22.11.2014 Views

Stirling Power Cooler LPC-RL - Stirling Cryogenics

Stirling Power Cooler LPC-RL - Stirling Cryogenics

Stirling Power Cooler LPC-RL - Stirling Cryogenics

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

SC.1.1.1003<br />

<strong>Stirling</strong> <strong>Power</strong> <strong>Cooler</strong> GPC<br />

gas power cooler<br />

The Gas <strong>Power</strong> <strong>Cooler</strong> (GPC) uses pressurized helium gas<br />

(typically 20 barg) as medium to transfer cold to the application.<br />

as a shield for the 20 K loop, maximizing the cooling power<br />

available to the 20 K target.<br />

The GPC is a two-stage <strong>Stirling</strong> cryogenerator which<br />

simultaneously provides refrigeration at 20 K and at 80 K<br />

by means of two separate heat exchangers. Each of them<br />

consists of a wound spiral tube and a cold gas pump. The two<br />

pumps circulate the gas in seperate loops, from the two heat<br />

exchangers in the application (where energy in injected into<br />

the medium) to the GPC (where energy in extracted from the<br />

medium).<br />

The GPC is connected to the application by two delivery<br />

and return lines ducted together in a single flexible vacuum<br />

insulated line. This offers flexibility for the positioning and<br />

installation of the GPC (up to a radius of 10 meters). In both<br />

the application and transfer lines, the 80 K loop can be used<br />

Operation of the GPC is fully automatic. It runs down to the<br />

lowest possible temperature depending on the application<br />

load. If required, the GPC can be equipped with a set-point<br />

controller that maintains a fixed temperature regardless of<br />

fluctuations in the application load.<br />

The delivery of a GPC system consistst of a two stage<br />

cryogenerator with two cold gas pumps and optional flexible<br />

connection lines.<br />

The figures mentioned below are only an indication, correct<br />

values can only be given after detailed technical discussion and<br />

optimization.<br />

GAS POWER COOLERS<br />

Capacity [W]** <strong>Power</strong> input Cooling water<br />

20 K/80 K 20 K/80 K 30 K/80 K He gas flow [kW] [l/h@15°C]<br />

• GPC-1<br />

75/0<br />

50/400<br />

90/400<br />

Will be a result<br />

11<br />

750<br />

• GPC-2<br />

150/0<br />

100/800<br />

180/800<br />

of customers<br />

22<br />

1.000<br />

• GPC-4<br />

350/0<br />

200/1.600<br />

360/1.600<br />

process conditions.<br />

45<br />

3.500<br />

** simultaneously at 2nd stage ad 1st stage<br />

All specifications at nominal operating conditions. All data are subject to alteration without prior notice.<br />

Pictures are intended to present a general idea of the products.<br />

<strong>Stirling</strong> <strong>Cryogenics</strong> BV, Science Park Eindhoven 5003, 5692 EB Son, The Netherlands<br />

a<br />

company

Hooray! Your file is uploaded and ready to be published.

Saved successfully!