Medium voltage switchgear application guide
Medium voltage switchgear application guide
Medium voltage switchgear application guide
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Electrical installations<br />
contain receivers, the<br />
power supply to which<br />
must be controlled by<br />
<strong>switchgear</strong>.<br />
<strong>Medium</strong> <strong>voltage</strong> <strong>switchgear</strong><br />
<strong>application</strong><br />
T<br />
<strong>guide</strong><br />
his behaviour <strong>guide</strong> is of based electrical on the equipment analysis of (transformers, phenomena arising motors, from etc.), the<br />
type and during characteristics normal or of faulty the device running.Its best adapted aim is to to help your you needs. choose the<br />
Switchgear provides<br />
circuit electrical<br />
protection,<br />
disconnection and<br />
control.<br />
date<br />
11/94<br />
- B•3•2 -<br />
revised<br />
05/2004<br />
■ Merlin Gerin<br />
■ Square D ■ Telemecanique
<strong>Medium</strong> <strong>voltage</strong> <strong>switchgear</strong> <strong>application</strong> <strong>guide</strong><br />
CONTENTS<br />
1<br />
- Transformer 3<br />
1 - 1 Switchgear to be used 3<br />
1 - 2 Device characteristics 3<br />
2 - Motor 7<br />
2 - 1 Switchgear to be used 7<br />
2 - 2 Device characteristics 7<br />
3 - Capacitor 10<br />
3 - 1 Switchgear to be used 10<br />
3 - 2 Device characteristics 11<br />
12 Switchgear Device characteristics to be used 4 - 3 Determination of a generator circuit breaker 13 15<br />
4 - Generator 13<br />
5 - Lines and cables 16<br />
5 - 1 Switchgear to be used 16<br />
5 - 2 Device characteristics 16<br />
6 - Arc furnace 18<br />
6 - 1 Switchgear to be used 18<br />
6 - 2 Device characteristics 18<br />
date<br />
11/94<br />
- B•3•2 -<br />
revised<br />
12/95<br />
1: 2: motor transformer<br />
3: 4: capacitor<br />
5: lines generator<br />
6: arc furnace and cables<br />
Appendix 7: 8: diode fused switch-disconnector and thyristor <strong>application</strong>s and fused contactor association<br />
7 - Appendices 20<br />
page 2
<strong>Medium</strong> <strong>voltage</strong> <strong>switchgear</strong> <strong>application</strong> <strong>guide</strong><br />
1 - TRANSFORMER 1 - 1 Switchgear to be used<br />
A fused switch-disconnector, fused contactor and circuit breaker are<br />
usually used for operating and protecting high power transformers.<br />
type power transformer controlled by<br />
MV/LV P ≤ 2 MVA dry or immersed type fused switch-disconnector<br />
transformer<br />
or circuit breaker<br />
or fused contactor<br />
2 MVA < P ≤ 4 MVA dry or immersed type fused switch-disconnector<br />
or circuit breaker<br />
or fused contactor<br />
MV/MV P ≤ 4 MVA dry type circuit breaker<br />
transformer immersed type circuit breaker<br />
P > 4 MVA immersed type circuit breaker<br />
The switch and contactor make sure the transformer is switched on and off<br />
during normal and overload running.<br />
network The fuse short-circuit limits and breaks power. short-circuit currents generated by the upstream<br />
The as short-circuit breaker currents. can make, withstand and break operating currents as well<br />
The protection system (CT, VT, relay, release…) automatically causes tripping<br />
when a fault is detected.<br />
1 - 2 Device characteristics<br />
The device must be able to:<br />
■ withstand and operate the continuous operating current and<br />
eventual overloads,<br />
■ break the fault current at the connection point; on the transformer’s<br />
secondary terminals,<br />
■ withstand short-circuit switching and no-load transformer<br />
switching peaks,<br />
■ break the no-load currents without excessive over<strong>voltage</strong><br />
(downstream open).<br />
The control and/or protection device must be located upstream of the<br />
transformer.<br />
Transformer faults cannot be picked up by downstream protection alone.<br />
A downstream control mechanism cannot isolate the fault transformer.<br />
date<br />
11/94<br />
- B•3•2 -<br />
revised<br />
12/95<br />
page 3
@@@@@@@@e<br />
@@@@@@@@<br />
@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e<br />
@@@@@@@@<br />
@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e<br />
@@@@@@@@e<br />
@@h<br />
@@h<br />
@@h<br />
@@h<br />
@@h<br />
@@h<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@g<br />
@@g<br />
@@g<br />
@@g<br />
@@g<br />
@@g<br />
@@@@@@@@<br />
@@@@@@@@<br />
@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@<br />
@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@@@@@@@<br />
@@@@@@@@<br />
<strong>Medium</strong> <strong>voltage</strong> <strong>switchgear</strong> <strong>application</strong> <strong>guide</strong><br />
1 - TRANSFORMER<br />
(cont’d)<br />
fig. 1: transformers feeder<br />
MV/LV transformers<br />
MV upstream busbars<br />
date<br />
11/94<br />
MV busbars<br />
fig. 2: transformers incomer<br />
MV downstream busbars<br />
- B•3•2 -<br />
revised<br />
05/2004<br />
MV/MV transformer<br />
THE DEVICE MUST BE ABLE TO:<br />
■<br />
EVENTUAL<br />
WITHSTAND<br />
OVERLOADS<br />
AND OPERATE THE CONTINUOUS OPERATING CURRENT AND<br />
rated The device current must and be eventual dimensioned overloads. to be able to withstand the transformer’s<br />
The rated current Inis given<br />
U:<br />
in the<br />
operating<br />
following<br />
<strong>voltage</strong><br />
equation:<br />
Ir =<br />
In specific 3<br />
S (in kVA)<br />
• U (in<br />
transformer cases kV)<br />
manufacturer where the must transformer supply overloads must operate likely in to overload, be applied the<br />
device depending on the ambient temperature. to the<br />
This The current overload value is expressed that should in be time taken and into as a account percentage is the of following: the rated power.<br />
Ir overload= Ir •Xoverload<br />
Examples:<br />
630 ■MV/LV kVA MV/LV transformer transformer; tee-off (fig.<br />
Unprimary:<br />
1) 20 kV<br />
Ir au primaire : control device 3 S<br />
•<br />
rating U = must<br />
3630<br />
• 20 = 18.18 A<br />
The be higher than or equal to 18.18 A.<br />
400 standardised values used by Merlin Gerin are:<br />
If - 630 - 1250 - 2500 - 3150 A.<br />
■a the control device is:<br />
200 fused A and switch-disconnector: the real rating of the assembly the fuse association becomes the limits same this as current the fuse. to<br />
■<br />
device a fused contactor: it is impossible to use a fused contactor as an control<br />
■a circuit since breaker: the contactor the rating has which a maximum we approve rated is <strong>voltage</strong> 400 A. of 12 kV.<br />
3150 ■MV/MV transformer incomer (fig. 2)<br />
temporary kVA MV/MV load of transformer; 20% one hour.<br />
Un secondary= 5.5 kV operating with a<br />
Ir secondary: 3150<br />
Ir overload= 331<br />
3 •<br />
x<br />
5.5 = 331 A<br />
We shall choose a<br />
1.2<br />
circuit<br />
= 397<br />
breaker<br />
A.<br />
with a rated current of 630 A.<br />
■<br />
The<br />
BREAK<br />
breaking<br />
THE<br />
capacity<br />
INSTALLATION’S<br />
must be higher<br />
FAULT<br />
than<br />
CURRENT<br />
circuit current at the point of installation. or equal to the maximum short-<br />
When must be a fused higher contactor than the current is used limited as a control by the device, fuse. the breaking capacity<br />
The short-circuit current limited<br />
Uk: transformer<br />
by the transformer<br />
short-circuit<br />
is equal<br />
<strong>voltage</strong><br />
to:<br />
Ik = Ir transfo. x 100<br />
Uk transfo.<br />
You will find in appendix 1 some values of Uk<br />
page 4
@@@@@@@@e<br />
@@@@@@@@<br />
@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e<br />
@@@@@@@@<br />
@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e<br />
@@@@@@@@e<br />
@@h<br />
@@h<br />
@@h<br />
@@h<br />
@@h<br />
@@h<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@g<br />
@@g<br />
@@g<br />
@@g<br />
@@g<br />
@@g<br />
@@@@@@@@<br />
@@@@@@@@<br />
@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@<br />
@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@@@@@@@<br />
@@@@@@@@<br />
<strong>Medium</strong> <strong>voltage</strong> <strong>switchgear</strong> <strong>application</strong> <strong>guide</strong><br />
1 - TRANSFORMER<br />
(cont’d)<br />
date<br />
11/94<br />
0<br />
- B•3•2 -<br />
revised<br />
I 1 = current giving maximum<br />
breaking capacity<br />
I 2 = current giving the matching<br />
arc energy conditions<br />
I 3 = minimum breaking<br />
current<br />
05/2004<br />
I r = rated current<br />
definition of fuse operating areas<br />
(see fuse technical leaflet)<br />
Example:<br />
Transformer: Secondary <strong>voltage</strong>: 10 MVA10 kV; primary <strong>voltage</strong>: 20 kV<br />
Short-circuit<br />
Insecondary: 577 <strong>voltage</strong>: A 9%<br />
a) the device is upstream of the transformer<br />
The standardised breaking capacity values must are: be 8 - equal 12.5 - to 16 or - higher 20 - 25 than - 31.5 the - network 40 - 50 kA.<br />
