Page 18 of <strong><strong>Europe</strong>an</strong> technical approval <strong>ETA</strong>-<strong>08</strong>/<strong>0376</strong>, issued on 8 September 2011<br />
Table 10: Design method A:<br />
Characteristic values for tension loads in cracked concrete<br />
Anchor size threaded rod M 12 M 16 M 20 M 24 M 27 M 30<br />
Steel failure<br />
Characteristic tension resistance,<br />
Steel, property class 5.8<br />
Characteristic tension resistance,<br />
Steel, property class 8.8<br />
Partial safety factor γ Ms,N<br />
1)<br />
Characteristic tension resistance,<br />
Stainless steel A4 and HCR,<br />
property class 50 (>M24) and 70 (≤ M24)<br />
Partial safety factor γ Ms,N<br />
1)<br />
Combined pullout and concrete cone failure<br />
Characteristic bond resistance τ Rk,cr [N/mm²] in cracked concrete C20/25<br />
N Rk,s [kN] 42 78 122 176 230 280<br />
N Rk,s [kN] 67 125 196 282 368 449<br />
1,50<br />
N Rk,s [kN] 59 110 171 247 230 281<br />
1,87 2,86<br />
Temperature range I 4) :<br />
40°C/24°C<br />
Temperature range II 4) :<br />
60°C/43°C<br />
Temperature range III 4) :<br />
72°C/43°C<br />
dry and wet concrete<br />
h ef ≤12d<br />
h ef >12d<br />
7,5<br />
7,0<br />
flooded bore hole 5) h ef ≤12d 7,5 6,0 5,0 4,5 4,0 4,0<br />
dry and wet concrete<br />
h ef ≤12d<br />
h ef >12d<br />
4,5<br />
4,0<br />
6,5<br />
6,5<br />
6,0<br />
6,0<br />
5,5<br />
5,5<br />
4,0 3,5 3,5<br />
4,0 3,5 3,5<br />
flooded bore hole 5) h ef ≤12d 4,5 4,0 3,5 3,5 3,5 3,5<br />
dry and wet concrete<br />
h ef ≤12d<br />
h ef >12d<br />
4,0<br />
3,5<br />
flooded bore hole 5) h ef ≤12d 4,0 3,5 3,0 3,0 3,0 3,0<br />
3,5<br />
3,5<br />
3,0<br />
3,0<br />
3,0<br />
3,0<br />
5,5<br />
5,5<br />
3,5<br />
3,5<br />
3,0<br />
3,0<br />
5,5<br />
5,5<br />
3,5<br />
3,5<br />
3,0<br />
3,0<br />
Partial safety factor (dry and wet concrete)<br />
1)<br />
γ Mp = γ Mc 1,8 2) 2,1 3)<br />
Partial safety factor (flooded bore hole)<br />
1)<br />
γ Mp = γ Mc 2,1 3)<br />
C30/37 1,04<br />
Increasing factors for<br />
concrete ψ c<br />
C40/50 1,<strong>08</strong><br />
C50/60 1,10<br />
Splitting failure<br />
Characteristic edge distance c cr,sp [mm]<br />
h≥2h ef<br />
1,0h ef<br />
2,0h ef >h>1,3h ef 5h ef – 2h<br />
h≤1,3h ef<br />
2,4h ef<br />
Characteristic spacing s cr,sp [mm] 2◦c cr,sp<br />
Partial safety factor (dry and wet concrete) γ Msp<br />
1)<br />
Partial safety factor (flooded bore hole)<br />
γ Msp<br />
1)<br />
1,8 2) 2,1 3)<br />
2,1 3)<br />
1) In absence of other national regulations<br />
2)<br />
The partial safety factor γ 2 = 1,2 is included.<br />
3)<br />
The partial safety factor γ 2 = 1,4 is included.<br />
4)<br />
Explanations see chapter 1.2<br />
5) Applications in flooded holes only until h ef = 12 d allowed<br />
<strong>Powers</strong> PURE150-PRO Injection resin with anchor rod for concrete<br />
Application with threaded rod<br />
Design method A:<br />
Characteristic values for tension loads in cracked concrete<br />
Annex 10<br />
of <strong><strong>Europe</strong>an</strong><br />
technical approval<br />
<strong>ETA</strong>-<strong>08</strong>/<strong>0376</strong>