When the natural cooling capacity at the location where the filter is installed is not sufficient, air<br />

conditioning systems have to be added to the room. In the design of the air conditioning systems, the filter<br />

heat losses have to be taken into account. Table 6.3. gives an overview of the <strong>PQFI</strong> heat losses for the<br />

different power units. For multi-unit filters, the values of Table 6.3. have to be multiplied by the number of<br />

filter units. In CE versions of <strong>PQFI</strong>, one cubicle contains one filter unit. In cULus versions of <strong>PQFI</strong>, one<br />

filter unit is distributed over two cubicles.<br />

Table 6.3. <strong>Filter</strong> unit heat losses<br />

Network voltage U (Vrms) Unit rating (Arms) Heat loss (kW)<br />

208 ≤ Ue ≤ 480<br />

250 ≤ 5.2<br />

450 ≤ 11<br />

480 < Ue ≤ 690 (b) 180 (a) ≤ 7.1<br />

320 (a) - (c)<br />

Remark:<br />

(a)<br />

If the nominal system voltage is higher than 600V (Ue > 600V) the current rating<br />

of <strong>PQFI</strong> units in this voltage range may be derated automatically depending on<br />

the load condition for ambient temperatures higher than 30°C (86°F).<br />

(b)<br />

cULus version of <strong>PQFI</strong> are limited to 600 Vrms.<br />

(c)<br />

Not available at time of printing.<br />

6.4. Standard cubicle dimensions, fixing holes and clearances<br />

Standard CE versions of <strong>PQFI</strong> are mounted in cubicles of the Rittal TS8 type and have dimensions of 800<br />

x 600 x 2150 mm (width x depth x height). The cubicles have an elevated roof with lifting lugs. Each<br />

cubicle contains one power unit and is fitted with its own bottom cable entry and breaker. An optional<br />

cable entry cubicle (wxdxh 600 x 600 x 2150 mm) may be provided for top cable entry, single cable entry<br />

point (multi-unit filters).<br />

Standard cULus versions of <strong>PQFI</strong> are mounted in cubicles of the Rittal TS8 type. Each cULus filter unit is<br />

distributed over two cubicles and is mounted on a base frame. The overall dimensions of a cULus filter<br />

unit are 1400 x 600 x 2250 mm (width x depth x height) including the base frame. The cubicles have an<br />

elevated roof with lifting lugs. The cable entry cubicle houses a main breaker and can be supplied from<br />

the top and the bottom. Slave units also come with their own cable entry cubicle incorporating a<br />

protection breaker.<br />

A filter panel (consisting of one or more power units) can be installed against a wall or back to back to<br />

other cubicles providing that the heat transfer from the other cubicles to the filter cubicle is negligible. If a<br />

high heat transfer is expected, a spacing of 100 mm between the filter panel and the wall or the other<br />

cubicles is recommended. Figure 6.2. and Figure 6.3. show a top view of a typical <strong>PQFI</strong> installation with<br />

indication of the cubicle fixation holes. For fixing the cubicle to the floor M12 bolts and washers are<br />

recommended.<br />

<strong>PQFI</strong> - Chapter 6. Mechanical installation 31