Ik<br />
b) the device is downstream of the transformer<br />
The current breaking limited capacity by the transformer must be equal as in to the or following higher than equation: the short-circuit<br />
Ik = In x 100<br />
We shall<br />
Uk<br />
= 577 •<br />
choose a device<br />
9<br />
100 = 6411 A<br />
with a breaking capacity equal to 8 kA.<br />
The Fuse fuse protection<br />
network as makes a result sure of that a downstream short-circuit fault currents are broken. generated by the upstream<br />
protection, In order to determine you must know: the required fuse rating to ensure transformer<br />
■the ■power transformer’s (S in kVA), characteristics<br />
■short-circuit ■rated current <strong>voltage</strong> with eventual (Ukin%),<br />
■the characteristics of the fuse overload family (A).<br />
■time/current characteristics at 0.1 s), used<br />
■minimum ■the installation breaking and current operating (I3in conditions A).<br />
open a cubicle, air,<br />
■in<br />
In order<br />
fuse<br />
to<br />
chambers.<br />
■choose the determine rated current the fuse of the rating, you must:<br />
■in ■if the general: installation transfo. and Ir1.3 operating ≤fuseIr≤transfo. conditions are Ir1.5,<br />
a fuse current rating immediately higher than transfo. not fully Ir1.5. known, choose<br />
■check secondary that short-circuit transformer current switching does does melt not the melt fuse the with fuse the and equation: that the<br />
IkxI3
<strong>Medium</strong> <strong>voltage</strong> <strong>switchgear</strong> <strong>application</strong> <strong>guide</strong><br />
1 - TRANSFORMER<br />
(cont’d)<br />
Transformer Circuit breaker protection protection<br />
thresholds: is provided mainly by amperimetric relays with two<br />
■an low immediate threshold high acts threshold on downstream acts on upstream faults. or internal transformer faults.<br />
■must Different take threshold transformer settings:<br />
account. switching, load current and fault current peaks into<br />
■for and downstream the downstream protection protection is ensured. device so that selectivity between upstream<br />
The ■thermal following image devices relays: are protection also used:<br />
■over<strong>voltage</strong> relays: protection against against over<strong>voltage</strong>, overloads and overheating,<br />
■earth ■tank protection overcurrent relays, relays,<br />
■restricted ■differential earth relays. relays,<br />
■<br />
TRANSFORMER<br />
WITHSTAND THE<br />
SWITCHING<br />
SHORT-CIRCUIT<br />
PEAKS<br />
SWITCHING CURRENT AND THE NO-LOAD<br />
The of the device short-circuit making current capacity (Ik2.5 must according be higher to than IEC or standard). equal to the peak value<br />
■<br />
(DOWNSTREAM<br />
BREAK NO-LOAD<br />
OPEN)<br />
CURRENTS WITHOUT EXCESSIVE OVERVOLTAGE<br />
The No-load transformer transformer insulation breaking may is be like damaged small inductive by over<strong>voltage</strong>. current breaking.<br />
peak value must be limited. The linking circuit between the device The over<strong>voltage</strong><br />
transformer plays an important role. The presence of cables (thus of and the<br />
capacitances) be checked. greatly reduces over<strong>voltage</strong>. Insulation co-ordination must<br />
Such value over<strong>voltage</strong> accepted by must standards. not be higher than 3.5 pu (1 pu =Ur3 2 ) , general<br />
SF6 breaking devices are particularly well adapted to this utilization.<br />
date<br />
11/94<br />
- B•3•2 -<br />
revised<br />
05/2004<br />
page 6
@@@@@@@@e<br />
@@@@@@@@<br />
@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e<br />
@@@@@@@@<br />
@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e<br />
@@@@@@@@e<br />
@@h<br />
@@h<br />
@@h<br />
@@h<br />
@@h<br />
@@h<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@g<br />
@@g<br />
@@g<br />
@@g<br />
@@g<br />
@@g<br />
@@@@@@@@<br />
@@@@@@@@<br />
@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@<br />
@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@@@@@@@<br />
@@@@@@@@<br />
<strong>Medium</strong> <strong>voltage</strong> <strong>switchgear</strong> <strong>application</strong> <strong>guide</strong><br />
2 - MOTOR 2 - 1 Switchgear to be used<br />
A fused contactor, contactor and circuit breaker are usually used<br />
for operating and protecting motors.<br />
M M M<br />
type power or current controlled by<br />
asynchronous I < 200 A fused contactor<br />
I < 315 A<br />
contactor<br />
P < 2 MW<br />
circuit breaker<br />
synchronous P ≥ 2 MW circuit breaker<br />
The fused operating contactor rate is is high, used to operate the motor when:<br />
■the power operating is low <strong>voltage</strong> (P < 1,500 is lower kW), than or equal to 11 kV.<br />
The short-circuit fuse breaks power. short-circuit currents generated by the upstream network<br />
The circuit operate breaker rate is is low, used to operate the motor when:<br />
■the power operating is high <strong>voltage</strong> (I > 315 is higher A), than 12 kV.<br />
2 - 2 Device characteristics<br />
date<br />
11/94<br />
- B•3•2 -<br />
revised<br />
05/2004<br />
The control and/or protection device must be able to:<br />
■ withstand and operate continuous operating current,<br />
■ break the fault current,<br />
■ withstand the short-circuit fault current (I k ),<br />
■ break currents during starting without excessive over<strong>voltage</strong>.<br />
THE DEVICE MUST BE ABLE TO:<br />
■<br />
The<br />
WITHSTAND<br />
device must<br />
AND<br />
be dimensioned<br />
OPERATE THE<br />
to<br />
OPERATING<br />
be able to withstand<br />
CURRENT<br />
current.<br />
the motor load<br />
The rated current Ir is given in the following equation:<br />
Ir (A) = U cos = ϕ= phase motor phase power <strong>voltage</strong> factor in kV<br />
3<br />
P (in kW)<br />
• U • cos ϕ•η<br />
η= motor output<br />
Example:1160 kW motor under 6.6 kV; cos ϕ = 0.92; η = 0.94<br />
I (A) = 3<br />
P (in kW)<br />
• U • cos<br />
■fused We shall contactor: choose:<br />
= 3 1160<br />
ϕ•η • 6.6 • 0.92 • 0.94 = 117.35 A<br />
■circuit breaker: 400 200 A. A or 250 A<br />
page 7
<strong>Medium</strong> <strong>voltage</strong> <strong>switchgear</strong> <strong>application</strong> <strong>guide</strong><br />
2 - MOTOR(cont’d) ■ BREAK FAULT CURRENTS<br />
fuse time-current curve<br />
t<br />
125 150 200 250<br />
t d<br />
I<br />
I d I dm<br />
date<br />
11/94<br />
- B•3•2 -<br />
revised<br />
05/2004<br />
When capacity a fused must contactor be compatible is used with as the a control need arising device, from the co-ordination contactor breaking<br />
the fuse and the different protective mechanisms. with<br />
The short-circuit fuse breaking current capacity possible. must be higher than or equal to the maximum<br />
When breaking a circuit capacity breaker must or be a higher contactor than alone the maximum is used as short-circuit a control device, current its<br />
possible.<br />
The<br />
Fuse<br />
specific<br />
protection<br />
motor which<br />
type<br />
they must<br />
of stress<br />
protect<br />
that<br />
and<br />
the fuses<br />
the network<br />
must withstand<br />
on which<br />
comes<br />
it is located.<br />
from the<br />
■stress ■rated current due to (Ir) the motor<br />
■starting current time Id(Id= 6 to 7 Ir for direct starting)<br />
tddepends on the<br />
td<br />
■the number of consecutive motor (values startings. between 1 and 30 seconds)<br />
■stress ■rated <strong>voltage</strong> due to the (< 11 network<br />
■prospective short-circuit kV). Only current. fuses with Ur ≤12 kV are used<br />
■choice ■ideal starting of fuse current characteristics<br />
The ideal starting current calculation Idmis equal<br />
(Idm)<br />
2.4 Idif the ratio Id/ to:<br />
- 2 Idif the ratio Id/<br />
Ir given by the manufacturer is a design value<br />
This Idmvalue guarantees<br />
Ir given two by consecutive the manufacturer start-ups is or a measured six start-ups value.<br />
intervalsper hour.<br />
at regular<br />
■to record determine the Idmand the fuse starting rating<br />
shown in figure 1 time value on the fuse time-current curve as<br />
intersection - choose the value immediately higher than the Idmand tdright angle<br />
On When figure the 1, fused the fuse contactor rating is to installed be taken in is the 250 cubicle, A.<br />
by 20%.<br />
Idmmust be increased<br />
The Circuit motors breaker are protected protection<br />
■thermal image against overloads, by the following protection devices:<br />
■independent ■earth overcurrent time for overcurrent insulation for faults, short-circuits,<br />
inverse ■against component slow start-ups maximum and rotor-locking. for unbalance,<br />
The under<strong>voltage</strong> motors must relay. be Ingeneral, protected against a single <strong>voltage</strong> relay is drops installed by on a time-delay<br />
carries out load shedding to all the associated devices. the busbar and<br />
page 8
