.4 37.1 37.8<br />
Dry bulb temperature<br />
27 °C Sensible cooling<br />
40.2 41.0 41.9 42.7 43.6 44.4<br />
29 °C capacity (kW)<br />
46.1 47.1 48.1 49.1 50.0 51.0<br />
31 °C 52.1 53.2 54.3 55.4 56.5 57.6<br />
33 °C 58.0 59.3 66.1 64.8 63.1 61.1<br />
Wet bulb temperature = 23 °C<br />
Total cooling capacity (kW) 75.0 72.4 69.7 67.1 64.4 61.7<br />
Total power input (kW) 17.1 18.1 19.1 20.0 21.0 22.0<br />
25 °C<br />
25.0 25.6 26.1 26.6 27.2 27.7<br />
Dry bulb temperature<br />
27 °C<br />
Sensible cooling<br />
29 °C 37.7 38.5 39.3 40.1 40.9 41.7<br />
31 °C<br />
capacity (kW)<br />
44.0 44.9 45.8 46.8 47.7 48.6<br />
31.3 32.0 32.7 33.3 34.0 34.7<br />
33 °C 50.3 51.3 52.4 53.5 54.5 55.6<br />
17