Unit Location on Site / <strong>Condensing</strong> Unit Access<br />

<strong>Condensing</strong> Unit Access<br />

<strong>GEA</strong> <strong>Aircooled</strong> <strong>Condensing</strong> <strong>Units</strong><br />

C-Range<br />

Ensure that the site is level and that it can support the weight of the equipment.<br />

<strong>Condensing</strong> <strong>Units</strong> must be located in an unobstructed position to ensure adequate air circulation through the cooling<br />

coils. Care must be taken to avoid "short circuit" air paths and re-circulation of air from one unit to another. Whenever<br />

possible position <strong>Condensing</strong> <strong>Units</strong> such that they are reasonably sheltered from strong winds and avoid prevailing<br />

winds blowing directly onto the fan(s). <strong>Units</strong> should be bolted down in case of high winds.<br />

<strong>Condensing</strong> <strong>Units</strong> should not be sited more than 15 m (50ft) above or 4 m (13ft) below the base of the air<br />

conditioning unit.<br />

Please note that ALL <strong>GEA</strong> Denco <strong>Condensing</strong> <strong>Units</strong> are supplied with a 5 psig holding charge of Nitrogen.<br />

Access space should be provided as detailed on the drawings below but allowing at least one metre free access.<br />

<strong>Condensing</strong> Unit Access<br />

Access is gained by means of a removable panel secured by two screws. The panel also contains the interlocked<br />

door isolator, which will have to be turned to the “OFF” position, before the panel can be removed. This panel is<br />

situated on the left-hand side of the unit (looking at the fan). For major service work, such as replacing the<br />

compressor, the top and side panels may be removed.<br />