Invento IFT Drives - Systemair
Invento IFT Drives - Systemair
Invento IFT Drives - Systemair
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
<strong>Invento</strong> EC Drive<br />
DOMEL<br />
Controller Configuration<br />
34<br />
35<br />
100<br />
101<br />
Speed output mode<br />
SO output signal<br />
0: disabled (input)<br />
1: 2..10V (1mA)<br />
2: FREQ(10V, 1mA)<br />
3: PWM(25mA)<br />
4: PWM(10V,1mA)<br />
5: 0..20mA<br />
6: 0..10V(1mA)<br />
7: 4..20mA<br />
8: FREQ(25mA)<br />
9: hhh<br />
>9: reserved<br />
2: reserved<br />
0…9<br />
-10000…2<br />
6<br />
1<br />
1<br />
0.01%<br />
W/1<br />
W/1<br />
/<br />
/<br />
7.1.4 Description of supported Input Registers:<br />
Input Registers<br />
36 1 EC drive type EC Drive type *1 NaN R/0 /<br />
37 2 Firmware version Software version *2 NaN R/0 /<br />
38 3 Required Speed Required speed in RPM 0 1 R/0 m in-1<br />
39 4 Speed Current speed in RPM 0 1 R/0 %<br />
40 5 Temperature Controller Temperature 0 0.1 R/0 °C<br />
41 6 DC Bus Voltage DC Bus Voltage in V 0 1 R/0 V<br />
42 7 AC voltage AC Voltag in V 0 0.1 R/0 V<br />
43 8 15V DC Voltage 15V Power supply in V 0 0.1 R/0 V<br />
44 9 Analog Input 1 Analog input 1 voltage -300..2000 0 0.01 R/0 V<br />
45 10 Analog Input 2 Analog input 2 voltage -300..2000 0 0.01 R/0 V<br />
46 11 Reserved<br />
47 12 SO voltage Speed Output output voltage -300..2000 0.01 R/0 V<br />
48 13 SO current Speed Output output current -300..3300 0.01 R/0 A<br />
49 14 R/0<br />
50 11 Minutes Operating minutes counter 0 - 1439 0 1 R/0 Minutes<br />
51 12 Day Operating days counter 0 - 65535 0 1 R/0 days<br />
52 13 FM_Min_Last<br />
Fire Mode function: Operating mi nutes<br />
counter (las t event)<br />
0 - 1439 0 1 R/0 m in<br />
53<br />
54<br />
14-18<br />
19<br />
Reserved for debug<br />
ErrorCode<br />
Red LED error codes (priority in the<br />
order below):<br />
7 = motor failed to start repeatedly<br />
6 = under or overvoltage<br />
5 = motor missconnected/faulty<br />
4 = internal frequency converter fault 0..7, -1 x 1<br />
R/0<br />
3 = temperature protection active<br />
2 = active overcurrent protection<br />
1 = slow blink=standby<br />
-1 = fast blink (fire activated)<br />
0 = always on (operating normally)<br />
55 20 FireMinutes Minutes under fire mode. 0-1439 1 R/0 m in<br />
56 21 FireDays Days under fire mode. 0 - 65535 1 R/0 days<br />
57 22 FireCycles Fire Mode function: Event counter 1 R/0<br />
58 23 OpMinutes Minutes of operation 1 R/0 m in<br />
59 24 OpDays Days of operation (RPM>0, no error) 0 - 65535 0 1 R/0 days<br />
60 25-30 Reserved<br />
Notes:<br />
*1: depends on the type of housing, max current<br />
*2: last version of firmware<br />
DOMEL – <strong>Invento</strong> <strong>IFT</strong> EC <strong>Drives</strong> – Operating instruction<br />
Version: V3.0, June2013<br />