Page 21 of <strong><strong>Europe</strong>an</strong> technical approval <strong>ETA</strong>-<strong>08</strong>/<strong>0376</strong>, issued on 8 September 2011<br />

Table 14: Design method A:<br />

Characteristic values for tension loads in uncracked concrete<br />

Anchor size reinforcing bar ∅ 8 ∅ 10 ∅ 12 ∅ 14 ∅ 16 ∅ 20 ∅ 25 ∅ 28 ∅ 32<br />

Steel failure (Properties acc. to Annex 4)<br />

Characteristic tension resistance,<br />

BSt 500 S acc. to DIN 488-2:1986 or N Rk,s [kN] 28 43 62 85 111 173 270 339 442<br />

E DIN 488-2:2006 5)<br />

Partial safety factor γ Ms,N<br />

1)<br />

Combined pullout and concrete cone failure<br />

Characteristic bond resistance τ Rk,ucr [N/mm²] in uncracked concrete C20/25<br />

Temperature range I 4) :<br />

40°C/24°C<br />

Temperature range II 4) :<br />

60°C/43°C<br />

Temperature range III 4) :<br />

72°C/43°C<br />

dry and wet<br />

concrete<br />

h ef ≤12d<br />

h ef >12d<br />

11<br />

9,0<br />

11<br />

9,5<br />

flooded bore<br />

hole 6) h ef≤12d 11 10 9,0 8,0 7,5 6,5 5,5 5,0 5,0<br />

dry and wet<br />

concrete<br />

h ef ≤12d<br />

h ef >12d<br />

6,5<br />

5,0<br />

6,5<br />

5,5<br />

flooded bore<br />

hole 6) h ef≤12d 6,5 6,5 6,5 6,0 6,0 5,5 4,5 4,5 4,0<br />

dry and wet<br />

concrete<br />

h ef ≤12d<br />

h ef >12d<br />

6,0<br />

5,0<br />

6,0<br />

5,0<br />

flooded bore<br />

hole 6) h ef≤12d 6,0 6,0 5,5 5,5 5,5 5,0 4,0 4,0 3,5<br />

Partial safety factor (dry and wet concrete) γ Mp = γ Mc<br />

1)<br />

Partial safety factor (flooded bore hole) γ Mp = γ Mc<br />

1)<br />

10<br />

9,0<br />

6,5<br />

6,0<br />

5,5<br />

5,0<br />

10<br />

9,5<br />

6,0<br />

5,5<br />

5,5<br />

5,0<br />

1,40<br />

9,5<br />

9,5<br />

6,0<br />

6,0<br />

5,5<br />

5,5<br />

9,0<br />

9,0<br />

5,5<br />

5,5<br />

5,0<br />

5,0<br />

9,0<br />

9,0<br />

5,5<br />

5,5<br />

4,5<br />

4,5<br />

1,8 2) 2,1 3)<br />

C30/37 1,04<br />

Increasing factors for<br />

concrete ψ c<br />

C40/50 1,<strong>08</strong><br />

C50/60 1,10<br />

2,1 3)<br />

8,5<br />

8,5<br />

5,0<br />

5,0<br />

4,5<br />

4,5<br />

8,5<br />

8,5<br />

5,0<br />

5,0<br />

4,5<br />

4,5<br />

Splitting failure<br />

Characteristic edge distance c cr,sp [mm]<br />

h≥2h ef<br />

1,0h ef<br />

2,0h ef >h>1,3h ef 5h ef – 2h<br />

h≤1,3h ef<br />

2,4h ef<br />

Characteristic spacing s cr,sp [mm] 2◦c cr,sp<br />

Partial safety factor (dry and wet concrete) γ Msp<br />

1)<br />

Partial safety factor (flooded bore hole) γ Msp<br />

1)<br />

1,8 2) 2,1 3)<br />

2,1 3)<br />

1)<br />

In absence of other national regulations<br />

2)<br />

The partial safety factor γ 2 = 1,2 is included.<br />

3)<br />

The partial safety factor γ 2 = 1,4 is included.<br />

4)<br />

Explanations see chapter 1.2<br />

5) For reinforcing bars, which do not comply with DIN 488: The characteristic resistance N Rk,s shall be<br />

determined acc. to <strong>Technical</strong> Report TR 029, Equation (5.1).<br />

6) Applications in flooded holes only until h ef = 12 d allowed<br />

Regarding design of post-installed rebar as anchor see chapter 4.2<br />

<strong>Powers</strong> PURE150-PRO Injection resin with anchor rod for concrete<br />

Application with reinforcing bar<br />

Design method A:<br />

Characteristic values for tension loads in uncracked concrete<br />

Annex 13<br />

of <strong><strong>Europe</strong>an</strong><br />

technical approval<br />

<strong>ETA</strong>-<strong>08</strong>/<strong>0376</strong>