SLUDGE THICKENER - Operation Manual - Stone Food Machinery
SLUDGE THICKENER - Operation Manual - Stone Food Machinery
SLUDGE THICKENER - Operation Manual - Stone Food Machinery
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Mariestad 20061109<br />
Level Controls for Sludge Water<br />
A level meter is placed in a pipe in the incoming sludge water and set at a level about 25 cm.<br />
The Exact level has to be adjusted, from experience, later. The level meter is used to interlock<br />
the sludge water pump to ensure the reject/waste water quality remains optimal in terms of<br />
Suspended Solids.<br />
As the pump is interlocked, the screen will continue to lift up the sludge and the pump will<br />
start when the right water level has been reached.<br />
Frequency Inverter<br />
The <strong>SLUDGE</strong> <strong>THICKENER</strong> is controlled by a Frequency Inverter with the ability to adjust<br />
the screen speed and therefore the Sludge Solids.<br />
Regulation of Dry Solids content<br />
• The variation of the Screen`s speed is used to adjust the content of dry solids in the<br />
thickened sludge.<br />
• High volumes of incoming sludge water and high speed gives a LOWER content of<br />
dry solids.<br />
• LOWER volumes of sludge water and LOW Screen speed gives a HIGHER content of<br />
solids.<br />
• The same polymer dosing can be used.<br />
• The regulation can also be done by advance knowledge of the solid contents and the<br />
quality of the incoming sludge water. Less solids gives a higher frequency and a<br />
higher speed and vice versa.<br />
<strong>Operation</strong> time<br />
<strong>Operation</strong> time depends on the load on the screen, the amount of suspended solids in the<br />
incoming sludge water and desired content of solids in the final thickened sludge. Effective<br />
use is reached with an even covering of flocculated sludge over the entire screen surface.<br />
Polymer<br />
The polymer dose is best set by eye. Clear water should be seen between the sludge flocs. If<br />
the polymer is added before the sludge pump there is enough flocculation in the pump and the<br />
Annika Kjellkvist<br />
Vatten och Miljöteknik 80 p<br />
KY-utb. Hallsberg<br />
2<br />
D:\EQUIPMENT-SUPPLIERS\Swedish\MEVA\BROCHURES\<strong>SLUDGE</strong> <strong>THICKENER</strong>\MANUAL\1-9-07-<br />
<strong>Operation</strong> <strong>Manual</strong> MST15.doc