Membrane Pre-treatment Using Plate Settlers - Ohiowater.org
Membrane Pre-treatment Using Plate Settlers - Ohiowater.org
Membrane Pre-treatment Using Plate Settlers - Ohiowater.org
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Convert the horizontal projected area to<br />
55 0 plate angle<br />
3. Divide the effective area by .574 (COS of 55 0 )<br />
to convert the surface area to 55 0<br />
25,740 ft 2 = 44,843 ft 2 of actual plate surface<br />
.574<br />
Convert the plate area to number of plate<br />
settlers<br />
4. Divide the actual plates surface area by the<br />
area of each plate (i.e. 45 ft 2 )<br />
44,843 ft 2 = 997 plates for 10 mgd<br />
45 ft 2