Specification Guide (continued)<br />

special features<br />

Economizer<br />

The rooftop shall be factory assembled with an ECONOMIZER. The<br />

economizer shall have two counteracting dampers linked together to an<br />

actuator, modulating proportionally the volume of outdoor and return air from<br />

0 to 100%.<br />

The blades shall be constructed of galvanized steel with transmission gearwheel.<br />

Retractable weather hood with bird screen shall protect the outdoor<br />

air damper.<br />

Economizer shall have one of the following controls:<br />

• Sensible control using temperature difference (RAT: Return Air<br />

Temperature & OAT : Outdoor Air Temperature).<br />

• Enthalpy control using temperature and humidity sensor to define<br />

enthalpy difference (RAH & OAH).<br />

• Quality control using air quality sensor placed on the return to ensure the<br />

necessary ventilation with more outdoor air to dilute the contaminants<br />

and maintain supply air quality.<br />

Exhaust air blower<br />

An exhaust air blower shall be provided with unit when economizer is fitted.<br />

The exhausted air shall not be short-circuited with the outdoor air intake. The<br />

volume of rejected air shall be at least 25% of the nominal air flow of the unit.<br />

Hot water heating<br />

The hot water coil shall be supplied with a modulating 3-way valve. The coil<br />

shall be mounted on a sliding rail down stream of the DX indoor coil. The<br />

hot water coil shall have the same face area as the indoor coil. A freeze limit<br />

thermostat shall be factory fitted and open the valve, close the outdoor air<br />

damper.<br />

Electric heat<br />

The rooftop shall be factory supplied with an electric heater placed at the<br />

blower discharge in a non-flammable compartment to protect the motor<br />

against radiated heat. The electric elements shall be of stainless steel and<br />

provide 2-stage heats. Manual and automatic reset safety thermostats shall<br />

be factory fitted and wired to the control devices.<br />