21.11.2014 Views

GEA Aircooled Condensing Units - GEA Happel Belgium

GEA Aircooled Condensing Units - GEA Happel Belgium

GEA Aircooled Condensing Units - GEA Happel Belgium

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Electrical Data<br />

<strong>GEA</strong> <strong>Aircooled</strong> <strong>Condensing</strong> <strong>Units</strong><br />

C-Range<br />

CU<br />

Fan Motor<br />

(220-240 V/1~/50 Hz)<br />

Compressor<br />

(220-240 V/1~/50 Hz)<br />

Total (5)<br />

Motor Rated<br />

Protection<br />

Model OA FLA LRA OA (2) FLA (3) LRA FLA MCB (6)<br />

CT18 5.9 7.4 35 8.2 16<br />

CT22 0.7 0.8 1.8 7.6 9.5 47 10.3 16<br />

CT28 9.8 12.2 61 13.0 16<br />

CU<br />

Fan Motor<br />

(220-240 V/1~/50 Hz)<br />

Compressor<br />

(380-420 V/3~/50)<br />

Total (5)<br />

Motor Rated<br />

Protection<br />

Model OA FLA LRA OA (2) FLA (3) LRA FLA MCB (6)<br />

CT22 0.7 0.8 1.8 3.0 3.5 24 4.3 10<br />

CT28 3.8 4.4 32 5.2 10<br />

CS28 3.8 4.4 32 5.2 10<br />

CS34 0.7 0.8 1.8 4.5 5.4 40 6.2 10<br />

CS40 5.2 6.1 46 6.9 10<br />

CM40 5.2 6.1 46 7.3 16<br />

CM48 0.9 1.2 4.5 6.2 7.2 50 8.4 16<br />

CM61 8.0 9.3 66 10.5 16<br />

CP61 8.0 9.3 66 10.7 16<br />

CP72 1.3 1.4 4.6 8.7 10.6 74 12.0 16<br />

CP81 10.5 12.7 101 14.1 20<br />

CP90 12.1 14.0 99 15.4 20<br />

CL90 (4) 12.1 14.0 99 16.8 20<br />

CL11 (4) 14.2 16.6 123 19.4 25<br />

CL12 (4) 2.5 2.8 9.2 16.3 19.0 127 21.8 25<br />

CL16 (4) 19.1 23.0 167 25.8 32<br />

CL19 (4) 22.7 27.1 198 29.9 40<br />

CU<br />

Fan Motor<br />

(220-240 V/1~/50 Hz)<br />

Compressor<br />

(380-420 V/3~/50 Hz)<br />

Total (5)<br />

Motor Rated<br />

Protection<br />

Model OA FLA LRA OA (2) FLA (3) LRA FLA MCB (6)<br />

CPV48 1.3 1.4 4.6 12.4 14.4 100 15.8 20<br />

CLV48 (4) 12.4 14.4 100 15.8 20<br />

CLV61 (4) 2.5 2.8 9.2 16.0 18.6 132 21.4 25<br />

CLV72 (4) 17.4 21.2 148 24.0 32<br />

CLV81 (4) 21.0 25.4 202 28.2 40<br />

(1) OA = Operating Amps, FLA = Full Load Amps and LRA = Locked Rotor Amps<br />

(2) Operating Amps at 5 o C evaporating, 50 o C condensing with R407C.<br />

(3) Full Load Amps at 10 o C evaporating, 60 o C condensing with R407C.<br />

(4) CL units have two (2) fans.<br />

(5) The values are Total Full Load Amps for the unit.<br />

(6) <strong>Condensing</strong> units are supplied by MCB's fitted in the Air Handling Unit as standard,<br />

the ratings of which are shown in this column. MCB's have a C-Type tripping characteristic to IEC 898, VDE 0641T11.<br />

10 PR-2007-0346-GB • Subject to modifications • Status 05/2007