Capacities and<br />

information for<br />

selecting the right unit<br />

4.1. Choosing your <strong>AquaFREE</strong> <strong>system</strong><br />

The following steps are an example of how to choose the <strong>system</strong> units and indicates the<br />

way to decide on the model best suited to your own specific needs:<br />

We re<strong>com</strong>mend that you choose the <strong>AquaFREE</strong> <strong>system</strong> according to the heating load.<br />

4.1.1. How to use the data in this chapter<br />

Define the installation requirements: load, operating temperature and special installation<br />

needs. Then select the most suitable units. Decide on where to put the outdoor unit to<br />

allow easy maintenance and service.<br />

Use the following information to calculate the most suitable units:<br />

<br />

Relevant sections of Chapter 4:<br />

−<br />

−<br />

−<br />

Unit capacities: Section 4.2<br />

Correction factors for piping lenght: Section 4.6<br />

Data related to noise: Section 4.7<br />

<br />

−<br />

−<br />

−<br />

In addition, use the following information from the technical catalogue:<br />

General data: Chapter 2<br />

Length of water piping: Section 7.4.2<br />

Electrical “water rule” wiring: Section 9.3.2<br />

4.1.2. Example of choosing units by heating load<br />

We suggest the following method to determine the characteristics of the <strong>system</strong> units:<br />

System requirements<br />

Step 1:<br />

Heating load:<br />

Wet-bulb temperature of the in<strong>com</strong>ing air: -5 ºC<br />

Temperature of the water outlet: 35 ºC<br />

Temperature of the water inlet: 30 ºC<br />

Thermal load:<br />

8.00 kW<br />

NOTE:<br />

The calculation<br />

methods for thermal<br />

loads in the building<br />

should <strong>com</strong>ply with the<br />

regulations applicable<br />

in each country.<br />

Type of installation:<br />

Installation restrictions:<br />

Power source:<br />

<strong>AquaFREE</strong> module lower than the outdoor<br />

unit:<br />

Total equivalent distance between the<br />

<strong>AquaFREE</strong> module and the outdoor unit:<br />

Radiant Floorr<br />

230 V, 1~, 50 Hz<br />

15 m<br />

20 m<br />

Type of <strong>AquaFREE</strong> module:<br />

<strong>AquaFREE</strong> RWM modules needed<br />

pag. 44<br />

TCGB0042 rev.0 - 01/2007