Specification Guide (continued)<br />
special features<br />
Economizer<br />
The rooftop shall be factory assembled with an ECONOMIZER. The<br />
economizer shall have two counteracting dampers linked together to an<br />
actuator, modulating proportionally the volume of outdoor and return air from<br />
0 to 100%.<br />
The blades shall be constructed of galvanized steel with transmission gearwheel.<br />
Retractable weather hood with bird screen shall protect the outdoor<br />
air damper.<br />
Economizer shall have one of the following controls:<br />
• Sensible control using temperature difference (RAT: Return Air<br />
Temperature & OAT : Outdoor Air Temperature).<br />
• Enthalpy control using temperature and humidity sensor to define<br />
enthalpy difference (RAH & OAH).<br />
• Quality control using air quality sensor placed on the return to ensure the<br />
necessary ventilation with more outdoor air to dilute the contaminants<br />
and maintain supply air quality.<br />
Exhaust air blower<br />
An exhaust air blower shall be provided with unit when economizer is fitted.<br />
The exhausted air shall not be short-circuited with the outdoor air intake. The<br />
volume of rejected air shall be at least 25% of the nominal air flow of the unit.<br />
Hot water heating<br />
The hot water coil shall be supplied with a modulating 3-way valve. The coil<br />
shall be mounted on a sliding rail down stream of the DX indoor coil. The<br />
hot water coil shall have the same face area as the indoor coil. A freeze limit<br />
thermostat shall be factory fitted and open the valve, close the outdoor air<br />
damper.<br />
Electric heat<br />
The rooftop shall be factory supplied with an electric heater placed at the<br />
blower discharge in a non-flammable compartment to protect the motor<br />
against radiated heat. The electric elements shall be of stainless steel and<br />
provide 2-stage heats. Manual and automatic reset safety thermostats shall<br />
be factory fitted and wired to the control devices.<br />