01.12.2014 Views

AquaFREE system - Airconwarehouse.com

AquaFREE system - Airconwarehouse.com

AquaFREE system - Airconwarehouse.com

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Capacities and<br />

information for<br />

selecting the right unit<br />

4.4. Capacities and electrical power consumed for the most significant values<br />

4.4.1. Heating mode<br />

<strong>AquaFREE</strong> units<br />

Outdoor air inlet<br />

temperature<br />

DB/WB (ºC)<br />

Water outlet/inlet<br />

temperature<br />

(35/30 ºC)<br />

Water outlet/inlet<br />

temperature<br />

(45/40 ºC)<br />

CAP IPT CAP IPT<br />

Radiant floor<br />

Radiators<br />

RWM-3FSN1E<br />

8,00 1,98 7,47 2,47<br />

RWM-4FSN1E 7/6<br />

11,20 3,24 10,10 3,78<br />

RWM-5FSN1E 14,00 4,03 14,10 4,83<br />

NOTES:<br />

CAP: Compressor capacity at nominal frequency (kW)<br />

IPT: Nominal electrical power consumed (kW)<br />

<strong>AquaFREE</strong> units<br />

Outdoor air inlet<br />

temperature<br />

WB (ºC)<br />

Water outlet/inlet<br />

temperature<br />

(35/30 ºC)<br />

Water outlet/inlet<br />

temperature<br />

(45/40 ºC)<br />

Max. CAP Max. IPT Max. CAP Max. IPT<br />

Radiant floor<br />

Radiators<br />

RWM-3FSN1E<br />

6,00 2,74 5,30 3,06<br />

RWM-4FSN1E -7<br />

8,60 3,79 8,70 4,46<br />

RWM-5FSN1E 12,02 5,34 10,59 5,85<br />

NOTES:<br />

Max. CAP: Compressor capacity at maximum frequency (kW)<br />

Max. IPT: Maximum electrical power consumed (kW)<br />

pag. 52<br />

TCGB0042 rev.0 - 01/2007