Convert the horizontal projected area to<br />

55 0 plate angle<br />

3. Divide the effective area by .574 (COS of 55 0 )<br />

to convert the surface area to 55 0<br />

25,740 ft 2 = 44,843 ft 2 of actual plate surface<br />

.574<br />

Convert the plate area to number of plate<br />

settlers<br />

4. Divide the actual plates surface area by the<br />

area of each plate (i.e. 45 ft 2 )<br />

44,843 ft 2 = 997 plates for 10 mgd<br />

45 ft 2