<strong>Medium</strong> <strong>voltage</strong> <strong>switchgear</strong> <strong>application</strong> <strong>guide</strong><br />
2 - MOTOR(cont’d) ■ WITHSTAND THE FAULT SWITCHING CURRENT (Ik)<br />
The equal contactor to the peak or circuit short-circuit breaker current making value. capacity It is equal must be to 2.5 higher Ikaccording than to the IEC.<br />
■<br />
The<br />
BREAK<br />
motors are<br />
CURRENTS<br />
sensitive<br />
DURING<br />
to over<strong>voltage</strong><br />
STARTING<br />
since,<br />
WITHOUT<br />
for technological<br />
EXCESSIVE<br />
reasons,<br />
OVERVOLTAGE<br />
are not as well insulated. The <strong>switchgear</strong> operation creates an over<strong>voltage</strong> they<br />
insulation for each start-up. which cause Repeated it to wear over<strong>voltage</strong> down prematurely, creates weak if not points destroy in the it. turn<br />
Devices and do not using need the motor SF6 technique protection do devices. not generate dangerous over<strong>voltage</strong><br />
Rotating devices are arc likely techniques to provoke should higher be kept currents if they than work the well. rotating Puffer arc technique<br />
therefore more dangerous over<strong>voltage</strong> (see“selling points” folder, and<br />
over<strong>voltage</strong> file).<br />
date<br />
11/94<br />
- B•3•2 -<br />
revised<br />
05/2004<br />
page 9
<strong>Medium</strong> <strong>voltage</strong> <strong>switchgear</strong> <strong>application</strong> <strong>guide</strong><br />
3 - CAPACITOR 3 - 1 Switchgear to be used<br />
A fuse-switch combination, fused contactor, circuit-breaker-switch<br />
and circuit breaker are usually used for operating and protecting<br />
capacitor banks.<br />
type power I capacitance current<br />
(1) controlled by<br />
delta P ≤ 1050 kvar I ≤ 240 A fused contactor<br />
connection U ≤ 11 kV I ≤ 160 A ISF1circuit-breaker-switch<br />
bank<br />
I ≤ 60 A<br />
SM6 fixed fused<br />
switch-disconnector<br />
star 600 ≤ P ≤ 1050 kvar I ≤ 160 A ISF1 circuit-breaker-switch<br />
connection 11.7 ≤ U ≤ 21.8 kV<br />
bank 1050 ≤ P ≤ 4200 kvar I ≤ 240 A fused contactor<br />
U ≤ 11 kV<br />
1050 ≤ P ≤ 4800 kvar I ≤ 160 A ISF1 circuit-breaker-switch<br />
U ≤ 21.8 kV<br />
1050 ≤ P ≤ 21000 kvar 440 A 630 A circuit breaker<br />
U ≤ 21.8 kV 875 A 1250 A circuit breaker<br />
1750 A 2500 A circuit breaker<br />
2200 A 3150 A circuit breaker<br />
(1) capacitive current that the breaking device is capable of breaking<br />
The on and switch off during and the normal contactor running. make sure that the capacitor bank is switched<br />
The currents fuse-switch generated or fuse-contactor by the upstream combination network short-circuit make sure power that short-circuit<br />
General protection and breaking device with the required breaking are capacity broken.<br />
are The necessary circuit breaker even is if able capacitors make, are withstand designed and with break an operating internal fuse.<br />
well as short-circuit currents. Fault tripping is carried out automatically currents by theas<br />
protection The capacitor system banks (CT, are VT, either relay, mounted release, in etc.).<br />
bank (fig. 2). a single bank (fig. 1),or in multi steps<br />
The head<br />
multi<br />
circuit<br />
steps capacitor<br />
breaker ensuring<br />
bank with<br />
the<br />
the<br />
general<br />
following<br />
protection<br />
arrangement is often used:<br />
■a switch (ISF1)<br />
control each tap. or circuit breaker (if the number of operations is low)<br />
fig. 1: single bank<br />
fig. 2: automatic banks<br />
circuit breaker or<br />
fused contactor<br />
switch<br />
or<br />
circuit breaker<br />
date<br />
11/94<br />
- B•3•2 -<br />
revised<br />
05/2004<br />
banks with delta<br />
or double star connections<br />
banks with delta<br />
or double star connections<br />
page 10
@@@@@@@@e<br />
@@@@@@@@<br />
@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e<br />
@@@@@@@@<br />
@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e<br />
@@@@@@@@e<br />
@@h<br />
@@h<br />
@@h<br />
@@h<br />
@@h<br />
@@h<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@g<br />
@@g<br />
@@g<br />
@@g<br />
@@g<br />
@@g<br />
@@@@@@@@<br />
@@@@@@@@<br />
@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@<br />
@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@@@@@@@<br />
@@@@@@@@<br />
<strong>Medium</strong> <strong>voltage</strong> <strong>switchgear</strong> <strong>application</strong> <strong>guide</strong><br />
3 - CAPACITOR(cont’d) 3 - 2 Device characteristics<br />
date<br />
11/94<br />
- B•3•2 -<br />
revised<br />
05/2004<br />
The control and/or protection device must be able to:<br />
■ withstand the continuous operating current,<br />
■ break the fault current,<br />
■ withstand the network switching current and switching peaks<br />
generated when power to the capacitors is switched on,<br />
■ make and break without excessive over<strong>voltage</strong>.<br />
THE DEVICE MUST BE ABLE TO:<br />
■<br />
The<br />
WITHSTAND<br />
device must<br />
THE<br />
be dimensioned<br />
CONTINOUS OPERATING<br />
to be able to<br />
CURRENT<br />
capacitor bank rated current. withstand 1.43 times the<br />
The Irdevice rated = current Ircapacitor of the x device 1.1 x 1.3 is given = I capacitor by the following x 1.43 equation:<br />
1.3 currents. to take into account overheating due to the presence of harmonic<br />
1.1 The take rated into capacitive account current the tolerance must be over lower the than capacitance the capacitive value.<br />
the device is able to break (value given by the manufacturer). current that<br />
Irdevice Example:Ircapacitor = 100 A<br />
The = I capacitor x 1.43 = 100 •1.43 = 143 A<br />
than breaking 143 A. device must have a rated current value equal to or higher<br />
The following control devices are the ones we would choose:<br />
■for switch: ISF1 (Ibrokencapacitor =160 A)<br />
■a circuit a contactor: breaker Rollarc with a 630 (Ibrokencapacitor A rating (Ibrokencapacitor = 240 A) = 440 A).<br />
■<br />
The<br />
BREAK<br />
breaking<br />
THE<br />
capacity<br />
FAULT CURRENT<br />
maximum short-circuit current of the device possible. must be higher than or equal to the<br />
When be higher the device than the is current a fused limited contactor, by the the fuse. contactor breaking capacity must<br />
The<br />
Fuse<br />
fuse<br />
protection<br />
bank. This<br />
rating<br />
coefficient<br />
must be<br />
takes<br />
between<br />
into account<br />
1.7 and<br />
a<br />
1.9<br />
downgrading<br />
times the rated<br />
of 1.3<br />
current<br />
due to<br />
of<br />
the<br />
the<br />
Ircapacitor<br />
presence of<br />
x<br />
harmonic<br />
1.7 ≤Irfuse<br />
currents<br />
≤Ircapacitor<br />
and the derating<br />
x 1.9<br />
due to the inrush currents<br />
Protection against overloads must also be provided on each phase.<br />
Protection Circuit breaker against protection<br />
phase. short-circuits and overloads must be provided on each<br />
page 11
@@@@@@@@e<br />
@@@@@@@@<br />
@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e<br />
@@@@@@@@<br />
@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e<br />
@@@@@@@@e<br />
@@h<br />
@@h<br />
@@h<br />
@@h<br />
@@h<br />
@@h<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@g<br />
@@g<br />
@@g<br />
@@g<br />
@@g<br />
@@g<br />
@@@@@@@@<br />
@@@@@@@@<br />
@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@<br />
@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@@@@@@@<br />
@@@@@@@@<br />
<strong>Medium</strong> <strong>voltage</strong> <strong>switchgear</strong> <strong>application</strong> <strong>guide</strong><br />
3 - CAPACITOR(cont’d) ■<br />
The<br />
WITHSTAND<br />
making capacity<br />
THE SWITCHING<br />
of the device<br />
CURRENT<br />
greatest of the following values: must be equal to or higher than the<br />
■Ipnetwork ■bank switching (2.5 Ik<br />
current according Ie. to IEC)<br />
The bank switching current I e must always be less than I capacitor x 100.<br />
Otherwise arcing contact it must wear. be limited by installing dumpingreactors in order to reduce<br />
This current plays an important role in the mechanical endurance of the device.<br />
maximum<br />
Example:Rollarc<br />
number contactor, of operations<br />
Ir = : 400 300 A; 000 Ibrokencapacitor in mechanical latching. = 240 A;<br />
Imax.<br />
number<br />
switching<br />
of operations<br />
current: 8 kA at peak;<br />
The determination of switching<br />
Imax. switching<br />
current<br />
current=<br />
values 10,000. is given in appendix 3.<br />
■ MAKE AND BREAK WITHOUT EXCESSIVE OVERVOLTAGE<br />
If 1 pu =Ur<br />
the over<strong>voltage</strong> 3<br />
2<br />
single bank: must 2 not pu be higher than:<br />
■for a automaticbank (n identical taps):<br />
2 n 2 + n1 SF6 devices = pu<br />
are especially well adapted to this <strong>application</strong>.<br />
date<br />
11/94<br />
- B•3•2 -<br />
revised<br />
05/2004<br />
page 12
<strong>Medium</strong> <strong>voltage</strong> <strong>switchgear</strong> <strong>application</strong> <strong>guide</strong><br />
