<strong>Invento</strong> EC Drive<br />

DOMEL<br />

Controller Configuration<br />

34<br />

35<br />

100<br />

101<br />

Speed output mode<br />

SO output signal<br />

0: disabled (input)<br />

1: 2..10V (1mA)<br />

2: FREQ(10V, 1mA)<br />

3: PWM(25mA)<br />

4: PWM(10V,1mA)<br />

5: 0..20mA<br />

6: 0..10V(1mA)<br />

7: 4..20mA<br />

8: FREQ(25mA)<br />

9: hhh<br />

>9: reserved<br />

2: reserved<br />

0…9<br />

-10000…2<br />

6<br />

1<br />

1<br />

0.01%<br />

W/1<br />

W/1<br />

/<br />

/<br />

7.1.4 Description of supported Input Registers:<br />

Input Registers<br />

36 1 EC drive type EC Drive type *1 NaN R/0 /<br />

37 2 Firmware version Software version *2 NaN R/0 /<br />

38 3 Required Speed Required speed in RPM 0 1 R/0 m in-1<br />

39 4 Speed Current speed in RPM 0 1 R/0 %<br />

40 5 Temperature Controller Temperature 0 0.1 R/0 °C<br />

41 6 DC Bus Voltage DC Bus Voltage in V 0 1 R/0 V<br />

42 7 AC voltage AC Voltag in V 0 0.1 R/0 V<br />

43 8 15V DC Voltage 15V Power supply in V 0 0.1 R/0 V<br />

44 9 Analog Input 1 Analog input 1 voltage -300..2000 0 0.01 R/0 V<br />

45 10 Analog Input 2 Analog input 2 voltage -300..2000 0 0.01 R/0 V<br />

46 11 Reserved<br />

47 12 SO voltage Speed Output output voltage -300..2000 0.01 R/0 V<br />

48 13 SO current Speed Output output current -300..3300 0.01 R/0 A<br />

49 14 R/0<br />

50 11 Minutes Operating minutes counter 0 - 1439 0 1 R/0 Minutes<br />

51 12 Day Operating days counter 0 - 65535 0 1 R/0 days<br />

52 13 FM_Min_Last<br />

Fire Mode function: Operating mi nutes<br />

counter (las t event)<br />

0 - 1439 0 1 R/0 m in<br />

53<br />

54<br />

14-18<br />

19<br />

Reserved for debug<br />

ErrorCode<br />

Red LED error codes (priority in the<br />

order below):<br />

7 = motor failed to start repeatedly<br />

6 = under or overvoltage<br />

5 = motor missconnected/faulty<br />

4 = internal frequency converter fault 0..7, -1 x 1<br />

R/0<br />

3 = temperature protection active<br />

2 = active overcurrent protection<br />

1 = slow blink=standby<br />

-1 = fast blink (fire activated)<br />

0 = always on (operating normally)<br />

55 20 FireMinutes Minutes under fire mode. 0-1439 1 R/0 m in<br />

56 21 FireDays Days under fire mode. 0 - 65535 1 R/0 days<br />

57 22 FireCycles Fire Mode function: Event counter 1 R/0<br />

58 23 OpMinutes Minutes of operation 1 R/0 m in<br />

59 24 OpDays Days of operation (RPM>0, no error) 0 - 65535 0 1 R/0 days<br />

60 25-30 Reserved<br />

Notes:<br />

*1: depends on the type of housing, max current<br />

*2: last version of firmware<br />

DOMEL – <strong>Invento</strong> <strong>IFT</strong> EC <strong>Drives</strong> – Operating instruction<br />

Version: V3.0, June2013<br />

18