30.11.2014 Views

ieee transactions on energy conversion, vol. 21, no - Richard J ...

ieee transactions on energy conversion, vol. 21, no - Richard J ...

ieee transactions on energy conversion, vol. 21, no - Richard J ...

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

874 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. <strong>21</strong>, NO. 4, DECEMBER 2006<br />

TABLE I<br />

2-hp AND 5-hp INDUCTION MOTORS PROPERTIES<br />

Fig. 6. Experimentally based results of the absolute value of Re(⃗i s (t)) in<br />

amperes versus angle δ(t) ≠ ⃗ i s (t) − ̸ ⃗v s (t) in degrees for the case of the<br />

5-hp inducti<strong>on</strong> motor under a healthy c<strong>on</strong>diti<strong>on</strong>.<br />

Fig. 5.<br />

Schematic representati<strong>on</strong> of a tapped inducti<strong>on</strong> motor.<br />

As representative examples of the many tests performed <strong>on</strong><br />

the 2-hp and 5-hp inducti<strong>on</strong> motors in the laboratory, the pendulous<br />

oscillati<strong>on</strong>s of the 5-hp inducti<strong>on</strong> motor in a polar coordinate<br />

plot are shown in Figs. 6 and 7 with corresp<strong>on</strong>ding enlargements<br />

(zooms) in Figs. 8 and 9, respectively, for a healthy and a<br />

12 turns (5%) fault. The short circuit was through a 1-Ω resistor,<br />

r f =1Ω. Again, the range of the pendulous oscillati<strong>on</strong>, the<br />

so-called swing angle ∆δ, is shown for the above-menti<strong>on</strong>ed<br />

cases of Figs. 6 and 7 in an enlarged fashi<strong>on</strong> in Figs. 8 and 9,<br />

respectively. As <strong>on</strong>e can see in Fig. 9, an interturn fault generates<br />

an unfilled-petal shape with a slight degree of curvature.<br />

This curvature is due to the existence of the resistor r f in the<br />

circuit shown in Fig. 5, which is used to restrict the shorted<br />

loop current to an immune (safe) level of current that does <strong>no</strong>t<br />

cause permanent coil damage. The amplitude of the maximum<br />

thickness of the petal shape caused by the swing angle is used<br />

here as the interturn fault signature or index.<br />

The functi<strong>on</strong>al block diagram of an <strong>on</strong>-line interturn fault<br />

diag<strong>no</strong>sis using the swing angle, ∆δ, is depicted in Fig. 10. In<br />

this block diagram, the motor terminal currents and <strong>vol</strong>tages are<br />

measured through current and <strong>vol</strong>tage sensors and the outputs<br />

are digitized using an analog-to-digital (A/D) c<strong>on</strong>verter. The output<br />

signals of the A/D c<strong>on</strong>verter are filtered by a band pass filter<br />

(BPF), while the output signals of the BPF are further sampled<br />

(collected) throughout a period equal to the period of the power<br />

supply frequency; see Fig. 10. For each set of collected data<br />

Fig. 7. Experimentally based results of the absolute value of Re(⃗i s (t)) in<br />

amperes versus angle δ(t) ≠ ⃗ i s (t) − ̸ ⃗v s (t) in degrees for the case of the<br />

5-hp inducti<strong>on</strong> motor under a faulty c<strong>on</strong>diti<strong>on</strong> having 12 (5%) shorted turns,<br />

(shorted through 1-Ω resistor.)<br />

Fig. 8. Enlarged dotted-frame porti<strong>on</strong> of Fig. 6, showing swing angle, ∆δ =<br />

max(∆δ(r) =δ max − δ min ), in the healthy situati<strong>on</strong>.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!