<strong>Power</strong> <strong>Cables</strong><br />

1 Core & 2 Cores<br />

PVC / PVC <strong>Cables</strong> IEC 60502<br />

PVC / PVC <strong>Cables</strong> IEC 60502 Table 3<br />

No. and<br />

Radial<br />

Nominal Diameter Thickness Approx.<br />

Conductor of of Overall Approx.<br />

Area Wire Insulation Diameter Weight<br />

(mm 2 ) (no./mm) (mm) (mm) (kg/km)<br />

1.5 7 / 0.53 0.8 6.3 55<br />

2.5 7 / 0.67 0.8 6.7 70<br />

4 7 / 0.85 1.0 7.6 100<br />

6 7 / 1.04 1.0 8.2 125<br />

10 7 / 1.35 1.0 9.2 175<br />

16 7 / 1.70 1.0 10.2 240<br />

25 7 / 2.14 1.2 11.9 350<br />

35 7 / 2.52 1.2 13.1 460<br />

50 19 / 1.78 1.4 14.8 595<br />

70 19 / 2.14 1.4 16.6 810<br />

95 19 / 2.52 1.6 19.2 1110<br />

120 37 / 2.03 1.6 20.8 1360<br />

150 37 / 2.25 1.8 23.0 1670<br />

185 37 / 2.52 2.0 25.4 2070<br />

240 61 / 2.25 2.2 28.7 2690<br />

300 61 / 2.52 2.4 31.7 3340<br />

400 61 / 2.85 2.6 35.3 4230<br />

500 61 / 3.20 2.8 39.5 5290<br />

630 127 / 2.52 2.8 43.2 6680<br />

800 127 / 2.85 2.8 47.7 8460<br />

1000 127 / 3.20 3.0 53.0 10545<br />

2 x 1.5 7 / 0.53 0.8 10.4 145<br />

2 x 2.5 7 / 0.67 0.8 11.2 180<br />

2 x 4 7 / 0.85 1.0 13.1 255<br />

2 x 6 7 / 1.04 1.0 14.2 285<br />

2 x 10 7 / 1.35 1.0 16.1 395<br />

2 x 16 7 / 1.70 1.0 18.2 590<br />

2 x 25 7 / 2.14 1.2 21.8 900<br />

2 x 35 7 / 2.52 1.2 24.0 1160<br />

2 x 50 (S) 19 / 1.78 1.4 23.0 1260<br />

2 x 70 (S) 19 / 2.14 1.4 26.0 1700<br />

2 x 95 (S) 19 / 2.52 1.6 30.0 2310<br />

2 x 120 (S) 37 / 2.03 1.6 32.0 2880<br />

2 x 150 (S) 37 / 2.25 1.8 36.0 3520<br />

2 x 185 (S) 37 / 2.52 2.0 40.0 4290<br />

2 x 240 (S) 61 / 2.25 2.2 44.0 5570<br />

2 x 300 (S) 61 / 2.52 2.4 49.0 6970<br />

Construction<br />

1. Conductor : Plain Annealed Copper to IEC 60228<br />

2. Insulation : PVC Compound Type A<br />

3. Sheath : PVC Compound Type ST1<br />

4. Colour : Insulation: 1 Core - Black<br />

2 Cores - Red & Black<br />

Sheath: 1 Core - Grey<br />

2 Cores - Black<br />

Technical Data<br />

Voltage Uo/U : 600 / 1000 V<br />

Conductor Stranding : Class 1, 2 stranded circular<br />

or compacted conductors<br />

Operating Temperature : Maximum 70°C<br />

Minimum Bending Radius : 1 Core –<br />

8D for 1.5mm 2 to 1000mm 2<br />

2 Cores –<br />

8D for 1.5mm 2 to 300mm 2<br />

4