Page 22 of <strong><strong>Europe</strong>an</strong> technical approval <strong>ETA</strong>-<strong>08</strong>/<strong>0376</strong>, issued on 8 September 2011<br />
Table 15: Design method A:<br />
Characteristic values for tension loads in cracked concrete<br />
Anchor size reinforcing bar ∅ 12 ∅ 14 ∅ 16 ∅ 20 ∅ 25 ∅28 ∅32<br />
Steel failure (Properties acc. to Annex 4)<br />
Characteristic tension resistance,<br />
BSt 500 S acc. to DIN 488-2:1986 or<br />
N Rk,s [kN] 62 85 111 173 270 339 442<br />
E DIN 488-2:2006 5)<br />
Partial safety factor γ Ms,N<br />
1)<br />
Combined pullout and concrete cone failure<br />
Characteristic bond resistance τ Rk,cr [N/mm²] in cracked concrete C20/25<br />
1,40<br />
Temperature range I 4) :<br />
40°C/24°C<br />
Temperature range II 4) :<br />
60°C/43°C<br />
Temperature range III 4) :<br />
72°C/43°C<br />
dry and wet concrete<br />
h ef ≤12d<br />
h ef >12d<br />
flooded bore hole 6) h ef ≤12d 5,5 4,5 4,0 3,5 3,0 3,0 3,0<br />
dry and wet concrete<br />
h ef ≤12d<br />
h ef >12d<br />
flooded bore hole 6) h ef ≤12d 3,0 3,0 2,5 2,5 2,0 2,0 2,0<br />
dry and wet concrete<br />
h ef ≤12d<br />
h ef >12d<br />
flooded bore hole 6) h ef ≤12d 3,0 2,5 2,5 2,0 2,0 2,0 2,0<br />
5,5<br />
5,0<br />
3,0<br />
2,5<br />
3,0<br />
2,5<br />
4,5<br />
4,5<br />
3,0<br />
3,0<br />
2,5<br />
2,5<br />
4,5<br />
4,5<br />
2,5<br />
2,5<br />
2,5<br />
2,5<br />
4,0<br />
4,0<br />
2,5<br />
2,5<br />
2,0<br />
2,0<br />
3,5<br />
3,5<br />
2,0<br />
2,0<br />
2,0<br />
2,0<br />
3,5<br />
3,5<br />
2,0<br />
2,0<br />
2,0<br />
2,0<br />
3,5<br />
3,5<br />
2,0<br />
2,0<br />
2,0<br />
2,0<br />
Partial safety factor (dry and wet concrete)<br />
1)<br />
γ Mp = γ Mc 1,8 2) 2,1 3)<br />
Partial safety factor (flooded bore hole)<br />
1)<br />
γ Mp = γ Mc 2,1 3)<br />
C30/37 1,04<br />
Increasing factors for<br />
C40/50 1,<strong>08</strong><br />
concrete ψ c<br />
C50/60 1,10<br />
Splitting failure<br />
Characteristic edge distance c cr,sp [mm]<br />
h≥2h ef<br />
1,0h ef<br />
2,0h ef >h>1,3h ef 5h ef – 2h<br />
h≤1,3h ef<br />
2,4h ef<br />
Characteristic spacing s cr,sp [mm] 2◦c cr,sp<br />
Partial safety factor (dry and wet concrete) γ Msp<br />
1)<br />
Partial safety factor (flooded bore hole) γ Msp<br />
1)<br />
1,8 2) 2,1 3)<br />
2,1 3)<br />
1)<br />
In absence of other national regulations<br />
2)<br />
The partial safety factor γ 2 = 1,2 is included.<br />
3)<br />
The partial safety factor γ 2 = 1,4 is included.<br />
4)<br />
Explanations see chapter 1.2<br />
5) For reinforcing bars, which do not comply with DIN 488: The characteristic resistance N Rk,s shall be<br />
determined acc. to <strong>Technical</strong> Report TR 029, equation (5.1).<br />
6) Applications in flooded holes only until h ef = 12 d allowed<br />
Regarding design of post-installed rebar as anchor see chapter 4.2<br />
<strong>Powers</strong> PURE150-PRO Injection resin with anchor rod for concrete<br />
Application with reinforcing bar<br />
Design method A:<br />
Characteristic values for tension loads in cracked concrete<br />
Annex 14<br />
of <strong><strong>Europe</strong>an</strong><br />
technical approval<br />
<strong>ETA</strong>-<strong>08</strong>/<strong>0376</strong>