Electrical Data<br />
<strong>GEA</strong> <strong>Aircooled</strong> <strong>Condensing</strong> <strong>Units</strong><br />
C-Range<br />
CU<br />
Fan Motor<br />
(220-240 V/1~/50 Hz)<br />
Compressor<br />
(220-240 V/1~/50 Hz)<br />
Total (5)<br />
Motor Rated<br />
Protection<br />
Model OA FLA LRA OA (2) FLA (3) LRA FLA MCB (6)<br />
CT18 5.9 7.4 35 8.2 16<br />
CT22 0.7 0.8 1.8 7.6 9.5 47 10.3 16<br />
CT28 9.8 12.2 61 13.0 16<br />
CU<br />
Fan Motor<br />
(220-240 V/1~/50 Hz)<br />
Compressor<br />
(380-420 V/3~/50)<br />
Total (5)<br />
Motor Rated<br />
Protection<br />
Model OA FLA LRA OA (2) FLA (3) LRA FLA MCB (6)<br />
CT22 0.7 0.8 1.8 3.0 3.5 24 4.3 10<br />
CT28 3.8 4.4 32 5.2 10<br />
CS28 3.8 4.4 32 5.2 10<br />
CS34 0.7 0.8 1.8 4.5 5.4 40 6.2 10<br />
CS40 5.2 6.1 46 6.9 10<br />
CM40 5.2 6.1 46 7.3 16<br />
CM48 0.9 1.2 4.5 6.2 7.2 50 8.4 16<br />
CM61 8.0 9.3 66 10.5 16<br />
CP61 8.0 9.3 66 10.7 16<br />
CP72 1.3 1.4 4.6 8.7 10.6 74 12.0 16<br />
CP81 10.5 12.7 101 14.1 20<br />
CP90 12.1 14.0 99 15.4 20<br />
CL90 (4) 12.1 14.0 99 16.8 20<br />
CL11 (4) 14.2 16.6 123 19.4 25<br />
CL12 (4) 2.5 2.8 9.2 16.3 19.0 127 21.8 25<br />
CL16 (4) 19.1 23.0 167 25.8 32<br />
CL19 (4) 22.7 27.1 198 29.9 40<br />
CU<br />
Fan Motor<br />
(220-240 V/1~/50 Hz)<br />
Compressor<br />
(380-420 V/3~/50 Hz)<br />
Total (5)<br />
Motor Rated<br />
Protection<br />
Model OA FLA LRA OA (2) FLA (3) LRA FLA MCB (6)<br />
CPV48 1.3 1.4 4.6 12.4 14.4 100 15.8 20<br />
CLV48 (4) 12.4 14.4 100 15.8 20<br />
CLV61 (4) 2.5 2.8 9.2 16.0 18.6 132 21.4 25<br />
CLV72 (4) 17.4 21.2 148 24.0 32<br />
CLV81 (4) 21.0 25.4 202 28.2 40<br />
(1) OA = Operating Amps, FLA = Full Load Amps and LRA = Locked Rotor Amps<br />
(2) Operating Amps at 5 o C evaporating, 50 o C condensing with R407C.<br />
(3) Full Load Amps at 10 o C evaporating, 60 o C condensing with R407C.<br />
(4) CL units have two (2) fans.<br />
(5) The values are Total Full Load Amps for the unit.<br />
(6) <strong>Condensing</strong> units are supplied by MCB's fitted in the Air Handling Unit as standard,<br />
the ratings of which are shown in this column. MCB's have a C-Type tripping characteristic to IEC 898, VDE 0641T11.<br />
10 PR-2007-0346-GB • Subject to modifications • Status 05/2007