4 - GENERATOR 4 - 1 Switchgear to be used<br />
The control device usually used for operating and protecting<br />
generators is a circuit breaker.<br />
The ■low two power most station current generator uses for the protection generator circuit breaker are:<br />
In (generator/transformer practical cases, power set). station A VHV generators circuit breaker are built is used as self-contained to operate and units<br />
■protection them.<br />
circuits in the of event auxiliary of a generators distribution providing network failure. a power supply to priority<br />
In Its this characteristics case, the circuit are those breaker described used in as chapter a transformer 1 (transformer). protection incomer.<br />
power station generator<br />
G<br />
generator<br />
distributor power supply<br />
power<br />
generator<br />
G<br />
essential<br />
power supply<br />
MV circuit breaker<br />
LV<br />
transformer<br />
MV<br />
MV capacitors<br />
MV<br />
transformer<br />
VHV<br />
VHV circuit breaker<br />
VHV network<br />
4 - 2 Device characteristics<br />
date<br />
11/94<br />
- B•3•2 -<br />
revised<br />
05/2004<br />
When in use, the generator circuit breaker comes up against very<br />
different operating conditions. It must:<br />
■ withstand high load currents (overheating),<br />
■ break strong and highly asymmetrical fault currents which may<br />
be higher than 100% (generator terminal fault),<br />
■ close on very high currents generated by the asymmetry,<br />
■ withstand transient recovery <strong>voltage</strong> with highly increasing speeds,<br />
■ withstand phase displacement.<br />
DIFFERENT IN OPERATION, CONDITIONS THE GENERATOR OF RUNNING. CIRCUIT IT MUST BREAKER BE ABLE MEETS TO: VERY<br />
■<br />
The<br />
WITHSTAND<br />
rated current<br />
HIGH<br />
is given<br />
LOAD<br />
by<br />
CURRENTS<br />
the following equation: I ≥<br />
3 S<br />
• U<br />
page 13
@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e<br />
@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e @@@@@@@@<br />
@@@@@@@@<br />
@@@@@@@@e<br />
@@h<br />
@@h<br />
@@h<br />
@@h<br />
@@h<br />
@@h<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@g<br />
@@g<br />
@@g<br />
@@g<br />
@@g<br />
@@g<br />
@@@@@@@@<br />
@@@@@@@@<br />
@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@<br />
@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@@@@@@@<br />
@@@@@@@@<br />
<strong>Medium</strong> <strong>voltage</strong> <strong>switchgear</strong> <strong>application</strong> <strong>guide</strong><br />
4 - GENERATOR(cont’d) ■<br />
fig. 1: evolution of a generator<br />
short-circuit current<br />
I (kA)<br />
I dc<br />
t o<br />
time<br />
to = circuit breaker switching time<br />
+ relay time<br />
Iac aperiodic component<br />
Idc = component<br />
date<br />
11/94<br />
- B•3•2 -<br />
revised<br />
05/2004<br />
I ac<br />
BREAK HIGHLY ASYMMETRICAL FAULT CURRENTS<br />
When current a speed short-circuit is the one occurs represented on a network in figure close 1. to a generator the fault<br />
It values is essential at the moment to know the the evolution circuit breaker of the arcing short-circuit contacts current separate: and the<br />
aperiodic Current asymmetry<br />
(Idc) and can periodic reach<br />
(Iac)<br />
very component high values, value.<br />
which delays the natural passages of the current sometimes through zero higher that than are100%,<br />
In necessary highly asymmetrical for breaking.<br />
asymmetry for a total asymmetrical breaking, the current SF6 technique equal to is 2 times limited the to peak 100%<br />
symmetrical short-circuit current.<br />
•<br />
Iasym. =Isym. 1 + 2A2 with A = % asymmetry =Idc 100<br />
The or equal breaking to the capacity maximum of short-circuit the generator current circuit possible. breaker<br />
Iac peak<br />
must be higher than<br />
The value short-circuit to be taken current into supplied account is by the the greatest network, of:<br />
■the asymmetrical current of the generator at the moment the contacts open.<br />
is<br />
Example:when<br />
29 kA with 80% the asymmetry contacts separate, at the periodic short-circuit current<br />
to<br />
Asymmetrical current = Isym.•<br />
29 •1.35<br />
1<br />
=<br />
+ 2A2<br />
39.15<br />
=<br />
kA<br />
29 • 1 + 2 80% 2<br />
We The short-circuit current supplied by the network is 25 kA.<br />
If shall choose a circuit breaker with a breaking capacity equal to 40 kA.<br />
the the breaking capacity required is higher than the breaking capacity of<br />
order device, one solution consists in delaying circuit breaker switching in<br />
open due to avoid to a an fault. overly high asymmetry when the circuit breaker has to<br />
■<br />
The<br />
SWITCHING<br />
making capacity<br />
WITH<br />
must<br />
VERY<br />
be<br />
HIGH<br />
higher<br />
CURRENTS<br />
short-circuit current made. than or equal to the peak value of the<br />
The ■2.5 value times to the be breaking taken into capacity account of is the the circuit greatest breaker, of the following:<br />
asymmetry ■the peak value of the of generator the short-circuit current (figure current, 1). taking into account the<br />
■<br />
The<br />
INVERSION<br />
short-circuit<br />
OPERATION<br />
breaking capacity current given value by the in manufacturer phase inversion of the must circuit be lower breaker. than the<br />
■<br />
The<br />
TRANSIENT<br />
TRV values<br />
RECOVERY<br />
as well as the<br />
VOLTAGE<br />
TRV increase<br />
VALUES<br />
time<br />
(TRV)<br />
the circuit breaker in all types of situations (see circuit must breaker be compatible technical with<br />
<strong>guide</strong> § 5.11).<br />
page 14
<strong>Medium</strong> <strong>voltage</strong> <strong>switchgear</strong> <strong>application</strong> <strong>guide</strong><br />
4 - GENERATOR(cont’d) 4 - 3 Characteristics required for the determination<br />
of a generator circuit breaker<br />
must To be be able satisfied: to select a generator circuit breaker, the following characteristics<br />
■the ■generator rated current power in in MVA continous or kVA, operation<br />
■operating ■generator <strong>voltage</strong> rated current. in kV,<br />
short-circuit asymmetrical symmetrical current and current the continuous rms kA<br />
closing current in peak kA component value<br />
rated peak value withstand of the current TRV (in (rms peak kA/1 kA) s)<br />
■the rated operating cycle (O- 3 mn - CO as - well 3 mn as - the CO increase advised). time in µs<br />
The following generator values circuit are breaker known: can operate in phase inversion which implies<br />
■the short-circuit peak value TRV current, and increase time.<br />
date<br />
11/94<br />
- B•3•2 -<br />
revised<br />
05/2004<br />
page 15
<strong>Medium</strong> <strong>voltage</strong> <strong>switchgear</strong> <strong>application</strong> <strong>guide</strong><br />
5 - CABLES OR<br />
CABLES/LINES<br />
5 -1 Switchgear to be used<br />
A switch, fused switch-disconnector and circuit breaker are usually<br />
used to operate and protect lines and cables.<br />
lines feeder<br />
MV busbars<br />
lines incomer<br />
MV upstream busbars<br />
MV downstream busbars<br />
type current controlled by<br />
cables I ≤ 630 A switch<br />
I ≤ 200 A<br />
I ≤ 3150 A<br />
5 - 2 Device characteristics<br />
fused switch-disconnector<br />
circuit breaker<br />
The operating and/or protection device must be able to:<br />
■ carry the load current,<br />
■ withstand the short-circuit current,<br />
■ break the fault current if the device is an incomer,<br />
■ operate weak currents (no-load cables or lines) without<br />
excessive over<strong>voltage</strong>.<br />
THE DEVICE MUST BE ABLE TO:<br />
■<br />
The<br />
CARRY<br />
rated current<br />
THE LOAD<br />
depends<br />
CURRENT<br />
receivers installed on the outlet directly feeder. on the supply power and <strong>voltage</strong> of the<br />
Installed power: S = U I3 ⇒ I = US3<br />
date<br />
11/94<br />
- B•3•2 -<br />
revised<br />
05/2004<br />
page 16
<strong>Medium</strong> <strong>voltage</strong> <strong>switchgear</strong> <strong>application</strong> <strong>guide</strong><br />
5 - CABLES OR<br />
CABLES/LINES(cont’d)<br />
■<br />
The<br />
BREAK<br />
breaking<br />
THE<br />
capacity<br />
INSTALLATION’S<br />
must be higher<br />
FAULT<br />
than<br />
CURRENTS<br />
circuit current possible at the installation point. or equal to the maximum short-<br />
If the device is used as an incomer<br />
The circuit breaking current capacity possible must at the be installation higher than point. or equal to the maximum short-<br />
The on the short-circuit type and current section limited of the conductors. by the overhead or underground link depends<br />
Ik = 3 U•Zk ■for X 0.4 an ohm/km overhead = U<br />
3 • R2 +X2<br />
link<br />
R = ρL<br />
Three-phase ■for an S with ρ= 3.310-6 ohm cm2<br />
underground cables: link<br />
for Almelec<br />
Single-phase R = ρL cables: X = 0.1 0.1 to to 0.15 0.20 ohm/km ohm/km<br />
