detuned reactors - product range (suite)<br />
INSTALLATION<br />
It will be responsibility of the installer to comply with the national and international installation standards<br />
The reactors operate properly only under the specified conditions:<br />
- Storage and transportation temperature : -25°C / +70 °C<br />
- Selection of the right type according to harmonic pollution<br />
- In operation an adequate air circulation has to be guaranteed<br />
- Windings must be installed vertically for better heat dissipation<br />
- The reactor must be protected against overloads and short-circuits by fuses and/or circuit breakers.<br />
- Suitable protection against undesired contacts (IP00) must be provided by means of enclosures or boxes protecting the power system where<br />
the reactor is installed<br />
- It is imperative to that the thermal N.C dry contact be connected in series with the contactor coil, in order to disconnect the step in case of<br />
overheating<br />
- This range of detuned reactors can not be connected with standard capacitors. It must be connected with appropriate H type capacitors<br />
selected by our service (see selection table)<br />
Available upon request :<br />
- Ambient temperature higher than 40°C<br />
- Other voltages (example 220V, 440V) lower than 1000V<br />
- Other frequencies (example 60Hz)<br />
- Other blocking factor p% : 5.67% ( tuning frequency 215Hz) - 13.7% ( tuning frequency 135Hz)<br />
TECHNICAL CHARACTERISTICS<br />
DETUNED THREE-PHASE REACTORS 400V, 50 Hz<br />
<br />
Standard Class designed for harmonic level 25% < SH/ST < 35%<br />
Q<br />
<br />
Capacitor part number<br />
Ln<br />
<br />
I RMS<br />
<br />
Part Number<br />
Ptot<br />
<br />
12.5 VH12.540 2.85 21 SAH-2.85-21 100<br />
25 VH2540 1.45 42 SAH-1.45-42 160<br />
50 VH5040 0.72 83 SAH-0.72-83 230<br />
75 VH7540 0.48 123 SAH-0.48-123 320<br />
<br />
Reinforced Class designed for harmonic level 35% < SH/ST < 50%<br />
Q<br />
<br />
Capacitor part number<br />
Ln<br />
<br />
I RMS<br />
<br />
Part Number<br />
Ptot<br />
<br />
20 VH2040 1.78 38 SAH-1.78-38 200<br />
40 VH4040 0.9 75 SAH-0.9-75 280<br />
80 VH8040 0.45 150 SAH-0.45-150 380<br />
Nota: If the ratio SH/ST is between the 2 values given in the table then you must select the most restricting alternative<br />
L<br />
C<br />
x 100)<br />
It is related to the resonance frequency (fris) of the system by the formula:<br />
fris = 50x<br />
100<br />
p%<br />
Q : compensation reactive power (KVAr)<br />
Ln : rated inductance, expressed in mH.<br />
I <br />
: current, expressed in A. It is given by the formula:<br />
2<br />
1<br />
2<br />
5<br />
2<br />
7<br />
I RMS<br />
= 1.075xI + I + I + ...<br />
where I 5<br />
is the rms value of the 5 th harmonic current, I 7<br />
of the 7 th harmonic…<br />
Ptot : total losses, including additional losses due to harmonics, expressed in W and referred to 75°C<br />