OPTIONAL EQUIPMENT<br />

Single Side Inlet Connection<br />

The <strong>EDX</strong> is available with a Single Side Inlet option which eliminates<br />

external pipework, valves and field balancing associated<br />

with the standard (2) inlet design.<br />

Internal PVC pipework is utilized to relocate the water inlet to the<br />

side of each cell. The connection is standard with a hole and bolt<br />

circle pattern, other options are available. Note: Multiple cell<br />

installation will require adequate space between towers to allow<br />

for piping, unless the bottom inlet option is selected.<br />

If a tight, side by side layout is required, the <strong>EDX</strong> is available with<br />

an optional Bottom Inlet Connection. The inlet is located on the<br />

bottom of the cold water basin and allows the inlet pipework to<br />

run underneath the unit. Note: Adequate space is required<br />

underneath the unit for pipework. Please consult the factory for<br />

certified drawings indicating connection size and location.<br />

S<br />

K<br />

Model Static Single P Water Inlet* Water Outlet**<br />

No. Lift Inlet Height (Per Cell) (Per Cell)<br />

<strong>EDX</strong> 212-0122 17' 5” 8'-8-3/8” 11' 1” (1) 12” (1) 12”<br />

<strong>EDX</strong> 212-0222 23' 9-3/4” 14' 7-1/4” 11' 1” (1) 12” (1) 12”<br />

<strong>EDX</strong> 212-0322 19'- 4-1/2” 10' 8” 11' 1” (1) 12” (1) 12”<br />

<strong>EDX</strong> 212-0422 17' 5” 8' 8-3/8” 11' 1” (1) 12” (1) 12”<br />

<strong>EDX</strong> 212-0522 23' 9-3/4” 14' 7-1/4” 11' 1” (1) 12” (1) 12”<br />

<strong>EDX</strong> 212-0622 19' 4-1/2” 10' 8” 11' 1” (1) 12” (1) 12”<br />

<strong>EDX</strong> 212-0722 17' 5” 8' 8-3/8” 11' 1” (1) 12” (1) 12”<br />

<strong>EDX</strong> 212-0822 23' 9-3/4” 14' 7-/4” 11' 1” (1) 12” (1) 12”<br />

<strong>EDX</strong> 212-0922 19' 4-1/2” 10' 8” 11' 1” (1) 12” (1) 12”<br />

<strong>EDX</strong> 212-1022 23' 9-3/4” 14' 7-1/4” 11' 1” (1) 12” (1) 12”<br />

<strong>EDX</strong> 214-0124 17' 7-3/8” 8' 8-3/8” 12' 1” (1) 14” (1) 14”<br />

<strong>EDX</strong> 214-0224 19' 6-7/8” 10' 8” 12' 1” (1) 14” (1) 14”<br />

<strong>EDX</strong> 214-0324 17' 7-3/8” 8' 8-3/8” 12' 1” (1) 14” (1) 14”<br />

<strong>EDX</strong> 214-0424 19' 6-7/8” 10' 8” 12' 1” (1) 14” (1) 14”<br />

<strong>EDX</strong> 214-0524 17' 7-3/8” 8' 8-3/8” 12' 1” (1) 14” (1) 14”<br />

<strong>EDX</strong> 214-0624 19' 6-7/8” 10' 8” 12' 1” (1) 14” (1) 14”<br />

<strong>EDX</strong> 214-0724 17' 7-3/8” 8' 8-3/8” 12' 1” (1) 14” (1) 14”<br />

<strong>EDX</strong> 214-0824 24' 1/8” 14' 7-1/4” 12' 1” (1) 14” (1) 14”<br />

<strong>EDX</strong> 214-0924 19' 6-7/8” 10' 8” 12' 1” (1) 14” (1) 14”<br />

<strong>EDX</strong> 214-1024 17' 7-3/8” 8' 8-3/8” 12' 1” (1) 14” (1) 14”<br />

<strong>EDX</strong> 214-1124 19' 6-7/8” 10' 8” 12' 1” (1) 14” (1) 14”<br />

<strong>EDX</strong> 214-1224 24' 1/8” 14' 7-1/4” 12' 1” (1) 14” (1) 14”<br />

<strong>EDX</strong> 214-1324 24' 1/8” 14' 7-1/4” 12' 1” (1) 14” (1) 14”<br />

<strong>EDX</strong> 214-1424 19' 6-7/8” 10' 8” 12' 1” (1) 14” (1) 14”<br />

<strong>EDX</strong> 214-1524 24' 1/8” 14' 7-1/4” 12' 1” (1) 14” (1) 14”<br />

Notes:<br />

1. Use this chart for the pre-engineering phase of the project. Obtain factory certified drawings from your local EVAPCO representative or the factory.<br />

2. Pipework shown is provided by EVAPCO. Consult the factory certified drawings for dimensions.<br />

3. External pipework not shown must be provided by others and self-supported. Do not support pipework from the cooling tower.<br />

4. Note: The single inlet connection is located above the basin access door, position inlet piping properly to avoid blocking the door. Consult page 5 for<br />

dimensions of the unit.<br />

5. Consult the factory for optional bottom inlet connection.<br />

* Standard connection is hole and bolt circle design for 150# raised face flange.<br />

** Standard connection is Beveled for Weld and grooved for a mechanical coupling.<br />

Other Accessories/Optional Materials<br />

• Pony Motors<br />

• Bottom Sump Box<br />

• Gear Drive<br />

• Air Inlet Screens<br />

• Electric Water Level Controls and Level Indicators<br />

• Vibration Switch<br />

• Fan and Motor Davit<br />

• Flanged Connections<br />

• Flume Plate<br />

Models<br />

KW*<br />

<strong>EDX</strong> 212-0122 to 1022 (4) 12<br />

<strong>EDX</strong> 214-0124 to 1524 (4) 15<br />

Electric Pan Heaters<br />

9