<strong>FDB2</strong> Installation, operation and<br />

maintenance instructions<br />

Version: 10<br />

Date: 19.12.2012<br />

4. INSTRUCTIONS FOR SPRING OPERATED <strong>DAMPER</strong><br />

A) Under normal operating conditions the fire damper blade is held in the “open” position by the arm (pos 1)<br />

and connecting rod of fusible link (pos 2).<br />

The internal fusible link includes a fusible link (pos 2), which in turn holds a spring return connecting rod. This<br />

connecting rod holds the spring (pos 4) and fire damper in open position.<br />

B) The fusible link is temperature sensitive and when the air passing through and/or the air surround the fire<br />

damper reaches a temperature of approximately 74 º°C, the link will shatter.<br />

When the link smelts (pos 2) the connecting-rod is released and the spring (pos 4) will close the fire damper.<br />

°C) If you want close the damper manually pull the knob (pos 3) release and the external spring (pos 4) will<br />

close the fire damper.<br />

To reset the damper to close position pull the knob (pos 3) and rotate the arm counter-clockwise (pos 1) over<br />

the clamp up to the position of the connecting rod. Then set the shaft of the knob (pos 3) into the end section of<br />

connecting rod.<br />

WARNING:<br />

DURING RELEASE <strong>AND</strong> RESET OPERATION BE SURE THAT THERE IS NO RISK TO HURT<br />

YOURSELF!!!<br />