S with ρ=2.810-6 ρ=1.810-6 ohm ohm cm2<br />
cm2<br />
for copper<br />
for aluminium<br />
If the device is used as an outlet<br />
The protection switch device does not located have upstream a short-circuit which current provides breaking protection capacity. against It is shortcircuits.<br />
the<br />
the It must time however needed be to eliminate able to withstand it. the short-circuit current induced for<br />
If or protection the fuse-switch against combination short-circuits must is required be used. the fused switch-disconnector<br />
the The short-circuit breaker current must at have the connection a breaking capacity point. higher than or equal to<br />
■<br />
Applying<br />
OPERATE<br />
<strong>voltage</strong><br />
WEAK<br />
to a<br />
CURRENTS<br />
no-load line<br />
WITHOUT<br />
can be<br />
EXCESSIVE<br />
compared<br />
OVERVOLTAGE<br />
to capacitor switching.<br />
date<br />
11/94<br />
- B•3•2 -<br />
revised<br />
05/2004<br />
page 17
@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e<br />
@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e @@@@@@@@<br />
@@@@@@@@<br />
@@@@@@@@e<br />
@@h<br />
@@h<br />
@@h<br />
@@h<br />
@@h<br />
@@h<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@g<br />
@@g<br />
@@g<br />
@@g<br />
@@g<br />
@@g<br />
@@@@@@@@<br />
@@@@@@@@<br />
@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@<br />
@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@@@@@@@<br />
@@@@@@@@<br />
<strong>Medium</strong> <strong>voltage</strong> <strong>switchgear</strong> <strong>application</strong> <strong>guide</strong><br />
6 - ARC FURNACES 6 - 1 Switchgear to be used<br />
The ISF2 switch-circuit breaker was designed for arc furnace <strong>application</strong>.<br />
The maximum characteristics of the ISF2 are given in the table below.<br />
max. <strong>voltage</strong> max. load breaking no. of daily<br />
power current capacity operations<br />
180 MVA 40.5 kV<br />
156 MVA 36 kV 2500 A 20 kA 200<br />
104 MVA 24 kV<br />
6 - 2 Device characteristics<br />
date<br />
11/94<br />
- B•3•2 -<br />
revised<br />
05/2004<br />
The switch must be able to:<br />
■ operate the load current,<br />
■ break the installation’s short-circuit currents,<br />
■ operate weak currents (no-load transformer) without<br />
excessive over<strong>voltage</strong>,<br />
■ carry out a large number of operations.<br />
THE DEVICE MUST BE ABLE TO:<br />
■<br />
The<br />
OPERATE<br />
rated current<br />
THE<br />
depends<br />
LOAD CURRENT<br />
Furnace power: S = U I 3<br />
directly on the furnace supply <strong>voltage</strong> and power.<br />
⇒ I =<br />
S: U: apparent primary <strong>voltage</strong> power of of furnace US3<br />
transformer<br />
Example:<br />
Furnace Supply <strong>voltage</strong>: power: 30 100 kVMVA<br />
I = US3 = 30100<br />
• 3 •10 3 = 1924 A<br />
■ BREAK THE SHORT-CIRCUIT CURRENTS<br />
furnace switch current must may be able be calculated to break the in electrode a perfectly short-circuit general way. current.<br />
The short-circuit impedance is essentially due to the LV links.<br />
Zk LV = 2.510-3 Ω whatever the furnace size is<br />
The primary short-circuit power is:<br />
Sk MV=UMV •Ik MV• 3 andUMV=Zk •Ik<br />
The primary short-circuit current is:<br />
Ik MV = UMV withZk MV = UMV<br />
3 •Zk MV<br />
Ik MV =UMV (ULV)2<br />
3 1<br />
•<br />
(UMV)2 • Zk LV<br />
ULV 2 • Zk LV<br />
page 18
@@@@@@@@e<br />
@@@@@@@@<br />
@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e<br />
@@@@@@@@<br />
@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e<br />
@@@@@@@@e<br />
@@h<br />
@@h<br />
@@h<br />
@@h<br />
@@h<br />
@@h<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@g<br />
@@g<br />
@@g<br />
@@g<br />
@@g<br />
@@g<br />
@@@@@@@@<br />
@@@@@@@@<br />
@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@<br />
@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@@@@@@@<br />
@@@@@@@@<br />
<strong>Medium</strong> <strong>voltage</strong> <strong>switchgear</strong> <strong>application</strong> <strong>guide</strong><br />
6 - ARC FURNACES<br />
(cont’d)<br />
■<br />
OVERVOLTAGE<br />
OPERATE TRANSFORMER NO-LOAD CURRENTS WITHOUT EXCESSIVE<br />
In transformer: the melting 50% process of the (see case appendix upon opening 6) a and switch 90% operates of the case with upon the no-load closing.<br />
Operating This over<strong>voltage</strong> over<strong>voltage</strong> arises must during be furnace limited when transformer the arc operation. furnace is It installed.<br />
to the progressive destruction of the transformer’s internal insulation contributes<br />
reduces its lifespan.<br />
and<br />
The (installation network of must over<strong>voltage</strong> be adapted protection to the breaking capacitors device’s for example). characteristics<br />
With The means SF6 technology of limiting operating over<strong>voltage</strong> over<strong>voltage</strong> are simple. is low.<br />
A simple RC circuit placed upstream of the furnace transformer is sufficient.<br />
■<br />
In the<br />
MECHANICAL<br />
melting process<br />
AND ELECTRICAL<br />
a switch operates:<br />
ENDURANCE<br />
with currents between 0.8 Iloadand 2.6 Iloadand<br />
50% of 90% the case of the upon case opening<br />
closing with load currents of 2.5 upon<br />
Iload<br />
The mechanical endurance of the ISF2 is 50,000 operations.<br />
The supplying electrical the endurance furnace transformer depends during on the the average process value and of the the number current<br />
operations carried out under this current. of<br />
The load expected current is lifespan given by of the the curve poles below. (number of CO cycles) depending on the<br />
the expected lifespan of the poles<br />
(number of FO cycles)<br />
Example:for<br />
supplied by a 52 an MVA arc furnace<br />
in accordance with the load current<br />
under 30 kV with a load transformer<br />
cycles<br />
1000 A, the expected lifespan current<br />
50,000<br />
(or of an 50,000 ISF2 is CO 25,000 cycles CO if the cycles<br />
45,000<br />
set is replaced). pole<br />
40,000<br />
35,000<br />
30,000<br />
25,000<br />
0<br />
1<br />
2<br />
20,000<br />
15,000<br />
10,000<br />
5,000<br />
I (A)<br />
date<br />
11/94<br />
- B•3•2 -<br />
revised<br />
05/2004<br />
500 1,000 1,500 2,000 2,500<br />
0 curve without replacement of the poles<br />
1 curve with 1 replacement of the poles<br />
2 curve with 2 replacements of the poles<br />
page 19
<strong>Medium</strong> <strong>voltage</strong> <strong>switchgear</strong> <strong>application</strong> <strong>guide</strong><br />
7 - APPENDICES Appendix 1: transformer<br />
Appendix 2: motor<br />
Appendix 3: capacitor<br />
Appendix 4: generator<br />
Appendix 5: cables<br />
Appendix 6: alternating current melting arc furnaces<br />
Appendix 7: diode and thyristor <strong>application</strong>s<br />
Appendix 8: fused switch-disconnector or fused contactor<br />
date<br />
11/94<br />
- B•3•2 -<br />
revised<br />
05/2004<br />
page 20
<strong>Medium</strong> <strong>voltage</strong> <strong>switchgear</strong> <strong>application</strong> <strong>guide</strong><br />
Appendix 1:<br />
transformer<br />
A transformer is defined by its rated power, its rated primary and<br />
secondary currents, its rated primary and secondary <strong>voltage</strong>s, its<br />
insulation level, its short-circuit <strong>voltage</strong> and its coupling.<br />
The peak-switching current is also a parameter that should not be<br />
forgotten in the determination of protective <strong>switchgear</strong>.<br />
1 - RATED POWER<br />
The<br />
S = U<br />
rated power (S in kVA or MVA) of a transformer is equal to:<br />
• 3 • I r<br />
2 - RATED CURRENT OF ONE WINDING<br />
The rated current Inis equal to:<br />
I r = 3 S •U<br />
3 - RATED VOLTAGE AND INSULATION LEVEL OF ONE WINDING<br />
This in “no-load” is the specified operating <strong>voltage</strong> between to be the applied terminals (primary) of one or transformer developed (secondary)<br />
The rated primary <strong>voltage</strong> must be higher than or equal to that of the winding. network.<br />
rated<br />
<strong>voltage</strong><br />
U r (kV)<br />
insulation level<br />
rms kV (50 Hz - 1 mn) kV impulse (1.2/50 µs)<br />
7.2 20 60<br />
12 28 75<br />
17.5 38 95<br />
24 50 125<br />
36 70 170<br />
4 - SHORT-CIRCUIT VOLTAGE<br />
The short-circuit short-circuit current <strong>voltage</strong> to be (expressed calculated. in %) allows the transformer’s secondary<br />
The short-circuit current is given in the following equation:<br />
•<br />
I k =In<br />
Uk: Ir: rated<br />
U<br />
100<br />
short-circuit current<br />
k<br />
andP k =U r •I k • 3<br />
in <strong>voltage</strong> Ampsin %<br />
given The usual in the Ukvalues tables on depending the following on transformer page. <strong>voltage</strong> and power are<br />
The real values must be requested from the manufacturer.<br />
date<br />
11/94<br />
- B•3•2 -<br />
revised<br />
05/2004<br />
