Technical Features (continued)<br />
Exhaust options :<br />
- Depression shutter<br />
- Exhaust blower<br />
RETURN AIR<br />
ROOM<br />
D2<br />
FILTER<br />
IC<br />
HWC<br />
IFAN<br />
HEAT<br />
FRESH AIR<br />
SUPPLY AIR<br />
D1<br />
Legend :<br />
D1<br />
Fresh air damper<br />
D2<br />
Return air damper<br />
IC<br />
Indoor coil<br />
OC<br />
Outdoor coil<br />
C1-2 Compressor<br />
IFAN<br />
Indoor fan, Main blower<br />
HEAT<br />
Electric<br />
HWC<br />
Hot water coil<br />
FILTER<br />
G4, F6<br />
C<br />
1 2<br />
OC1<br />
OC2<br />
C<br />
The economizer reduces the operational time of the compressors using<br />
outdoor air to satisfy the cooling or heating demand.<br />
• Outdoor air damper closed on OFF periods.<br />
• Outdoor air damper closed on start-up, morning warm-up and night-setback<br />
modes for an economic operation.<br />
The 2-damper configuration is suitable only for bottom or side return air<br />
configurations (R1 and R2).<br />
• A retractable rain hood with bird screen is factory-assembled.<br />
• Moisture eliminator on fresh air is optional.<br />
Options of exhaust air on the economizer<br />
Depression shutter (not compatible with R2)<br />
• Not compatible with the exhaust blower.<br />
• Exhaust air system with barometric damper to assist natural building depressurization<br />
when the return air damper is closed.<br />
• One-way depression shutter closed on OFF periods to avoid outdoor air<br />
intake.<br />
• Supplied with retractable rain hood to ease transportation.<br />
Exhaust blower (not compatible with R2)<br />
• Exhaust air blower kit, for mechanical removal of used air from the<br />
building, when the ducted return air is designed at pressure drop higher<br />
than the building natural leakage rate.<br />
• Used when economizer is fitted on the unit. Activated by the control when<br />
fresh air damper is 100% open.<br />
• The blower exhausts up to 25% of the nominal air volume on closed<br />
return air damper.<br />
• Installed at 90° from the outdoor air intake to avoid air short-circuiting.<br />
Manual 25% fresh air function<br />
• Factory fitted manual outdoor air system to ventilate the building with<br />
outdoor air up to 25% of nominal air volume.<br />
• Not compatible with the economizer.<br />
• Retractable rain hood to ease transportation.<br />
• Bird screen.<br />
• Non-return shutter closed during OFF periods, preventing infiltrations of<br />
outdoor air.<br />
• Moisture eliminator is optional (factory-fitted or field-installed).<br />
Hot water heating<br />
• Hot water heater available on all air flow configurations.<br />
• 1 or 2 row coil mounted on a sliding rail and covers the entire surface of<br />
the indoor DX coil. Advantages :<br />
- Low air face velocity<br />
- Low noise level<br />
- Low pressure drop (approx. 10 Pa)<br />
• Located downstream of indoor DX coil.<br />
• Access hinged door with quater-turn fasteners to ease service.<br />
• 3-way valve with copper plumbing and anti-freeze thermostat fitted at the<br />
factory inside the unit.<br />
Electric heat (S1 and S3 configurations)<br />
• Electric heaters available on down flow (S1) or front flow (S3) supply air<br />
configuration.<br />
• The electric heaters are made of smooth stainless steel tubes and placed<br />
in a slide drawer.<br />
• Two capacities are available for all models, low (CH1) and high (CH2)<br />
capacity.<br />
• Electric heaters supplied with two manual and automatic reset safety<br />
thermostats.<br />
5