Function<br />

The governor is closed when it is disconnected<br />

from the power supply.<br />

Opening: Alternating voltage is applied<br />

and fed to the solenoid coil via<br />

a rectifier with a suppressor circuit.<br />

The blue LED lights up. The coil’s<br />

magnetic field pulls the armature<br />

upwards and clears the supply<br />

nozzle for the gas inlet pressure p e .<br />

The gas passes through the internal<br />

impulse tube to the adjustment diaphragm<br />

and then pushes the valve<br />

seat open. The outlet pressure is applied<br />

to the servo-diaphragm via the<br />

internal bypass. The servo-governor<br />

then maintains a set constant outlet<br />

pressure p G .<br />

Governor for gas <strong>VAD</strong><br />

The nominal outlet pressure p G is<br />

defined by the control spring.<br />