page 1
<strong>Medium</strong> <strong>voltage</strong> <strong>switchgear</strong> <strong>application</strong> <strong>guide</strong><br />
Appendix 1:<br />
transformer(cont’d)<br />
For a MV/LV transformer<br />
transformer<br />
no-load secondary <strong>voltage</strong><br />
power U k (% U k (%)<br />
(kVA) 410 V 237 V<br />
50 to 630 4 4<br />
800 4.5 5<br />
1000 5 5.5<br />
1250 5.5 6<br />
1600 6 6.5<br />
2000 6.5 7<br />
2500 7 7.5<br />
3150 7 7.5<br />
For a MV/MV transformer<br />
transformer U k primary secondary<br />
power <strong>voltage</strong> <strong>voltage</strong><br />
(MVA) (%) (kV) (kV)<br />
5 8 24 or 36 7.2 or 12 or 17.5 or 24<br />
10 9<br />
20 11<br />
25 12<br />
5 9 72.5 7.2 or 12 or 17.5 or 24<br />
10 9<br />
20 9.5<br />
25 9.5<br />
5 - COUPLING<br />
The ■the coupling respective is a connection conventional modes symbol of the indicating:<br />
■The angular gap between the two vectors high representing and low <strong>voltage</strong> the <strong>voltage</strong> windings,<br />
between the neutral point (real or ideal) and the corresponding high and values<br />
<strong>voltage</strong> terminals. This phase displacement is expressed by a time index. low<br />
connection HV LV<br />
mode symbol symbol<br />
delta D d<br />
star Y y<br />
zig-zag Z z<br />
neutral out N n<br />
To give low you powers an example, (25 to 160 the kVA): most Yzn11 widely or used Dyn11; couplings are the following:<br />
■for medium high powers: powers Yyn11, (250 Ydn11 kVA to or 3150 Dyn11. kVA): Dyn11;<br />
date<br />
11/94<br />
- B•3•2 -<br />
revised<br />
05/2004<br />
page 2
<strong>Medium</strong> <strong>voltage</strong> <strong>switchgear</strong> <strong>application</strong> <strong>guide</strong><br />
Appendix 1:<br />
transformer(cont’d)<br />
6 - SWITCHING CURRENT PEAK<br />
When peaks the are power produced. is switched on, very high signals or switching<br />
Ie<br />
I r<br />
date<br />
11/94<br />
- B•3•2 -<br />
revised<br />
05/2004<br />
transient state of the current during no-load transformer switching<br />
is They very may quickly be 14 absorbed. times greater The time than constant the rated of current. the damp This down switching depends current<br />
the winding resistance and the secondary load. The real values must beon<br />
requested from the manufacturer.<br />
Time constant and peak-switching current values depending on the immersed transformer power<br />
(high <strong>voltage</strong> switching).<br />
transformer<br />
power<br />
(kVA)<br />
n e = I e peak<br />
I r rms<br />
100 14 0.15<br />
160 12 0.20<br />
250 12 0.22<br />
400 12 0.25<br />
630 11 0.30<br />
800 10 0.30<br />
1000 10 0.35<br />
1250 9 0.35<br />
1600 9 0.40<br />
2000 8 0.45<br />
5000 8 0.50<br />
10000 8 0.50<br />
15000 8 0.50<br />
time<br />
constant<br />
(s)<br />
20000 8 0.50<br />
and In the the event time of constant low <strong>voltage</strong> divided switching, by 1.5 in the relation ratio neshould to the values be multiplied given in the by 2<br />
table These above.<br />
protection switching is defined. peaks must be taken into account when the type of<br />
The transformer may have its own optional devices.<br />
following: Depending on the type, the transformer’s own protective are the<br />
gas ■the leak, waterproof pressure protection and temperature unit for complete detector. filling transformer:<br />
■Buchholz gaz leak and protection pressure relay detector. for transformer fitted with a conservator:<br />
monitoring. ■thermostat, thermometer for immersed-type transformers: temperature<br />
■thermostatic probes for dry-type transformers: temperature control.<br />
t<br />
page 3
<strong>Medium</strong> <strong>voltage</strong> <strong>switchgear</strong> <strong>application</strong> <strong>guide</strong><br />
Appendix 2: motor<br />
A motor is defined by its mechanical power, its <strong>voltage</strong>, its<br />
insulation level, its starting type (torque, current, time) as well as<br />
1 - RATED POWER<br />
calculate A motor’s the power rated is the power mechanical by taking power the output which into it develops. account. We may<br />
The<br />
P = U<br />
rated power (P in kW) of a motor is equal to:<br />
• 3 •In •cos ϕ• η<br />
U: Ir: rated phase current to phase in Amps; <strong>voltage</strong> in V;<br />
cos ϕ: power factor (generally cos ϕ<br />
η: efficiency (generally η: 0.94 is used) = 0.92)<br />
2 - RATED CURRENT<br />
The rated current Iris equal to:<br />
I r = P<br />
3 •U •cos ϕ • η<br />
3 - RATED VOLTAGE AND INSULATION LEVEL<br />
The insulation rated level. <strong>voltage</strong> must be higher than that of the network as well as its<br />
rated insulation<br />
<strong>voltage</strong> level<br />
U r (kV) rms kV (50 Hz - 1 mn) impulse kV (1.2/50 µs)<br />
3 2 U + 1 kV * 4 U + 5 kV *<br />
3.3 2 U + 1 kV * 4 U + 5 kV *<br />
5 2 U + 1 kV * 4 U + 5 kV *<br />
6.6 2 U + 1 kV * 4 U + 5 kV *<br />
10 2 U + 1 kV * 4 U + 5 kV *<br />
11 2 U + 1 kV * 4 U + 5 kV *<br />
* for modern motors<br />
☞ note:the real values should be requested from the manufacturer.<br />
date<br />
11/94<br />
- B•3•2 -<br />
revised<br />
05/2004<br />
page4
<strong>Medium</strong> <strong>voltage</strong> <strong>switchgear</strong> <strong>application</strong> <strong>guide</strong><br />
Appendix 2: motor<br />
(cont’d)<br />
4 - DIFFERENT MEDIUM VOLTAGE MOTORS<br />
Alternating and 100 kW current to 40 MW medium ranges. <strong>voltage</strong> motors are situated in the2 kV to 14 kV<br />
The <strong>application</strong>s motors can are be given classed in the in table 4 families below. whose main characteristics and<br />
motor characteristics, advantages <strong>application</strong>s<br />
type<br />
drawbacks<br />
asynchronous ■ highly robust due to their ■ intensive use<br />
motors with simple construction ■ aggressive or<br />
single cage, ■ hardly any on-load speed dangerous atmosphere<br />
double cage,<br />
or deep slots<br />
variation<br />
■ high quantity of reactive power<br />
absorbed with weak load<br />
asynchronous ■ easy optimisation of starting ■ machines with high starting<br />
motors with torque or signal torque<br />
widing rotor ■ rotor resistances and rings needing ■ machine needing strong<br />
adjustment and maintenance<br />
counter-current breaking<br />
■ power factor usually<br />
■ tending to give way to<br />
lower than 0.9<br />
double cage motors<br />
synchronous ■ same technology as ■ P > to 2000 kW<br />
motors<br />
alternators<br />
■ high transient state<br />
■ good output and good power<br />
factor<br />
synchronised ■ mixture of two previous ones: ■ tending to disappear<br />
asynchronous good starting torque and good<br />
motors<br />
power factor<br />
■ complex starting co-ordination<br />
5 - DIFFERENT MV ASYNCHRONOUS MOTOR STARTING TYPES<br />
J L<br />
J C J L<br />
J C<br />
J N<br />
J L J L<br />
J R3<br />
M<br />
R 3<br />
J R2<br />
R 2<br />
J R1<br />
M<br />
M<br />
M<br />
R 1<br />
date<br />
11/94<br />
- B•3•2 -<br />
revised<br />
05/2004<br />
direct auto-transformer reactance rotors<br />
6 - ASYNCHRONOUS MOTOR CHARACTERISTICS<br />
Direct characteristics<br />
asynchronous starting<br />
<strong>voltage</strong><br />
are motors<br />
power<br />
The the most widely used.<br />
starting current<br />
influencing main characteristics motor operation no-load current<br />
are opposite. given in the table<br />
asynchronous motor<br />
2 kV to 14 kV<br />
100 kW to 40 MW<br />
6 to 7 times motor I n<br />
≈ 0.3 times motor I n<br />
starting current cos ϕ 0.1 to 0.2<br />
no-load current cos ϕ ≈ 0.1<br />
load current cos ϕ 0.7 to 0.9<br />
page 5
<strong>Medium</strong> <strong>voltage</strong> <strong>switchgear</strong> <strong>application</strong> <strong>guide</strong><br />
Appendix 3: capacitor<br />
A capacitor bank is defined by the power, the <strong>voltage</strong>, the insulation<br />
level and the rated current. Depending on the connection mode<br />
(single or multi-steps bank), the switching current is an important<br />
parameter which must be taken into account.<br />
1 - REACTIVE POWER<br />
The reactive power (Q in kvar or Mvar) of a capacitor bank is equal to:<br />
Q =Un • 3 •Ic orU r<br />
2 •C•ω<br />
Ur: Ic: rated rated current <strong>voltage</strong> or of current the bank absorbed network by the <strong>voltage</strong> capacitor of the network (kV)<br />
C: capacitance<br />
ω = 2 •π •ƒnetwork= network pulsation<br />
2 - RATED CURRENT<br />
The rated current Icis equal to:<br />
Ic = Qc<br />
3 •Un<br />
3 - RATED VOLTAGE<br />
The insulation rated level. <strong>voltage</strong> must be the same as that of the network as well as its<br />
rated <strong>voltage</strong><br />
U r (kV)<br />
insulation level<br />
rms kV (50 Hz - 1 mn) impulse kV (1.2/50 µs)<br />
7.2 20 60<br />
12 28 75<br />
17.5 38 95<br />
24 50 125<br />
36 70 170<br />
date<br />
11/94<br />
- B•3•2 -<br />
revised<br />
05/2004<br />
page 6
