ALPIVAR 2 : CONNECTION AND PROTECTION DEVICES<br />
Connection<br />
The easy accessibility of the terminals on the top of the<br />
unit make the Alpivar 2 capacitor very easy to connect.<br />
The use of a system of "socket" terminals enables<br />
direct connection of the unit via cables and lugs.<br />
The Alpivar 2 double-insulated or class 2 capacitor<br />
does not need earthing.<br />
C onnection<br />
terminals<br />
Internal<br />
discharge<br />
resistor<br />
LOW VOLTAGE RANGE<br />
Electrical protection devices<br />
Self-healing dielectric: This self-healing property is<br />
connected with the characteristics of the metal deposit<br />
which forms the electrode and the nature of the<br />
insulating support (polypropylene film).<br />
This special manufacturing technique prevents<br />
breakdown of the capacitor due to electrical<br />
overvoltages. In fact overvoltages perforate the<br />
dielectric and cause discharges which vaporise the<br />
metal near the short circuit, thus instantaneously<br />
restoring the electrical insulation.<br />
Self-healing coil<br />
Self-extinguishing<br />
polyurethane resin<br />
vacuum coating<br />
Internal fuses: One per winding.<br />
Pressure monitoring devices: If an electrical fault<br />
cannot be overcome by the film self-healing or by<br />
means of the electric fuse, gas is emitted, causing<br />
a membrane to deform and disconnecting the faulty<br />
winding. The triggering of the pressure monitoring<br />
devices is visible from outside the capacitor. This<br />
feature makes it easy to carry out a quick check on the<br />
status of the unit.<br />
Self-extinguishing<br />
plastic casing<br />
These three protection devices, together with the<br />
vacuum coating of the windings (technique patented by<br />
LEGRAND), result in a very high-tech unit.<br />
Overpressure<br />
disconnection<br />
device with visible<br />
trip indication<br />
Electric fuse<br />