<strong>Industrial</strong> <strong>PC</strong> <strong>power</strong> <strong>supplies</strong><br />

UPS function<br />

BP-2423N-B1<br />

24V / 2.3 Ah<br />

Battery pack for eNSP-300P series<br />

Maintenance-free lead-battery<br />

Installation into 5.25“ drive slot<br />

The battery pack BP-2423N-B1 serves to store energy for the<br />

UPS <strong>PC</strong> <strong>power</strong> supply eNSP-300P. It is designed for the installation<br />

into a 5.25“ drive slot. It is connected to the UPS <strong>PC</strong> <strong>power</strong><br />

supply via a two-pole connector. A fuse for short-circuit protection<br />

is integrated in the circuit. The equipped lead batteries are<br />

maintenance-free.<br />

Te c h n i c a l d a t a<br />

Voltage<br />

24 V DC<br />

Capacitance<br />

2.3 Ah<br />

Number of batteries 2<br />

Type of battery<br />

Maintenance-free lead battery, 12 V<br />

Backup time of a typical <strong>PC</strong><br />

200 W app. 3 minutes, 100 W app. 9 minutes<br />

Fuse<br />

20 A<br />

Connector<br />

JST, VL series<br />

Operating temperature 0…+40 °C<br />

Storage temperature -20…+50 °C<br />

Dimensions<br />

191 x 145 x 41.5 mm ±0.5mm<br />

Weight (net)<br />

2.7 kg<br />

Drawing BP-2423N-B1<br />

BATT<br />

PIN No.<br />

Function<br />

1 Batt +<br />

2 Batt –<br />

Tolerance ±0.5 mm<br />

During storage the battery pack should be recharged<br />

every 6 months.<br />