Technical Features (continued)<br />

Exhaust options :<br />

- Depression shutter<br />

- Exhaust blower<br />

RETURN AIR<br />

ROOM<br />

D2<br />

FILTER<br />

IC<br />

HWC<br />

IFAN<br />

HEAT<br />

FRESH AIR<br />

SUPPLY AIR<br />

D1<br />

Legend :<br />

D1<br />

Fresh air damper<br />

D2<br />

Return air damper<br />

IC<br />

Indoor coil<br />

OC<br />

Outdoor coil<br />

C1-2 Compressor<br />

IFAN<br />

Indoor fan, Main blower<br />

HEAT<br />

Electric<br />

HWC<br />

Hot water coil<br />

FILTER<br />

G4, F6<br />

C<br />

1 2<br />

OC1<br />

OC2<br />

C<br />

The economizer reduces the operational time of the compressors using<br />

outdoor air to satisfy the cooling or heating demand.<br />

• Outdoor air damper closed on OFF periods.<br />

• Outdoor air damper closed on start-up, morning warm-up and night-setback<br />

modes for an economic operation.<br />

The 2-damper configuration is suitable only for bottom or side return air<br />

configurations (R1 and R2).<br />

• A retractable rain hood with bird screen is factory-assembled.<br />

• Moisture eliminator on fresh air is optional.<br />

Options of exhaust air on the economizer<br />

Depression shutter (not compatible with R2)<br />

• Not compatible with the exhaust blower.<br />

• Exhaust air system with barometric damper to assist natural building depressurization<br />

when the return air damper is closed.<br />

• One-way depression shutter closed on OFF periods to avoid outdoor air<br />

intake.<br />

• Supplied with retractable rain hood to ease transportation.<br />

Exhaust blower (not compatible with R2)<br />

• Exhaust air blower kit, for mechanical removal of used air from the<br />

building, when the ducted return air is designed at pressure drop higher<br />

than the building natural leakage rate.<br />

• Used when economizer is fitted on the unit. Activated by the control when<br />

fresh air damper is 100% open.<br />

• The blower exhausts up to 25% of the nominal air volume on closed<br />

return air damper.<br />

• Installed at 90° from the outdoor air intake to avoid air short-circuiting.<br />

Manual 25% fresh air function<br />

• Factory fitted manual outdoor air system to ventilate the building with<br />

outdoor air up to 25% of nominal air volume.<br />

• Not compatible with the economizer.<br />

• Retractable rain hood to ease transportation.<br />

• Bird screen.<br />

• Non-return shutter closed during OFF periods, preventing infiltrations of<br />

outdoor air.<br />

• Moisture eliminator is optional (factory-fitted or field-installed).<br />

Hot water heating<br />

• Hot water heater available on all air flow configurations.<br />

• 1 or 2 row coil mounted on a sliding rail and covers the entire surface of<br />

the indoor DX coil. Advantages :<br />

- Low air face velocity<br />

- Low noise level<br />

- Low pressure drop (approx. 10 Pa)<br />

• Located downstream of indoor DX coil.<br />

• Access hinged door with quater-turn fasteners to ease service.<br />

• 3-way valve with copper plumbing and anti-freeze thermostat fitted at the<br />

factory inside the unit.<br />

Electric heat (S1 and S3 configurations)<br />

• Electric heaters available on down flow (S1) or front flow (S3) supply air<br />

configuration.<br />

• The electric heaters are made of smooth stainless steel tubes and placed<br />

in a slide drawer.<br />

• Two capacities are available for all models, low (CH1) and high (CH2)<br />

capacity.<br />

• Electric heaters supplied with two manual and automatic reset safety<br />

thermostats.<br />

5