01.11.2014 Views

RTLH RoofTair (Airwell) - Certus

RTLH RoofTair (Airwell) - Certus

RTLH RoofTair (Airwell) - Certus

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Cooling Capacity Data - RTL 80 - Nominal Airflow 16500 m 3 /h<br />

INDOOR COIL ENTERING AIR TEMPERATURE (°C)<br />

OUTDOOR AIR TEMPERATURE (°C)<br />

20 25 30 35 40 45<br />

Wet bulb temperature = 15 °C<br />

Total cooling capacity (kW) 84.6 81.4 78.2 75.0 71.9 68.7<br />

Total power input (kW) 21.6 22.9 24.1 25.3 26.6 27.8<br />

21 °C<br />

56.6 57.9 59.1 60.3 61.5 62.7<br />

23 °C 63.7 65.1 66.4 67.8 69.1 68.7<br />

Dry bulb temperature<br />

25 °C Sensible cooling<br />

70.8 81.0 78.2 75.0 71.9 68.7<br />

27 °C capacity (kW)<br />

84.6 81.4 78.2 75.0 71.9 68.7<br />

29 °C 84.6 81.4 78.2 75.0 71.9 68.7<br />

31 °C 84.6 81.4 78.2 75.0 71.9 68.7<br />

Wet bulb temperature = 17 °C<br />

Total cooling capacity (kW) 89.9 86.6 83.3 79.9 76.6 73.3<br />

Total power input (kW) 21.8 23.1 24.3 25.6 26.8 28.1<br />

21 °C<br />

54.6 55.7 56.9 58.1 59.2 60.4<br />

23 °C 62.1 63.4 64.7 66.1 67.4 68.7<br />

Dry bulb temperature<br />

25 °C Sensible cooling<br />

69.6 71.1 72.6 74.1 75.5 72.5<br />

27 °C capacity (kW)<br />

85.4 84.6 83.2 79.9 76.6 73.3<br />

29 °C 89.0 86.6 83.3 79.9 76.6 73.3<br />

31 °C 89.9 86.6 83.3 79.9 76.6 73.3<br />

Wet bulb temperature = 19 °C<br />

Total cooling capacity (kW) 95.2 91.8 88.3 84.9 81.5 78.0<br />

Total power input (kW) 22.1 23.4 24.7 26.0 27.3 28.6<br />

21 °C<br />

43.9 44.8 45.8 46.7 47.6 48.6<br />

23 °C 51.9 53.0 54.1 55.2 56.3 57.4<br />

Dry bulb temperature<br />

25 °C Sensible cooling<br />

59.9 61.1 62.4 63.7 64.9 66.2<br />

27 °C capacity (kW)<br />

67.8 69.3 70.7 72.2 73.6 75.1<br />

29 °C 75.8 77.4 79.0 80.7 81.5 78.0<br />

31 °C 92.5 91.7 88.3 84.9 81.5 78.0<br />

Wet bulb temperature = 21 °C<br />

Total cooling capacity (kW) 100.9 97.3 93.6 90.0 86.4 82.8<br />

Total power input (kW) 23.1 24.4 25.7 27.1 28.4 29.8<br />

23 °C<br />

40.1 40.9 41.8 42.6 43.5 44.3<br />

25 °C 48.5 49.6 50.6 51.6 52.7 53.7<br />

Dry bulb temperature<br />

27 °C Sensible cooling<br />

57.0 58.2 59.4 60.6 61.9 63.1<br />

29 °C capacity (kW)<br />

65.5 66.9 68.3 69.7 71.0 72.4<br />

31 °C 73.9 75.5 77.1 78.7 80.2 81.8<br />

33 °C 82.4 84.2 93.9 92.0 89.6 86.7<br />

Wet bulb temperature = 23 °C<br />

Total cooling capacity (kW) 106.5 102.8 99.0 95.2 91.4 87.7<br />

Total power input (kW) 24.2 25.6 27.0 28.3 29.7 31.1<br />

25 °C<br />

35.6 36.3 37.1 37.8 38.6 39.3<br />

Dry bulb temperature<br />

27 °C<br />

Sensible cooling<br />

29 °C 53.5 54.6 55.7 56.9 58.0 59.1<br />

31 °C<br />

capacity (kW)<br />

62.4 63.7 65.1 66.4 67.7 69.0<br />

44.5 45.5 46.4 47.3 48.3 49.2<br />

33 °C 71.4 72.9 74.4 75.9 77.4 78.9<br />

21

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!