detuned reactors - product range (suite)<br />

INSTALLATION<br />

It will be responsibility of the installer to comply with the national and international installation standards<br />

The reactors operate properly only under the specified conditions:<br />

- Storage and transportation temperature : -25°C / +70 °C<br />

- Selection of the right type according to harmonic pollution<br />

- In operation an adequate air circulation has to be guaranteed<br />

- Windings must be installed vertically for better heat dissipation<br />

- The reactor must be protected against overloads and short-circuits by fuses and/or circuit breakers.<br />

- Suitable protection against undesired contacts (IP00) must be provided by means of enclosures or boxes protecting the power system where<br />

the reactor is installed<br />

- It is imperative to that the thermal N.C dry contact be connected in series with the contactor coil, in order to disconnect the step in case of<br />

overheating<br />

- This range of detuned reactors can not be connected with standard capacitors. It must be connected with appropriate H type capacitors<br />

selected by our service (see selection table)<br />

Available upon request :<br />

- Ambient temperature higher than 40°C<br />

- Other voltages (example 220V, 440V) lower than 1000V<br />

- Other frequencies (example 60Hz)<br />

- Other blocking factor p% : 5.67% ( tuning frequency 215Hz) - 13.7% ( tuning frequency 135Hz)<br />

TECHNICAL CHARACTERISTICS<br />

DETUNED THREE-PHASE REACTORS 400V, 50 Hz<br />

<br />

Standard Class designed for harmonic level 25% < SH/ST < 35%<br />

Q<br />

<br />

Capacitor part number<br />

Ln<br />

<br />

I RMS<br />

<br />

Part Number<br />

Ptot<br />

<br />

12.5 VH12.540 2.85 21 SAH-2.85-21 100<br />

25 VH2540 1.45 42 SAH-1.45-42 160<br />

50 VH5040 0.72 83 SAH-0.72-83 230<br />

75 VH7540 0.48 123 SAH-0.48-123 320<br />

<br />

Reinforced Class designed for harmonic level 35% < SH/ST < 50%<br />

Q<br />

<br />

Capacitor part number<br />

Ln<br />

<br />

I RMS<br />

<br />

Part Number<br />

Ptot<br />

<br />

20 VH2040 1.78 38 SAH-1.78-38 200<br />

40 VH4040 0.9 75 SAH-0.9-75 280<br />

80 VH8040 0.45 150 SAH-0.45-150 380<br />

Nota: If the ratio SH/ST is between the 2 values given in the table then you must select the most restricting alternative<br />

L<br />

C<br />

x 100)<br />

It is related to the resonance frequency (fris) of the system by the formula:<br />

fris = 50x<br />

100<br />

p%<br />

Q : compensation reactive power (KVAr)<br />

Ln : rated inductance, expressed in mH.<br />

I <br />

: current, expressed in A. It is given by the formula:<br />

2<br />

1<br />

2<br />

5<br />

2<br />

7<br />

I RMS<br />

= 1.075xI + I + I + ...<br />

where I 5<br />

is the rms value of the 5 th harmonic current, I 7<br />

of the 7 th harmonic…<br />

Ptot : total losses, including additional losses due to harmonics, expressed in W and referred to 75°C<br />