<strong>Medium</strong> <strong>voltage</strong> <strong>switchgear</strong> <strong>application</strong> <strong>guide</strong><br />
Appendix 3: capacitor<br />
(cont’d)<br />
date<br />
11/94<br />
- B•3•2 -<br />
revised<br />
05/2004<br />
4 - SWITCHING CURRENT<br />
The current switching of the capacitance. current must always be lower than 100 times the rated<br />
It is generally limited to 10 kA peak by impulse reactors.<br />
The switching current value depends on the type of bank used. It is equal to:<br />
1) for a single bank:<br />
Ie = 1<br />
L0 •C<br />
Ie =Ic • 2 •<br />
S •I L<br />
A B<br />
c • • 2 1ω<br />
I c<br />
k<br />
G<br />
U<br />
Ie: C: peak-switching capacitance of one current<br />
L0: network short-circuit tap<br />
Sk: supply short-circuit power reactor in MVA<br />
Qc: S capacitor = 3 •U •Isc bank with power U k<br />
3 =L0 in Mvar<br />
•Isc =U2<br />
• ω<br />
ω = 2 •π •ƒnetwork= network pulsation<br />
2) for a multi-steps bank with n identical steps:<br />
1 2 n + 1<br />
l l l<br />
C C C<br />
U: Ie: peak-switching network phase to current<br />
n: number of energized phase taps<strong>voltage</strong><br />
C: l: link capacitance reactor of one tap<br />
ω = 2 •π •ƒnetwork= network pulsation<br />
ƒinherent = 2<br />
1<br />
l • π • •C<br />
C<br />
L0 • ω<br />
Qc<br />
Ie =Ic • 2 •<br />
Ie = 2<br />
n + n1 ƒinherent<br />
3 •U •<br />
n + n<br />
• ƒnetwork<br />
1 c • l<br />
page 7
<strong>Medium</strong> <strong>voltage</strong> <strong>switchgear</strong> <strong>application</strong> <strong>guide</strong><br />
Appendix 4: generator<br />
A generator is defined by its power, its <strong>voltage</strong> and its internal<br />
impedance.<br />
1 - RATED POWER<br />
The<br />
S<br />
rated power (S in kVA or MVA) of a generator is equal to:<br />
In<br />
r = U • 3 •Ig<br />
large power stations, the power ranges between 500 and 1500 MVA<br />
2 - RATED CURRENT<br />
The rated current is equal toIg = 3<br />
S<br />
•U<br />
r<br />
3 - RATED VOLTAGE<br />
Generator standardised. <strong>voltage</strong> — contrary to distribution network <strong>voltage</strong> — is not<br />
There a variety of rated <strong>voltage</strong> values for generators.<br />
generator power<br />
(MVA)<br />
S n < 200 10 and 16<br />
200 - 400 14 and 21<br />
400 - 600 16 and 23<br />
600 - 1000 18 and 26<br />
S n > 1000 20 and 27<br />
generator rated <strong>voltage</strong><br />
(kV)<br />
4 - INTERNAL IMPEDANCE<br />
Manufacturers The resistance generally values are specify always generator negligible impedance before the reactance expressed values. in %.<br />
subtransient reactance reactance (X''d ≈20%),<br />
■the earth reactance (X'd ≈30%), (X'o ≈6%).<br />
These making values capacities will allow as well us to as determine protection the setting. circuit breaker breaking and<br />
Ik: (three-phase) short-circuit kA current<br />
Ur: Sr: generator generator rated rated power <strong>voltage</strong> (MVA)<br />
X'cc: transient reactance expressed (kV) in % by the manufacturer.<br />
date<br />
11/94<br />
- B•3•2 -<br />
revised<br />
05/2004<br />
I k = 3<br />
S<br />
•U<br />
r •<br />
r X' 1<br />
cc = 345<br />
•10 100 30 •<br />
= 8.66 kA<br />
page 8
@@@@@@@@e<br />
@@@@@@@@<br />
@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e<br />
@@@@@@@@<br />
@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e<br />
@@@@@@@@e<br />
@@h<br />
@@h<br />
@@h<br />
@@h<br />
@@h<br />
@@h<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@g<br />
@@g<br />
@@g<br />
@@g<br />
@@g<br />
@@g<br />
@@@@@@@@<br />
@@@@@@@@<br />
@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@<br />
@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@e@@@@@@@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@<br />
@@@@@@@@<br />
@@@@@@@@<br />
<strong>Medium</strong> <strong>voltage</strong> <strong>switchgear</strong> <strong>application</strong> <strong>guide</strong><br />
Appendix 5: cables<br />
MV cables<br />
single-pole cable<br />
individually screened<br />
three-pole cable<br />
screen<br />
belted three-pole cable<br />
conductor<br />
The purpose of all cable systems is to allow the transit of electrical<br />
energy which implies that in order to determine the system layout,<br />
it is necessary to know the following basic data:<br />
■ rated <strong>voltage</strong>,<br />
■ laying procedure,<br />
■ operating and short-circuit currents,<br />
■ conductor type.<br />
1 - RATED VOLTAGE<br />
The Uo: rms rated rated <strong>voltage</strong> power is defined frequency by <strong>voltage</strong> three values.<br />
the earth or the metal screen. between the phase conductor and<br />
U: Um: rms rms rated maximum power power frequency frequency <strong>voltage</strong> <strong>voltage</strong> between between two phase two phase conductors.<br />
Belted cables have the same phase to phase and phase to earth conductors.<br />
cables are only used for <strong>voltage</strong>s of 10 kV or less. insulation.<br />
These three values are written: Uo/U (Um) kV<br />
Example:<br />
individually belted cable: screened 6/6 (7.2) cable: kV 12/20 (24) kV<br />
2 - OPERATING AND SHORT-CIRCUIT CURRENT<br />
When temperature calculating at the the surface allowable of the current conductor for a and cable, screens the maximum must be allowable<br />
account:<br />
taken into<br />
cable, ■allowable its section permanent and how operating it is laid. temperature: this depends on the type of<br />
screens ■allowable (phase-earth short-circuit fault) current: must the be dimensioned conductor sections so that (phase the maximum fault) and<br />
temperatures circuit temperatures. reached during the fault remain below the allowable short-<br />
3 - CABLE-LAYING PROCEDURE<br />
The manufacturer characteristics correspond of allowable to specific steady ambient operating temperatures currents indicated and cable-laying by the<br />
conditions The ambient which temperatures are taken are as a sometimes reference.<br />
so that they heat each other or cool down with higher greater and the difficulty. links are often laid<br />
the So that currents allowable must be adjusted temperatures in accordance of the cable with constituents the installation are respected, conditions.<br />
date<br />
11/94<br />
- B•3•2 -<br />
revised<br />
05/2004<br />
page 9
<strong>Medium</strong> <strong>voltage</strong> <strong>switchgear</strong> <strong>application</strong> <strong>guide</strong><br />
Appendix 5: cables<br />
(cont’d)<br />
MV cables capacitance<br />
single-pole cable<br />
individually screened three-pole cable<br />
K<br />
C<br />
C<br />
C<br />
belted three-pole cable<br />
4 - TYPE OF CONDUCTOR<br />
A and cable mechanically is comprised united of either conductors. one conductor, or several electrically distinct<br />
The ■single-pole different types individually of cables screened insulated cables, by extruded solid dielectrics are:<br />
■individually ■belted three-pole screened cables. three-pole cables,<br />
■the The metal type part of metal: of the annealed conductor electrolytic is defined copper by:<br />
annealed aluminium, or 3/4 hard or sometimes<br />
■electric ■self-induction resistance coefficient per unit (L of in length H/km) (R which in ohm/km),<br />
geometrical size and the relative disposition of depends the conductors. essentially on the<br />
■the rated cables section capacitance. (mm2),<br />
5 - MV CABLES CAPACITANCE<br />
The capacitance of a cable depends on the construction type:<br />
■ single-pole<br />
cable capacitance<br />
cables:the<br />
C is that conductor measured is between surrounded the conductor by a screen and and the the<br />
which is earthed.<br />
screen<br />
■ individually screened three-pole<br />
by a screen and the cable capacitance<br />
cables:each<br />
is that measured conductor between is surrounded<br />
conductor and its individual screen which is earthed. each<br />
■ belted three-pole<br />
there is a capacitance<br />
cables:a<br />
K between screen conductors surrounds and a capacitance three conductors C between and<br />
a conductor and the screen which is earthed.<br />
Ic= The 3 capacitive C ωV which current causes Icof capacitance a network in C the only event to intervene of an earth whatever fault is:<br />
cable type.<br />
the<br />
In practice, C for for a star-connected individually screened capacitance, cables. the cable makers indicate:<br />
Upon ■the value request, 3 K the + C cable for belted maker cables.<br />
measured between the three inter-connected will tell you the conductors capacitance and the C2(C2= metal sleeve. 3 C)<br />
date<br />
11/94<br />
- B•3•2 -<br />
revised<br />
05/2004<br />
page 10
<strong>Medium</strong> <strong>voltage</strong> <strong>switchgear</strong> <strong>application</strong> <strong>guide</strong><br />
Appendix 6: alternating<br />
current melting arc<br />
furnaces<br />
1 - MELTING PROCESS<br />
Arc furnace operating principle<br />
The operations standard including processing scrap cycle metal of loading, an arc furnace melting, comprises liquid steel a refining series ofand<br />
