Baffling Condition T 10<br />

/T Baffling Description Typical Unit Process<br />

Unbaffled 0.1 None, agitated basins, very low length Clearwell, storage tank, no baffles or perforated inlet or<br />

to width ratio, high inlet and outlet<br />

outlet, submerged inlet and outlets.<br />

flow velocities<br />

Poor 0.3 Single or multiple unbaffled inlets and Conventional sedimentation<br />

outlets, few to none intra basin baffles<br />

basins or clearwell with<br />

2 or 3 baffles<br />

Average 0.5 Baffled inlet or outlet with some intra‐ Some sedimentation basins<br />

basin baffles<br />

with several baffles<br />

Superior 0.7 Perforated inlet baffle, serpentine or Filters or clearwell with perforated intra‐basin baffles,<br />

outlet serpentine baffling<br />

weir or perforated launders<br />

“Perfect” (plug flow) 1.0 Very high length‐to‐width ratio Piping (pipeline flow), perforated inlet, outlet<br />

and intra‐basin baffles