casting.<br />
alternating current melting arc furnace<br />
scrap metal<br />
loading<br />
melting<br />
liquid bath<br />
refining<br />
casting of liquid<br />
steel in ladles<br />
and inter-casting<br />
intermediary<br />
reloading<br />
furnace ■scrap is metal stopped. loading For and a single intermediary processing loading cycle, is carried two or three out when basket the<br />
loads ■scrap are metal required.<br />
part of the energy melting is consumed. during which the solid load is liquefied and the main<br />
■liquid bath steel refining casting which in ladles only involves requires the thermal furnace loss tipping compensation.<br />
metal is poured from the furnace into the ladles and the time so needed that the for liquid<br />
furnace to return to its original position. the<br />
The ■frequent scrap metal arcing melting and arc period suppression is characterised at the beginning by:<br />
■strong current variations caused by arc displacement of during each the basket,<br />
period,<br />
melting<br />
■short-circuits, generated by the metal as it collapses.<br />
2 - OPERATING FREQUENCY<br />
The number of casts per day furnace: depends 13 on casts the type per of day. furnace.<br />
■furnace with refining in the ladle furnace: 22 casts per day.<br />
date<br />
11/94<br />
- B•3•2 -<br />
revised<br />
05/2004<br />
page 11
<strong>Medium</strong> <strong>voltage</strong> <strong>switchgear</strong> <strong>application</strong> <strong>guide</strong><br />
Appendix 6: alternating<br />
current melting arc<br />
furnaces(cont’d)<br />
3 - ELECTRICAL POWER SUPPLY<br />
The transformer) power supply or on must the factory be channelled distribution from network. the HV (with step-down<br />
The from power 15 to 40 available kV. varies from 10 to 100 MVA with <strong>voltage</strong> values ranging<br />
arc furnace power supply<br />
on the internal factory network<br />
MV (15 to 40 kV)<br />
4<br />
MV/LV<br />
1 2 3 1<br />
1 = disconnector<br />
2 = circuit breaker<br />
3 = switch<br />
4 = arrester<br />
5 = over<strong>voltage</strong> limiting capacitors<br />
6 = earth switch<br />
5 6<br />
furnace<br />
10 to 100 MVA<br />
The furnace switch controls all devices downstream of the transformer.<br />
For ≈8 operations an average per of 13 cast. casts per day the <strong>switchgear</strong> carries out:<br />
≈100 ≈30,000 operations operations per per day. year.<br />
<strong>voltage</strong> The furnace (15 to transformer, 40 kV) to pass located to the next low to <strong>voltage</strong> the furnace, used by allows the furnace intermediate<br />
1000 V).<br />
≈800 to<br />
date<br />
11/94<br />
- B•3•2 -<br />
revised<br />
05/2004<br />
page 12
<strong>Medium</strong> <strong>voltage</strong> <strong>switchgear</strong> <strong>application</strong> <strong>guide</strong><br />
Appendix 7: diode and<br />
thyristor <strong>application</strong>s<br />
MV circuit breaker<br />
MV<br />
transformer<br />
LV<br />
rectifier bridge<br />
The transformer’s type coupling determines the choice of the breaking<br />
device.<br />
through In a diode the or contactor thyristor <strong>application</strong>, the circuit the breaker shape located of the load upstream current of which the MV/LV goes<br />
rectifier transformer bridge is greatly and coupling. deformed. It depends on the transformer’s type of<br />
1 - SWITCHGEAR TO BE USED<br />
We have to consider two types of feeding:<br />
■ the feeding transformer has the same primary and secondary coupling.<br />
The primary and secondary currents have the same shape.<br />
M<br />
direct<br />
current motor<br />
d i /d t low<br />
All our devices can interrupt this type of current because the current<br />
passes through zero during long periods owing to the switching cycle.<br />
no specific recommandations<br />
■ the feeding transformer has a different coupling on the primary and the<br />
secondary.The primary current is shaped as a stair with a high value of the<br />
di/dtwhen the current reaches the zero<br />
d i /d t high value<br />
■ if the rectifier bridge is with diodes and if the number of operations is<br />
acceptable, the vaccum technology or the SF6 auto-expansion (LF) are OK.<br />
■ if the rectifier bridge is with thyristors:<br />
■ the puffer technology (SF) can be used without any particular precautions.<br />
■ the rotating arc technology (LF or Rollarc) can be used if any tripping<br />
commands are accompanied by a thyristor locking command.<br />
date<br />
11/94<br />
- B•3•2 -<br />
revised<br />
05/2004<br />
page 13
<strong>Medium</strong> <strong>voltage</strong> <strong>switchgear</strong> <strong>application</strong> <strong>guide</strong><br />
Appendix 7: diode and<br />
thyristor <strong>application</strong>s<br />
(cont’d)<br />
The information corresponding should be relay taken must directly be positively from its safe auxiliary and the contacts device’s (opening opening<br />
contact) operating and device. relayed as directly as possible to the thyristor trigger<br />
than In this the case, given the values. arc is maintained in the device as long as the di/dtis higher<br />
MV<br />
+ Vdc<br />
+ Vdc<br />
S4<br />
stop PB<br />
S4<br />
1 NC<br />
KM<br />
tripping<br />
- Vdc<br />
trip.<br />
KM<br />
1 NO<br />
MV side fault<br />
1 NC<br />
MV<br />
+ Vdc<br />
LV<br />
K1<br />
1 NO<br />
K1<br />
LV contactor<br />
- Vdc<br />
LV =<br />
M<br />
=<br />
The vaccum technology allows the breaking in every cases<br />
date<br />
11/94<br />
- B•3•2 -<br />
revised<br />
05/2004<br />
page 14
<strong>Medium</strong> <strong>voltage</strong> <strong>switchgear</strong> <strong>application</strong> <strong>guide</strong><br />
Appendix 8: fused<br />
switch-disconnector or<br />
fused contactor<br />
35<br />
21<br />
20<br />
I limited current<br />
(peak kA)<br />
250<br />
160<br />
This is a good association if the <strong>switchgear</strong> breaking capacity is<br />
higher than the rated breaking current of the fuse (I 3 ) and if the<br />
fuse is able to withstand the load current<br />
(generally I load ≤ I r fuse )<br />
2<br />
1 - SWITCHGEAR CHARACTERISTICS<br />
which The fused are: contactor co-ordination imposes two parameters on the contactor<br />
presence ■the maximum of the fault fuses. current that it is likely to break, taking into account the<br />
■the fuses electrodynamic which depend on withstands the prospective of the contactor short-circuit without current fuses value and and with<br />
rating.<br />
the<br />
The figure below illustrates the fused contactor association.<br />
example of characteristics required of contactor when protection is provided by an<br />
interior Fusarc type fuse (250 A /7.2 kV) installed on a 6.6 kV network with a prospective<br />
short-circuit current of 50 rms kA.<br />
I 1 : current giving<br />
maximum breaking<br />
capacity (50 rms kA)<br />
I sc : maximum network<br />
short-circuit current<br />
8.75<br />
I sc<br />
(rms kA)<br />
I limited<br />
(35 peak kA)<br />
I 3 : minimum breaking<br />
current (2,200 rms A)<br />
I r : rated current<br />
(250 rms A)<br />
electrodynamic withstand (1)<br />
(25 peak kA)<br />
breaking capacity<br />
(10 rms kA)<br />
I r (315 rms A)<br />
I load<br />
1 3.5 8 50<br />
limited broken current amplitude<br />
characteristics<br />
fuse characteristics<br />
contactor characteristics<br />
(1) A device that withstands 25 peak kA without a fuse could, if it had a fuse, withstands a fuse<br />
peak current of over 35 peak kA without being destroyed. In fact, contact repulsion takes place<br />
above 25 peak kA but the destructive effect is linked to the thermal constraint which is relatively<br />
weak in the case of fuses intervening in less than 10 ms.<br />
short-circuit The fuse must current not be is required the most to intervene equal to the in Irto I1of I3range. the fuse The used. network<br />
Rated <strong>voltage</strong> fuses matching the network <strong>voltage</strong> must be used.<br />
0<br />
date<br />
11/94<br />
- B•3•2 -<br />
revised<br />
05/2004<br />
page 15
<strong>Medium</strong> <strong>voltage</strong> <strong>switchgear</strong> <strong>application</strong> <strong>guide</strong><br />
Appendix 8: fused<br />
switch-disconnector or<br />
fused contactor (cont’d)<br />
2 - DEVICE FUNCTIONS<br />
Each associated element ensures different and complementary functions.<br />
The role of the switch or<br />
■make or break the load<br />
contactoris<br />
current, to:<br />
■break ■cause fault three-phase currents tripping which are as not a result high of enough fuse breaking. to melt the fuse,<br />
The role of the fuse is to:<br />
■break ■limit switching short-circuit currents currents,<br />
■steadily withstand the load (in the current event without of a fault excessive circuit being overheating produced),<br />
depending on the installation and/or operating conditions.<br />
date<br />
11/94<br />
- B•3•2 -<br />
revised<br />
05/2004<br />
page 16